Transducer Output Table:

Transmitter Output in Milliamps

Temp

(°C)

Model

TM1M12

Model

TM2M12

 

Temp

(°C)

Model

TM1M12

Model

TM2M12

Temp

(°C)

Model

TM1M12

Model

TM2M12

-40

4.00

 

6

12.27

7.46

52

 

14.09

-39

4.18

 

7

12.45

7.60

53

 

14.23

-38

4.36

 

8

12.63

7.75

54

 

14.38

-37

4.54

 

9

12.81

7.89

55

 

14.52

-36

4.72

 

10

12.99

8.04

56

 

14.67

-35

4.90

 

11

13.17

8.18

57

 

14.81

-34

5.08

 

12

13.35

8.32

58

 

14.95

-33

5.26

 

13

13.53

8.47

59

 

15.10

-32

5.44

 

14

13.71

8.61

60

 

15.24

-31

5.62

 

15

13.89

8.76

61

 

15.39

-30

5.8

 

16

14.07

8.90

62

 

15.53

-29

5.98

 

17

14.25

9.05

63

 

15.68

-28

6.16

 

18

14.43

9.19

64

 

15.82

-27

6.34

 

19

14.61

9.33

65

 

15.96

-26

6.52

 

20

14.79

9.48

66

 

16.11

-25

6.70

 

21

14.97

9.62

67

 

16.25

-24

6.88

 

22

15.15

9.77

68

 

16.40

-23

7.06

 

23

15.33

9.91

69

 

16.54

-22

7.24

 

24

15.51

10.05

70

 

16.68

-21

7.42

 

25

15.69

10.20

71

 

16.83

-20

7.60

 

26

15.87

10.34

72

 

16.97

-19

7.78

 

27

16.04

10.49

73

 

17.12

-18

7.96

4.00

28

16.22

10.63

74

 

17.26

-17

8.13

4.14

29

16.40

10.77

75

 

17.41

-16

8.31

4.29

30

16.58

10.92

76

 

17.55

-15

8.49

4.43

31

16.76

11.06

77

 

17.69

-14

8.67

4.58

32

16.94

11.21

78

 

17.84

-13

8.85

4.72

33

17.12

11.35

79

 

17.98

-12

9.03

4.86

34

17.30

11.50

80

 

18.13

-11

9.21

5.01

35

17.48

11.64

81

 

18.27

-10

9.39

5.15

36

17.66

11.78

82

 

18.41

-9

9.57

5.30

37

17.84

11.93

83

 

18.56

-8

9.75

5.44

38

18.02

12.07

84

 

18.70

-7

9.93

5.59

39

18.20

12.22

85

 

18.85

-6

10.11

5.73

40

18.38

12.36

86

 

18.99

-5

10.29

5.87

41

18.56

12.50

87

 

19.14

-4

10.47

6.02

42

18.74

12.65

88

 

19.28

-3

10.65

6.16

43

18.92

12.79

89

 

19.42

-2

10.83

6.31

44

19.10

12.94

90

 

19.57

-1

11.01

6.45

45

19.28

13.08

91

 

19.71

0

11.19

6.59

46

19.46

13.23

92

 

19.86

1

11.37

6.74

47

19.64

13.37

93

 

20.00

2

11.55

6.88

48

19.82

13.51

3

11.73

7.03

49

20.00

13.66

4

11.91

7.17

50

 

13.80

5

12.09

7.32

51

 

13.95

regarding wiring, calibration and troubleshooting 

of the transmitter.
Note: The plastic shell of the transmitter is 

removed during assembly of the PRS-TMM12 

transducer due to space limitations.  The sides and

back of the transmitter are insulated with 

polyimide adhesive tape to isolate it from the 

sensor housing.  If the transmitter is removed from 

the housing during calibration or servicing, check 

to insure that the transmitter continues to be 

isolated from the housing during re-assembly.

Re-Assembly (See figure on page 1):

Re-assemble the housing as follows:

1. When re-assembling the cap to the housing,      

  position lead wires to insure that they will not    

  be pinched during replacement of the cap.

2. Check that the o-ring is in place as shown above.

3. Position the cap on the end of the housing,      

  gently turn the cap clockwise until the threads   

  engage (do not force).

4. Turn the cap until it is fully seated in the

   housing. The cap should turn freely until the

  o-ring seal reaches the top of the housing.  A

   1/2" wrench may be needed to complete the

   operation due to the resistance of the o-ring seal.

2