3-3 Test Run Operation
3
Operation
3-3 Test Run Operation
Power On
Checkpoints Before Turning On the Power
• Make sure that an appropriate power supply voltage is supplied and that the power input terminals
(R/L1, S/L2, and T/L3) are wired correctly.
3G3RX- A2
: 3-phase 200 to 240 V AC
3G3RX- A4
: 3-phase 380 to 480 V AC
• Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the motor
correctly.
• Make sure that the control circuit terminals and the control device are wired correctly and that all
control terminals are turned off.
• Set the motor to no-load status (i.e., not connected to the mechanical system).
Power On
• After checking the above, turn on the power.
Display Status Check
• When the power is turned on normally, the display shows:
[Normal] RUN LED indicator (during RUN) : ON
ALARM LED indicator
: OFF
POWER LED indicator
: ON
RUN command LED indicator
: ON
Data LED indicator (frequency)
: ON
Data display
: Displays the set value in d001
• If an error occurs, refer to "Chapter 5 Maintenance Operations" and make the necessary changes
to remedy.
[Fault]
RUN LED indicator (during RUN) : ON
ALARM LED indicator
: ON
POWER LED indicator
: ON
RUN command LED indicator
: ON
Data LED indicator (frequency)
: ON
Data display
: An error code, such as "E-01", is displayed.
(The display varies depending on the type of error.)
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......