Omron 61F-GP-N8 - Manual Download Page 9

9

61F-GP-N

@

Compact Plug-in Models (8-pin Type)

Specifications

Note: 1.

The length when using completely-insulated, 600-V, 3-conductor (0.75 mm

2

) cabtire cables. Usable cable lengths will become shorter as

the cable diameter or number of conductors becomes larger.

2.

The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power ter-

minals and contact terminals, and between Electrode terminals and contact terminals.

3.

Possible to use with 15 k

Ω

 or less, however, this may cause reset failure.

4.

61F-GP-N8H/-N8Y High-sensitivity Controllers use advanced operation.

When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-

nal relay will not operate.

When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal

relay will operate. 

If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.

Item

General-purpose 

Controller

61F-GP-N8

61F-GP-N8Y

 (see note 4)

Long-distance 

Controllers

61F-GP-N8L 2KM 

(for 2 km)

61F-GP-N8L 4KM 

(for 4 km)

High-sensitivity 

Controllers

61F-GP-N8H

61F-GP-N8HY

(see note 4)

Low-sensitivity 

Controller

61F-GP-N8D

Two-wire 

Controller

61F-GP-N8R

Variable 

Sensitivity 

Controller

61F-GP-N8-V50

Controlling mate-

rials and operat-

ing conditions

For control of ordi-

nary purified water 

or sewage water

For control of ordi-

nary purified water 

in cases where the 

distance between 

sewage pumps and 

water tanks or be-

tween receiver 

tanks and supply 

tanks is long or 

where remote con-

trol is required.

For control of liq-

uids with high spe-

cific resistance 

such as distilled 

water

For control of liq-

uids with low spe-

cific resistance 

such as salt water, 

sewage water, acid 

chemicals, alkali 

chemicals

For control of ordi-

nary purified water 

or sewage water 

used in combina-

tion with Two-wire 

Electrode Holder 

(incorporating a re-

sistor of 6.8 k

Ω

)

For control of cases 

where variable sen-

sitivity control is re-

quired such as 

detection of froth on 

the surface of a liq-

uid, control of soil 

moisture content, 

or detection of de-

gree of water pollu-

tion

Supply voltage

24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz

24, 110, 220 or 

240 VAC; 50/60 Hz

Operating voltage 

range

85% to 110% of rated voltage

Interelectrode 

voltage

8 VAC

24 VAC

8 VAC

24 VAC

Interelectrode 

current

Approx. 1 mA AC max.

Approx. 

0.4 mA AC max.

Approx. 1 mA AC max.

Approx. 3 mA AC 

max.

Power consump-

tion

Approx. 3.5 VA max.

Interelectrode op-

erate resistance

0 to approx. 4 k

Ω

0 to 1.3 k

Ω 

(for 

2 km)

0 to 0.5 k

Ω 

(for 

4 km)

Approx. 15 k

Ω

 to 

approx. 70 k

Ω 

(see note 3)

0 to approx. 1.3 k

Ω

0 to approx. 2 k

Ω

0 to 50 k

Ω

 (Vari-

able)

Interelectrode re-

lease resistance

Approx. 15 k to 

∞ Ω

4 k to 

∞ Ω 

(for 2 km)

2.5 k to 

∞ Ω 

(for 4 km)

Approx. 300 k to 

∞ Ω

Approx. 4 k to 

∞ Ω

Approx. 15 k to 

∞ Ω

Operating resis-

tance +50 k

Ω

 max.

Response time

Operate: 80 ms max.

Release: 160 ms max.

Cable length 

(see note 1)

1 km max.

2 km max.

4 km max.

50 m max.

1 km max.

800 m max.

50 m max.

Control output

1 A, 250 VAC (Inductive load: cos

φ

 = 0.4)

3 A, 250 VAC (Resistive load)

Ambient tempera-

ture

Operating: –10 to 55

°

C

Ambient humidity

Operating: 45% to 85% RH

Insulation resis-

tance 

(see note 2)

100 M

Ω

 min. (at 500 VDC)

Dielectric 

strength 

(see note 2)

2000 VAC, 50/60 Hz for 1 min.

Life expectancy

Electrical:

100,000 operations min.

Mechanical: 5,000,000 operations min.

Weight

Approx. 155 g

Accessories

Hold-down clip PFC-N8

Approved stan-

dards

UL508, CSA C22.2 No.14, EN61010-1, EN61326-1 Industrial electromagnetic environment

Summary of Contents for 61F-GP-N8 -

Page 1: ...High sensitivity D Low sensitivity R Two wire T High temperature Refer to Safety Precautions for Floatless Level Controllers Position of LED indicator 2 1 61F GP Type General purpose Long distance fo...

Page 2: ...rature is high For control of ordi nary purified water in cases where the distance between sewage pumps and water tanks or between receiver tanks and supply tanks is long or where remote con trol is r...

Page 3: ...1F GP N NT NL ND 61F GP NR 61F GP NH 3 9 1 4 10 11 U 24 V 8 V Control circuit S0 S1 E3 5 E1 Ta1 Tc1 Tb1 8 6 7 U Ta2 Tc2 Tb2 3 9 1 4 10 11 U 24 V 8 V Control circuit S0 S1 E3 5 E1 Ta1 Tc1 Tb1 8 6 7 U T...

Page 4: ...mmercial Voltage 61F GP N PS 3S 3 9 E2 E3 E1 P 8 V 0 V U U U 24 V Control circuit See note 4 8 7 6 5 10 11 1 2 Start Stop Contac tor Power supply Motor protection relay Waste water tank Note Be sure t...

Page 5: ...U U 61F GP N 5 6 7 8 4 8 V 0 V 24 V 10 3 9 1 2 11 Control circuit U See note Water tank Note The power supply phases terminals 3 to 9 can be matched to use the same ground for the common Electrode the...

Page 6: ...Control circuit U2 B PL PL See note Upper limit Lower limit Alarm Water tank Motor protection relay Note The power supply phases terminals 3 to 9 can be matched to use the same ground for the common...

Page 7: ...oir MCCB R S M T 61F GP NR See note 5 4 P R 8 V 0 V 24 V PS 3SR 10 3 9 1 2 11 Control circuit E3 Contac tor T Commercial Voltage Power supply Motor protection relay Waste water tank Note Be sure to gr...

Page 8: ...20 or 240 VAC 61F GP N 220 or 240 VAC Note 1 The diagram shows the connections for the water supply When draining change the connection from terminal 1 to terminal 11 2 Be sure to ground terminal 4 Po...

Page 9: ...r control of liq uids with high spe cific resistance such as distilled water For control of liq uids with low spe cific resistance such as salt water sewage water acid chemicals alkali chemicals For c...

Page 10: ...ply Control circuit 24 V Power supply 8 V see note 61F GP N8 N8L N8D N8HY 61F GP N8H 61F GP N8R 24 V 8 V Power supply Control circuit 2 2 4 3 61F GP N8Y 24 V 8 V Control circuit Power supply Note 24 V...

Page 11: ...N8 P 8 V 0 V U U U 24 V See note 3 4 5 6 PS 3S E2 E3 E1 Start Stop 2 1 8 7 Control circuit Contac tor Power supply Motor protection relay Waste water tank Commercial Voltage Note Be sure to ground the...

Page 12: ...T 61F GP N8R See note 7 8 1 2 P R 8 V 0 V 24 V PS 3SR 3 5 6 4 Control circuit Stop Start E1 Contac tor Commercial Voltage Power supply Motor protection relay Waste water tank Note Be sure to ground t...

Page 13: ...r to the following diagrams Line voltage R S S T or R T 380 or 415 VAC Phase voltage N R N S or N T 220 or 240 VAC 61F GP N8 220 or 240 VAC Note Be sure to ground terminal 1 Power source 380 to 415 VA...

Page 14: ...t provided with the Level Controller t 0 3 4 5 83 4 6 Approx 80 6 2 8 5 9 32 5 9 0 D 216 8037 I21 2 7 66 9 6 I7 FREQ 50 60 Hz SECON DARY 8 V AC VOLTA E 38 70 84 49 4 61F GP N8 PF083A 91 61F GP N8 N8L...