![Omicron CPC 100 Reference Manual Download Page 224](http://html2.mh-extra.com/html/omicron/cpc-100/cpc-100_reference-manual_3988877224.webp)
CPC 100 V1.41
8 - 6
For each state, a trigger signal can be specified to prematurely terminate
this state and execute the next one. If you move to the "Trigger" cell and
press the handwheel, the cell turns into a combo box.
The following trigger conditions are available for each state:
• No Trigger: the state runs for the pre-defined period of time, no trigger
signal will terminate this state.
• Binary: a trigger signal is fed into the Binary trigger input
Bin In
. The
state is terminated as soon as this signal occurs.
• IOut>: as soon as the output current exceeds a certain threshold value
(to define in column "Thresh"), the state is terminated.
• IOut<: as soon as the output current falls below a certain threshold
value (to define in column "Thresh"), the state is terminated.
• V2 AC >: as soon as the signal connected to the low level voltage
measuring input
V2AC
(0...3V AC) exceeds a certain threshold value
(to define in column "Thresh"), the state is terminated.
• V2 AC <: as soon as the signal connected to the low level voltage
measuring input
V2AC
(0...3V AC) falls below a certain threshold
value (to define in column "Thresh"), the state is terminated.
The availability of the trigger signals depends on the selected values
set at
and
of the measurement table (refer to Figure 5).
Note:
Since the determination of the r.m.s. value requires some
hundred milliseconds (
τ
≈
150ms), do not use this trigger condition for
measurements in millisecond ranges.
• Overload: the state terminates as soon as an Overload condition
occurs at the selected output.
What is an "Overload" trigger?
– At the
800A AC
output, an overload trigger is a condition in which
the set current cannot be reached any longer, for example,
because of an opening contact or circuit breaker.
Note:
Current values
<
50A do not initiate an "Overload" when the
current circuit opens. Therefore, if you use the trigger condition
"Overload", chose a nominal current value of
≥
50A.
7
10
11
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...