4-15
4-2 Function Mode
4
Func
tions
Adjusting the FE-FC Terminal
* Below is the ratio from -10 to 10 V.
-10 to 0 V: -100% to 0%
0 to 10 V: 0% to 100%
• For example, to input voltage ranging from -5 to 5 V on the
FE-FC terminal, set A113 to -50%, and A114 to 50%.
Max.
frequency
A012/A102
A011/A101
A013/A103
0
A014/A104
100%
Analog input
(0 V/0 mA)
(10 V/20 mA)
(0/OI)
(Example 1) A015/A105: 00
Max.
frequency
A012/A102
A011/A101
A013/A103
0
A014/A104
100%
Analog input
(0 V/0 mA)
(10 V/20 mA)
(0/OI)
(Example 2) A015/A105: 01
Parameter No.
Function name
Data
Default
setting
Unit
A111
FE start frequency
-400. to 400.
(Set a start frequency.)
0.00
Hz
A112
FE end frequency
-400. to 400.
(Set an end frequency.)
0.00
A113
FE start ratio
-100. to 100.:
(Set a start ratio relative to an external
frequency reference of -10 to 10 V.
*
)
-100.
%
A114
FE end ratio
-100. to 100.:
(Set an end ratio relative to an external
frequency reference of -10 to 10 V.
*
)
100.
Related functions
A003, A203, A303, A081, A082
Forward
max. frequency
A112
Analog input
(02)
(Example 3)
(-10 V)
-100% A113
A111
A114 100%
(+10 V)
Reverse
max. frequency
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......