Option Board Description 

The  3G3AX-MX2-EIP-A  is  an  option  board  which  can  be  attached  to  an 
MX2-A

  series  inverter.  The  3G3AX-MX2-EIP-A  allows  controlling, 

monitoring  and  parameterization  of  the  inverter  via  an  EtherNet/IP 
network. The application in the system that acts as an EtherNet/IP master 
is responsible for correct behaviour of the system. The 3G3AX-MX2-EIP-A 
is  a  gateway  that  passes  the  communicated  register  values  from  the 
EtherNet/IP network to the inverter and vice versa. 

 

MX2

 Inverter

 Support

 

Install  the module.  The  drive  firmware  version  can  be  read  from  the  web 
pages of the module using any web browser. If the version is 43.09, only 
limited  functionality  is  available. If  the  version  is  43.23  or  higher,  there  is 
full compatibility. 

 

MX2

 Inverter

 Safety (ISO 13849-1) 

MX2-A

  inverters  provide  the  Gate  Suppress  function  to  perform  a  safe 

stop according to the EN60204-1, stop category 0. The option board has 
been designed not to interfere with this safety function. 

 

External Dimensions 

External dimensions of the option board, shown in millimeters: 

 

 

Installation Procedure 

Follow the next steps to install a 3G3AX-MX2-EIP-A on an MX2-A

 series 

inverter: 

1. 

Power down the inverter 

2. 

Loosen  the screw  of  the  option  board  cover  on  the inverter,  remove 
the cover and put the cover aside 

3. 

For  inverters  up  to  4.0  kW  only:  loosen  the  screws  of  the  terminal 
block  cover  and  remove  the  cover  to  enable  access  to  the  chassis 
ground terminal screws 

4. 

Connect  the  grounding  cable  to  the  chassis  ground  of  the  inverter 
(located on the cooling fin) 

5. 

If removed, mount the terminal cover again and tighten the screw(s) 

6. 

Push the  3G3AX-MX2-EIP-A  option  board  into  the  previous  location 
of the option board cover until it clicks into place 

7. 

Tighten the screw of the option board (do not over-tighten). 

8. 

Select  the  right  warning  language  from  the  warning  label  sheet  and 
replace the English warning if appropriate. 

9. 

To  assign  an  IP  address,  set  the  rotary  switches  (see  chart  for  IP 
Settings  Rotary  Switches)  and  power  up  the  inverter,  the  network 
and  the  PLC  or  EtherNet/IP  master  unit.  For  other  option  board 
related inverter parameters see below 

  

EDS File and CX-Integrator 

OMRON provides a series of EDS files for the 3G3AX-MX2-EIP-A option 
board via the OMRON website. For each of the MX2 inverter type there is 
a unique EDS file, which is named: 

3G3AX-MX2-EIP-

-E.eds 

  indicates  the  specific  inverter  type,  such  as  A4150  or  AB004_A2004. 

Use these EDS files in the EtherNet/IP master configuration program used 
to configure your EtherNet/IP master. 

Network  Configurator  for  EtherNetIP  in  the  CX-One  Suite  is  the 
configuration  program  for  OMRON  EtherNet/IP  masters.  Start  the 
configurator  and  select  the  Tools/EDS  File/Install  menu  item.  Select  the 
EDS  file(s)  to  start  using  the  3G3AX-MX2-EIP-A  together  with  OMRON 
EtherNet/IP masters. 

 

 

 

 

 

Supported Modules and I/O Register Layout 

The  3G3AX-MX2-EIP-A  supports  the  modules  as  listed  in  the  EDS  file. 
The table below shows which modules can be connected. 

Description 

Output 
assembly 

Input 
assembly 

Basic Speed IO 

20 

70 

Extended Speed IO (default) 

21 

71 

Extended Speed and Torque Control 

123 

173 

Special IO 

100 

150 

Extended Control IO 

101 

151 

Extended Control IO and Multi function IO 
monitor 

101 

153 

Flexible format 

139 

159 

Extended Speed and Acceleration Control 

110 

111 

The EtherNet/IP master can be the source of either frequency reference or 
run  command.  The  selected  modules  influences  the  required  source 
selection.  See  the  section  below  about  Option  Board  Related  Inverter 
Parameters. 

 

 

LED Indicators 

Indicator 

Color 

Status 

Meaning 

MS 
(Module 
Status) 

Green 

Lit 

Normal operating status 

Flashing 

No I/O connection 
I/O connection in IDLE 

Red 

Lit 

Unit hardware error 
Unsupported inverter version. 

Flashing 

Recoverable fault. Consult manual. 

--- 

Not lit 

Power is not supplied to the Slave 
Unit. The Unit is being reset. 

NS 
(Network 
Status) 

Green 

Lit 

CIP connection established, no 
Exclusive owner connection timed out 

Flashing 

IP address configured but no CIP 
connection established 

Red 

Lit 

Duplicate IP address detected 

Flashing 

Exclusive owner connection timed out 

--- 

Not lit 

No IP address configured 
Power supply is OFF. 

LA1, LA2 
(Link 
Activity 
1,2) 

Green 

Lit 

Link established, 100 Mb 

Flickering 

Activity, 100 Mb 

Yellow 

Lit 

Link established, 10 Mb 

Flickering 

Activity, 10 Mb 

--- 

Not lit 

No link established 
Power supply is OFF 

 

 

IP Settings Rotary Switches 

Drive Parameter 

Meaning 

P185 = 0 

Use internally saved IP configuration.  

P185 = 1 - 127 

The value of P185 sets the last byte (xxx) of the IP 
address (192.168,250.xxx) 

P186=1 

Restores the module to default settings.  Set P186 to 
1, cylce power, P186 will auto change back to 0 

 

 

 

Option Board Related Inverter Parameters 

Various  inverter  parameters  influence  the  behaviour  of  the  option  board. 
The  table  below  shows  these  parameters.  Please  note  that  most 
parameter changes require a power cycle of the inverter or a restart of the 
option board. 

EtherNet/IP  Network Related Parameters 
Par 

Description 

Setting 

P044 

Communication watchdog 
timer while running. 
Note: additional to 
Ethernet/IP inactivity timer. 

0 to 9999 in 0.01 s units. Set 0 to 
disable. 
Action is defined in P045. 

P045 

Action on Network Error 
 

Set to 0 for inverter trip (default) 
Set to 1 for deceleration and trip 
Set to 2 for no action 
Set to 3 for stop due to free-run 
Set to 4 for deceleration and stop 

P048 

Action on Network Idle 
Mode 

Source Selection Parameters 
Par 

Description 

Setting 

A001 

Motor 1 Frequency Source 

Set to 3. Control determined from 
network by control bits NetCtrl and 
NetRef.  
Set to 4: Network control forced 

A002 

Motor 1 Run Command 
Source  

P033 

Torque Command Source 

For option board as source: 
Set to 6 if not flexible format 
Set to 3 if flexible format 

P036 

Torque Bias Mode

 

For option board as source: 
Set to 5 if not flexible format 
Set to 0 if flexible format 

C021 

Output Terminal 11 Source 

Set to 63 for option board as source 

C022 

Output Terminal 12 Source 

Set to 63 for option board as source 

C028 

Analog Output AM Source 

Set to 16 for option board as source 

Option Board Behaviour Related Parameters 
Par 

Description 

Setting 

C102 

Reset Mode Selection 

Set to 3 for resetting trip only 

P160

P169 

Output Register 1 to 10 
contents 

Modbus register mapped into 
flexible output word 1 to 10 

P170
-
P179 

Input Register 1 to 10 
contents 

Modbus register mapped into 
flexible input word 1 to 10 

 

IO Assembly Object Allocation 

The following table shows the I/O allocation for the main assemblies. 

 

Word 

Bit Allocation 

15 

14 

13 

12 

11 

10 

Instance ID 20: Basic Speed Control Output 

RST 

FWD 

n + 1 

Rotational Speed Reference (default [0.01 Hz]) 
Rotational Speed Reference 

Instance ID 70: Basic Speed Control Input 

DFR 

FLT 

n + 1 

Rotational Speed Monitor (default [0.01 Hz]) 
Rotational Speed Monitor 

 

Instance ID 21: Extended  Speed Control Output 

REF 

CTR 

RST 

REV 

FWD 

n + 1 

Rotational Speed Reference (default [0.01 Hz]) 
Rotational Speed Reference 

Instance ID 71: Extended Speed Control Input 

ARF 

RFN 

CFN 

RDY 

DRR 

DFR 

WR 

FLT 

Drive Status (see below) 

n + 1 

Rotational Speed Monitor (default [0.01 Hz]) 
Rotational Speed Monitor 

 

