PTS DP1 User Manual
MON
Position - Monitoring Mode
A completely transparent signal path between OPTICAL #1 and OPTICAL #2 is established.
The data received on interface OPTICAL #1 can be monitored on RS-232 #1.
The data received on interface OPTICAL #2 can be monitored on RS-232 #2.
PC with PTS 103 in
monitoring mode with
one or two serial interfaces
Primary
Station
(master,
control
center)
Secondary
Station
(slave, relay)
PTS DP1
PTS DP1 in monitoring mode
The described mode of operation requires the OR / NORM switch being in
NORM
Position.
3.2 LIGHT-ON / LIGHT-OFF Switch
This selection is to adopt to the light position for idle status on the optical interface.
The
LIGHT-ON
position is is the one defined in the IEC 61850-5-103 standard.
Some protective relays (e.g. from SIEMENS), are delivered with the
LIGHT-OFF
setting by default.