4-73
4-2 Function Mode
4
Func
tions
External Thermistor (TH)
• This function enables thermal protection of the external equipment (e.g. motor) if its internal
thermistor is connected to the Inverter.
Note: If thermistor selection b098 is set to "01" without connecting an external thermistor, the Inverter trips.
• Connect an external thermistor between control terminals TH and SC.
• Set the following functions according to the specifications of your thermistor.
• When this function is used, keep the cable length between the motor and Inverter within 20 m.
Since the current flowing through the thermistor is weak, you must take measures to prevent noise
due to motor current. (For example, place the thermistor cable away from the motor cable.)
Brake Control Function
• This function allows the Inverter to control the external brake of equipment, including an elevating
system. When brake control selection b120 is set to "01" (enabled), the Inverter operates as
follows:
(1) At RUN command input, the Inverter starts output, and accelerates to the release frequency.
(2) After the release frequency is reached, the Inverter outputs the brake release signal (BRK) after
the brake release establishment wait time (b121) elapses. However, if the Inverter's output
current is less than the current value set in release current b126, the Inverter does not output
the brake release signal. In this case, the Inverter trips, and outputs the brake error signal (BER).
(3) If the brake confirmation signal (BOK) is allocated to a multi-function input (when "44" is set in
any of C001 to C008), the Inverter waits for the brake confirmation signal for the period set in
brake confirmation wait time b124 without accelerating, after the brake release signal is output.
If the brake confirmation signal does not turn on within the period set in b124, the Inverter
outputs the brake error signal (BER), resulting in trip. If the brake confirmation signal is not
allocated to a multi-function input, brake confirmation wait time b124 is disabled, and the Inverter
performs processing (4) after the brake release signal is output.
(4) After the brake confirmation signal is input (or after the brake release signal is output if BOK is
not selected), the Inverter restarts acceleration up to a set frequency after the period set in
acceleration wait time b122 elapses.
(5) After the RUN command is turned off, the Inverter decelerates to the brake release frequency
(b125), and turns off the brake release signal (BRK).
Parameter No.
Function name
Data
Default setting
Unit
b098
Thermistor selection
00: Disabled
01: Enabled, Positive temperature
coefficient resistance element (PTC)
02: Enabled, Negative temperature
coefficient resistance element (NTC)
00
⎯
b099
Thermistor error level
0 to 9999.:
Set a temperature resistance value to trip
the Inverter, according to the
specifications of your thermistor.
3000.
Ω
C085
Thermistor adjustment
0.0 to 1000.:
Used for gain adjustment.
Factory default
⎯
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......