Instance ID 123: Extended  Speed and Torque Control Output 

n/n+1 

See instance ID 21 

n + 2 

Torque Reference [1 %] 
Torque Reference 

Instance ID 173: Extended Speed and Torque Control Input 

n/n+1 

See instance ID 71 

n + 2 

Torque actual [1 %] 
Torque actual 

 

Instance ID 101: Extended Control Output 

CI7 

CI6 

CI5 

CI4 

CI3 

REV 

FWD 

CO2 

CO1 

CR 

RST 

FFL 

n + 1 

Rotational Speed Reference (default [0.01 Hz]) 
Rotational Speed Reference 

n + 2 

Torque Reference [1 %] 
Torque Reference 

n + 3 

Torque Compensation Bias [1 %] 
Torque Compensation Bias 

Instance ID 151: Extended Control Input 

FLT 

WR 

RDY 

ARF 

DRR 

DZS 

DFR 

MO2 

MO1 

MR 

CFN 

n + 1 

Rotational Speed Monitor (default [0.01 Hz]) 
Rotational Speed Monitor 

n + 2 

Torque actual [1 %] 
Torque actual 

n + 3 

Output current monitor [0.1 A] 
Output current monitor 

 

 

Word 

Bit Allocation 

15 

14 

13 

12 

11 

10 

Instance ID 153: Extended Control Input + Multi Function Input 

n to  
n + 3 

See instance ID 151. 

n + 4 

MI7 

MI6 

MI5 

MI4 

MI3 

MI2 

MI1 

 

 

Output bits 

Bit 

Name 

Description 

FWD 

Forward/Stop 

0: Stop 1: Forward 

REV 

Reverse/Stop 

0: Stop 1: Reverse 

RST 

Fault Reset 

Reset Fault/Trip condition on transition from  
0 to 1 

REF 

NetRef 

Speed reference selection. 
0: Setting of A002    1: Network controlled 

CTR 

NetCtrl 

Run command selection. 
0: Setting of A001    1: Network controlled 

FFL 

Force Fault 

Force external fault/trip from network 

CI3 to 
CI7 

Control 
/Override Input 

0: Reset 1: Set override for Multi Function  
input 3 to 7 

CO1, 
CO2,
CR 

Set (Relay) 
Output 

0: Reset 1: Set Multi Function output 1 to 2 or 
Relay Output (CR) 

 

Input bits 

Bit 

Name 

Description 

FLT 

Fault 

0: Normal 1: Fault/Trip 

WR 

Warning 

0: Normal 1: Warning 

DFR 

During 
forward run 

0: Stop/reverse 1: During forward run 

DRR 

During 
reverse run 

0: Stop/forward 1: During reverse run 

DZS 

During zero 
speed 

0: Non-zero speed 1: During zero speed. 

RDY 

Inverter 
ready 

0: Inverter not ready 1: Inverter ready 

CFN 

Ctrl from Net 

Run command input selection 
0: Local  1: EtherNet/IP reference 

RFN 

Ref from Net 

Speed reference input selection 
0: Local  1: EtherNet/IP reference 

ARF 

At reference 

0: Accel/decel phase 1: At reference 

MI1 to 
MI7 

Monitor 
inputs 1 to 7 

0: OFF 1: ON 

MO1, 
MO2, 
MR 

Monitor 
(Relay) 
outputs 

0: OFF 1: ON 

 

Drive Status (for instance ID 71 and 173) 

Value 

Description 

Value 

Description 

Startup 

Stopping 

Not ready 

Fault/Trip Stop 

Ready 

Faulted/Tripped 

Enabled 

 

 

 

General Specifications

 

Item 

Specifications 

EtherNet/IP Specification 

Designed for conformance. 

EtherNet/IP Profile 

AC Drive (0x02) 

Autonegotiation 

10/100 Mbps 

Ambient operating temperature 

See MX2 inverter User’s Manual 

Ambient operating humidity 

See MX2 inverter User’s Manual 

Storage temperature 

-20 ºC to 65 ºC 

Weight 

170g 

 
 
 

 

 