Manual
RF-Gateway RS485 Typ APG03B-RS485
Omnio AG - RATIO® - radio bus system
Manual RS485-Gateway bidirectional
17.12.2008, Seite 13/ 19
Bächlistrasse 326, CH-8426 Lufingen, Phone +41 44 876 00 41, Fax +41 44 876 05 29,
info@omnio.
,
www.omnio.ch
4.1.9
Gateway Replay Set ID to INFI (RMT Receive Message Telegram)
This telegram is sent by the gateway to the Master after the Master
tried to enter a transmitter number into the input filter.
Status = 00 -> Transmitter successfully read into input filter
Status = F7 -> Gateway not in the LRN mode
(not valid since version 080831.05)
Status = FF -> Index not in the permitted range
4.1.10 Gateway Replay INFI Element (RMT Receive Message Telegram)
This telegram is sent by the gateway to the Master after the Master
has sent an inquiry for the transmitter ID (Ind) in the input filter.
The respective transmitter ID of the learned in transmitter is
indicated in the bytes DB3 to DB0.
IND = index pointer (1-32) in the input filter. Shows the position of
the already learned in transmitter in the input filter.
4.1.11 Gateway Replay INFI Size/Mode (RMT Receive Message Telegram)
This telegram is sent by the gateway to the Master after the Master
has sent an inquiry for the number of already stored transmitter ID’s
(Ind) in the input filter.
DB1 = 00 -> In the DB0 the number of the already learned in
transmitter in the input filter is indicated. Possible range
from 0 to 32 (20h).
The input filter is active.
DB1 = FF -> In the DB0 the number of the already learned in
transmitter in the input filter is indicated. Possible range
from 0 to 32 (20h).
The input filter is passive.
All
telegrams received from the gateway are sent to the
Master.
See also command „Master Set INFI Disable (TCT Transmit
Command Telegram)“, (chapter 4.2.6).
Bit7 Bit0
SB 1
0xA5
SB 2
0x5A
Typ
8B
ORG
B3
DB 3
00
DB 2
00
DB 1
00
DB 0
00
ID3
No. of the gateway
ID2
No. of the gateway
ID1
No. of the gateway
ID0
No. of the gateway
Status
00,F7,FF
Chks
Chk-Sum
Bit7 Bit0
SB 1
0xA5
SB 2
0x5A
Typ
8B
ORG
B4
DB 3
ID3
DB 2
ID2
DB 1
ID1
DB 0
ID0
ID3
No. of the gateway
ID2
No. of the gateway
ID1
No. of the gateway
ID0
No. of the gateway
Status
Ind
Chks
Chk-Sum
Bit7 Bit0
SB 1
0xA5
SB 2
0x5A
Typ
8B
ORG
B4
DB 3
00
DB 2
00
DB 1
00, FF
DB 0
Size (1..20h)
ID3
No. of the gateway
ID2
No. of the gateway
ID1
No. of the gateway
ID0
No. of the gateway
Status
FF
Chks
Chk-Sum