Cod. 710.0103.01.00 Rev2A – 11.2012
8 - 111
6.1
Icons description
ICON
DESCRIPTION
Generic Alarm
High / Low refrigerant discharge pressure Alarm (HP/LP)
Icon ON shows “Celsius degrees”
Icon OFF shows “Fahrenheit degrees”
Refrigerant compressor energized
(Blinking when start refrigerant compressor delay activated)
Suggested Maintenance
(Icon connected to CO14 parameter)
“Functions menu” activated
Icon connected to time parameters
(ON when in Functions or Programmation area)
6.2
Signalling Led description
SIMBOL
STATUS
DESCRIPTION
BUTTON
ON
Dryer energized
ON
Condensate drain energie
(Not used with no loss discharger)
6.3
Buttons function
Single buttons function
SYMBOL
DESCRIPTION
LED /
ICON
Activates or deactivates unit operation when pressed for 3 seconds (ON/OFF).
When deactivated, the OFF message is displayed.
When the dryer is switched off using this button all digital outputs are disconnected.
Allows entry the “Functions Menu”
Pressed during normal operation displays the compressor oil temperature.
When pressed during programming mode, it scrolls the parameters list or increases the displayed value.
Pressed during normal operating displays the refrigerant circuit suction pressure.
When pressed during programming mode, it scrolls the parameters list or decreases the displayed value.
Pushed and released shows on display the SET POINT value.
In programming mode selects a parameter or confirms a value.
When pressed for more than 3 seconds during the normal operating, it performs a test of the condensate
discharge valve. (Not used with no loss discharger)
Buttons combinations
Enters the PARAMETER PROGRAMMING MENU
Exits the PARAMETER PROGRAMMING MENU