61F-G
@
8
Automatic Water Supply with Overfull Tank Alarm
Automatic Drainage Control with Overfull Tank Alarm
Basic Type
61F-G2
Dimensions:
page 14
Automatic Drainage Control and
Water Supply with Abnormal
Water Increase Alarm
U
1
U
2
U
1
U
2
U
2
Contactor
Water supply
source
Water
tank
Motor
protection
relay
MCCB
R S
M
T
220 VAC power supply
61F-G2
S
o
T
c1
T
a1
T
b1
T
a2
T
c2
S
1
S
2
E
3
E
2
E
1
E
4
PS-4S
P
61F-11
Relay Unit
8 V
220 V
110 V
0 V
24 V
24 V
61F-11
Relay Unit
Alarm
B
(See note.)
Stop
Full
Start
E
1
E
2
E
3
E
4
Note:
Be sure to ground the common Electrode (the longest Electrode).
•
Connect Tb
1
to the power supply.
•
Power Supply Connections
110 VAC: Connect S
0
and S
1
.
220 VAC: Connect S
0
and S
2
.
Connections
U
1
U
2
U
1
U
2
U
2
Contactor
Waste
water
tank
Motor
protection
relay
MCCB
R S
M
T
220 VAC power supply
61F-G2
Reservoir
S
o
T
c1
T
a1
T
b1
T
a2
T
c2
S
1
S
2
E
3
E
2
E
1
E
4
PS-4S
E
2
E
3
E
4
P
61F-11
Relay Unit
8 V
220 V
110 V
0 V
24 V
24 V
61F-11
Relay Unit
Alarm
B
(See note.)
Stop
Start
Full
E
1
Note:
Be sure to ground the common Electrode (the longest Electrode).
•
Connect Ta
1
to the power supply.
•
Power Supply Connections
110 VAC: Connect S
0
and S
1
.
220 VAC: Connect S
0
and S
2
.
Connections
E
4
E
1
E
3
E
2
Water
supply
Upper
limit
(U
1
indicator ON)
Pump OFF
Pump ON
(U
2
indicator ON)
(U
2
indicator OFF)
P
B
L
U
1
U
2
Po
w
e
r
supply
•
The pump starts (U
2
indicator OFF) when the water level
drops below E
2
and starts (U
2
indicator ON) when the water
level reaches E
1
.
•
If the water level reaches E
4
for any reason, the alarm sounds
(U
1
indicator ON).
Relay Unit Location
Principles of Operation
E
4
E
1
E
3
E
2
Water drainage
Upper
limit
(U
1
indicator ON)
Pump OFF
Pump ON
(U
2
indicator ON)
(U
2
indicator OFF)
B
L
P
U
1
U
2
Po
w
e
r
supply
•
The pump starts (U
2
indicator OFF) when the water level
reaches E
1
and stops (U
2
indicator ON) when the water level
drops below E
2
.
•
If the water level reaches E
4
for any reason, the alarm sounds
(U
1
indicator ON).
Relay Unit Location
Principles of Operation