background image

Input Settings

16 and 12-bit Switch Settings

Set 16 or 12 bits to match the bit count of the input digital signal. Slide
the switch to the left for 16 bits and to the right for 12 bits.

[16/12-bit switch]

Parameter Settings

Set “3” (option) for the reference source (b1-01) setting.
Set the Digital Reference Card input (DI) selection (F3-01) for the in-
put signal specifications.

Setting

Description

0

BCD 1% units

1

BCD 0.1% units

2

BCD 0.01% units

3

BCD 1 Hz units

4

BCD 0.1 Hz units

5

BCD 0.01 Hz units

6

Special BCD settings (5-digit input from 0.00 to 399.99 Hz)
(See notes 1 and 2.)

7

Binary input (binary values displayed in decimal)

Note

1. The second digit below the decimal point is set by bits

8x10

0

, 4x10

0

, and 2x10

0

, so the settings are made in

units of 0.02 Hz. (If these three bits are “111,” “110,”
and “101,” they will be recognized as “9.”)

2. Only positive data can be set in order to use the Sign

(CODE) bit as a data bit.

Digital READ Timing

Use the following data settings and SET (READ) signal ON timing to
provide frequency references to the Inverter.

Frequency reference
data (D0 to 15, SIGN)

SET (READ) signal

5 ms min.

10 ms min.

5 ms min.

Summary of Contents for 3G3FV-PDI16H2

Page 1: ...sult in fatal or serious injury WARNING Not following a precaution given as a WARNING may result in fatal or serious injury Caution Not following a precaution given as a Caution can result in injury to people or damage to the product or system Items listed under caution may also have serious consequences de pending on the circumstances so be sure to heed these items at all times Mounting WARNING N...

Page 2: ... 50 m and that it is placed at least 30 cm away from other power lines Description of Input Terminals Termi No Code Description nal Binary input BCD input 5 digit BCD TC1 1 D0 20 1 x 100 2 x 100 2 D1 21 2 4 3 D2 22 4 8 4 D3 23 8 1 x 101 5 D4 24 1 x 101 2 6 D5 25 2 4 7 D6 26 4 8 8 D7 27 8 1 x 102 9 D8 28 1 x 102 2 10 D9 29 2 4 TC2 1 D10 210 4 8 2 D11 211 8 1 x 103 3 D12 212 1 x 103 2 4 D13 213 2 4 ...

Page 3: ...D 0 1 Hz units 5 BCD 0 01 Hz units 6 Special BCD settings 5 digit input from 0 00 to 399 99 Hz See notes 1 and 2 7 Binary input binary values displayed in decimal Note 1 The second digit below the decimal point is set by bits 8x100 4x100 and 2x100 so the settings are made in units of 0 02 Hz If these three bits are 111 110 and 101 they will be recognized as 9 2 Only positive data can be set in ord...

Page 4: ...laan 67 69 NL 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 OMRON ELECTRONICS INC 1 East Commerce Drive Schaumburg IL 60173 U S A Tel 847 843 7900 Fax 847 843 8568 OMRON ASIAPACIFIC PTE LTD 510 Thomson Road 13 03 SLF Bldg 1129 Singapore Tel 65 353 2611 Fax 65 353 5391 Note Specifications subject to change without notice Printed in Japan Cat No I519 E1 1 ...

Reviews: