background image

Cat. No. N149-E1-03A

 

Conductive Level Controller

 61F-D21T-V1

1

Conductive Level Controller

61F-D21T-V1

Ideal for level control for industrial facilities 
and equipment.

• Outputs can be set to self-hold at ON or OFF using self-holding 

circuits.

• Sensitivity adjustment of operating resistance from 10 to 

100 k

 for application to a wide range of liquids. 

• Delay timer to prevent relay contact chattering caused by 

waves.

• Models with a wide AC power supply range (100 to 240 VAC) 

and 24 VAC/DC reduce the number of level controller models 
kept in stock.

• CE marking, cUL recognized.

• Easy wiring with ferrules

×

 2.5 mm

2

 solid or 2 

×

 1.5 mm

2

 standard ferrules.

Model Number Structure

Model Number Legend

1. Basic Model

61F:

Conductive Level Controller

2. Functions

D21T-V1:

Automatic liquid supply operation/

Automatic liquid drainage operation

3. Supply Voltage

24 VAC/DC:

24 VAC/DC

100-240 VAC:

100 to 240 VAC

1

2 3

61F-

@@

Summary of Contents for 61F-D21T-V1

Page 1: ...Delay timer to prevent relay contact chattering caused by waves Models with a wide AC power supply range 100 to 240 VAC and 24 VAC DC reduce the number of level controller models kept in stock CE mark...

Page 2: ...5 mm2 Control output 6 A at 250 VAC for resistive load at 20 C 1 A at 250 VAC for inductive load cos 0 4 at 20 C Indicators Green LED Power Yellow LED Control output Ambient temperature Operating 20 t...

Page 3: ...ndicator OFF and starts when the water level drops below E2 indicator ON 2 Drainage RY SW1 ON The pump starts when the water level reaches E1 indicator ON and stops when the water level drops below E2...

Page 4: ...hen relay is operating Item Usage Operating resistance knob Used to set the operating resistance to 10 to 100 k Operating time knob Use to set the operating time to 0 1 to 10 s Operating time knob Pow...

Page 5: ...ch the 61F D21T V1 to a DIN Rail DIN Rails PFP 100N 1 000 mm PFP 50N 500 mm Separator F03 14 Recommended Crimp Terminals 22 5 5 90 100 72 5 Two M4 screws or Two 4 5 dia holes Installation Procedure Mo...

Page 6: ...ations Places where there are extreme changes in temperature and humidity or icing or condensation may occur Places subject to static electricity or inductive noise Places subject to electrical fields...

Page 7: ...Cat No N149 E1 03A Conductive Level Controller 61F D21T V1 7...

Page 8: ...of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE...

Reviews: