background image

58

Installation and Maintenance

Service Manual

7. Abnormal Sound and Vibration

Possible causes 

Discriminating method (air conditioner status)

Troubleshooting 

When turn on or turn off the unit, 
the panel and other parts will 
expand and theres abnormal 
sound 

Theres the sound of "PAPA"

Normal phenomenon. Abnormal sound will 
disappear after a few minutes. 

When turn on or turn off the 
unit, theres abnormal sound due 

conditioner

Water-running sound can be heard 

Normal phenomenon. Abnormal sound will 
disappear after a few minutes. 

Foreign objects inside the indoor 
unit or therere parts touching 
together inside the indoor unit 

Theres abnormal sound fro indoor unit

Remove foreign objects. Adjust all parts position 
of indoor unit, tighten  screws and stick damping 
plaster between connected parts 

Foreign objects inside the outdoor 
unit or therere parts touching 
together inside the outdoor unit 

Theres abnormal sound fro outdoor unit

Remove foreign objects. Adjust all parts position 
of outdoor unit, tighten  screws and stick 
damping plaster between connected parts 

Short circuit inside the magnetic 
coil 

During heating, the way valve has abnormal 
electromagnetic sound 

Replace magnetic coil 

Abnormal shake of compressor  Outdoor unit gives out abnormal sound 

Adjust the support foot mat of compressor, 
tighten the bolts 

Abnormal sound inside the 
compressor 

Abnormal sound inside the compressor 

If add too much refrigerant during maintenance, 
please reduce refrigerant properly. Replace 
compressor for other circumstances. 

6. Air Conditioner is Leaking

Possible causes 

Discriminating method (air conditioner status)

Troubleshooting 

Drain pipe is blocked 

Water leaking from indoor unit

Eliminate  the  foreign  objects  inside  the  drain 
pipe

Drain pipe is broken 

Water leaking from drain pipe

Replace drain pipe 

Wrapping is not tight

Water leaking from the pipe connection place of 
indoor unit

Wrap it again and bundle it tightly 

5. Compressor Can't Operate

Possible causes 

Discriminating method (air conditioner status)

Troubleshooting 

Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Connect wires according to wiring diagram to 
make sure all wiring terminals are connected 

Capacity of compressor is 
damaged 

Measure the capacity of fan capacitor with an 

the deviation range indicated on the nameplate of 
fan capacitor.

Replace the compressor capacitor

Power voltage is a little low or 
high 

Use universal meter to measure the power supply 
voltage. The voltage is a little high or low 

Suggest to equip with voltage regulator 

Coil of compressor is burnt out

Use universal meter to measure the resistance 
between compressor terminals and its 0

Repair or replace compressor

Cylinder of compressor is blocked Compressor Can't operate 

Repair or replace compressor 

4. ODU Fan Motor Can't Operate

Possible causes 

Discriminating method (air conditioner status)

Troubleshooting 

Wrong wire connection, or poor 
connection 

Check the wiring status according to circuit 
diagram 

Connect wires according to wiring diagram to 
make sure all wiring terminals are connected 

Capacity of the ODU fan motor is 
damaged 

Measure the capacity of fan capacitor with an 

the deviation range indicated on the nameplate of 
fan capacitor.

Replace the capacity of fan

Power voltage is a little low or 
high 

Use universal meter to measure the power supply 
voltage. The voltage is a little high or low 

Suggest to equip with voltage regulator 

Motor of outdoor unit is damaged

When unit is on, cooling/heating performance 
is bad and ODU compressor generates a lot of 
noise and heat. 

Change compressor oil and refrigerant. If no 
better, replace the compressor with a new one

Summary of Contents for OTEC ICHQ Series

Page 1: ......

Page 2: ...al Information 1 1 Summary 1 Removal Procedure 1 Removal Procedure of Indoor Unit 2 Removal Procedure of Outdoor Unit Troubleshooting 1 Flashing LED of Indoor Outdoor Unit and Primary Judgement 2 Procedure of Troubleshooting 3 Troubleshooting for Normal Malfunction ...

Page 3: ...1 Technical Information Service Manual 1 Summary Part Technical Information Indoor Unit Outdoor Unit Remote Controller ...

Page 4: ...35 Installation and Maintenance Service Manual Troubleshooting 1 Flashing LED of Indoor Outdoor Unit and Primary Judgement ...

Page 5: ...36 Installation and Maintenance Service Manual ...

Page 6: ...37 Installation and Maintenance Service Manual ...

Page 7: ...38 Installation and Maintenance Service Manual ...

Page 8: ...39 Installation and Maintenance Service Manual ...

Page 9: ...tion for evaporator E2 Not the error code It s the status code for the operation 50 Cold air prevention protection E9 Not the error code It s the status code for the operation 51 Refrigerant recovery mode Fo Refrigerant recovery The Serviceman operates it for maintenance ...

Page 10: ...en indoor unit and detection 53 Defrosting Heating indicator off for 0 5s and then blinks for 10s Not the error code It s the status code for the operation 54 outdoor unit error oE Cool compressor and outdoor fan stops operation while indoor compressor outdoor fan and indoor fan stop operation 1 Outdoor ambient temperature exceeds the operation range of unit eg less than 20oC or more than 2 Failur...

Page 11: ...on the controller and if damage of lead wire is found 5 Compressor over load protection 6 System malfun ction Overload protection When tube temperature Check the temperature of outdoor heat exchanger when cooling and check the temperature of indoor heat exchanger when heating is too high protection will beactivated Please refer to the malfunction analysis in the previous section for handling metho...

Page 12: ...the temperature sensor and the controller Start Insert the temperature sensor tightly Yes Yes Yes Yes Yes Yes No No No No No No Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace it with a temperature sensor with the same model Make the parts upright Is there short circuit due to trip over of the parts Is the temperature sensor normal Replace the mainboard with t...

Page 13: ...44 Installation and Maintenance Service Manual 2 Malfunction of Blocked Protection of IDU Fan Motor H6 ...

Page 14: ...tart Is the jumper cap inserted correctly Replace the jumper cap with the same model Appearance of the jumper cap Assemble the jumper cap with the same model Insert the jumper cap tightly Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace the mainboard with the same model End Yes Yes Yes Yes Yes No No No No No ...

Page 15: ...46 Installation and Maintenance Service Manual 4 Malfunction of detecting plate WIFI JF ...

Page 16: ...47 Installation and Maintenance Service Manual 5 Communication malfunction E6 ...

Page 17: ...48 Installation and Maintenance Service Manual Outdoot Unit ...

Page 18: ...49 Installation and Maintenance Service Manual 2 IPM protection phase current overcurrent the control board as below indicates the control board of outdoor unit H5 P5 ...

Page 19: ...50 Installation and Maintenance Service Manual ...

Page 20: ...51 Installation and Maintenance Service Manual ...

Page 21: ...52 Installation and Maintenance Service Manual ...

Page 22: ...53 Installation and Maintenance Service Manual ...

Page 23: ...54 Installation and Maintenance Service Manual ...

Page 24: ...55 Installation and Maintenance Service Manual ...

Page 25: ...56 Installation and Maintenance Service Manual 9 High pressure Protection ...

Page 26: ... point 5 of maintenance method for details 3 Troubleshooting for Normal Malfunction 1 Air Conditioner Can t be Started Up 2 Poor Cooling Heating for Air Conditioner 3 Horizontal Louver Can t Swing Possible Causes Discriminating Method Air conditioner Status Troubleshooting No power supply or poor connection for power plug After energization operation indicator isnt bright and the buzzer Can t give...

Page 27: ...in pipe is broken Water leaking from drain pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor Can t Operate Possible causes Discriminating method air conditioner status Troubleshooting Wrong wire connection or poor connection Check the wiring status according to circuit diagram Connect wires acc...

Page 28: ...63 Installation and Maintenance Service Manual Removal Procedure Caution discharge the refrigerant completely before removal 1 Removal Procedure of Indoor Unit ...

Page 29: ...64 Installation and Maintenance Service Manual ...

Page 30: ...65 Installation and Maintenance Service Manual ...

Page 31: ...66 Installation and Maintenance Service Manual ...

Page 32: ...67 Installation and Maintenance Service Manual ...

Page 33: ...68 Installation and Maintenance Service Manual ...

Page 34: ...69 Installation and Maintenance Service Manual ...

Page 35: ...70 Installation and Maintenance Service Manual ...

Page 36: ...71 Installation and Maintenance Service Manual ...

Page 37: ...72 Installation and Maintenance Service Manual 2 Removal Procedure of Outdoor Unit ...

Page 38: ...73 Installation and Maintenance Service Manual ...

Page 39: ...74 Installation and Maintenance Service Manual ...

Page 40: ...75 Installation and Maintenance Service Manual ...

Page 41: ...76 Installation and Maintenance Service Manual ...

Page 42: ... 15 82 83 82 4 28 37 38 37 4 3 61 62 60 8 16 84 85 84 2 29 39 40 39 2 4 63 62 6 17 86 87 86 30 41 42 41 5 64 65 64 4 18 88 89 87 8 31 43 44 42 8 6 66 67 66 2 19 90 89 6 32 45 44 6 7 68 69 68 20 91 92 91 4 33 46 47 46 4 8 70 71 69 8 21 93 94 93 2 34 48 49 48 2 9 72 71 6 22 95 96 95 35 50 51 50 10 73 74 73 4 23 97 98 96 8 36 52 53 51 8 11 75 76 75 2 24 99 98 6 37 54 53 6 12 77 78 77 25 Fahrenheit di...

Page 43: ...e main cause of refrigerant leakage Please expand the pipe according to the following steps A Cut the pip B Remove the burrs C Put on suitable insulating pipe D Put on the union nut the union nut on the pipe E Expand the port Outer diameter mm A mm Max Min 1 3 0 7 1 6 1 0 1 8 1 0 2 4 2 2 Appendix 3 Pipe Expanding Method Note Note ...

Page 44: ... 0 737 5 63 46 34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297 78 1 997 117 0 625 1 46 6 40 7 967 79 1 933 118 0 608 2 44 31 41 7 653 80 1 871 119 0 592 3 42 14 42 7 352 81 1 811 120 0 577 4 40 09 43 7 065 82 1 754 121 0 561 5 38 15 44 6 791 83 1 699 122 0 547 6...

Page 45: ... 144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 40 10 62 79 2 577 118 0 811 2 59 08 41 10 2 80 2 495 119 0 77 3 56 19 42 9 803 81 2 415 120 0 769 4 53 46 43 9 42 82 2 339 121 0 746 5 50 87 44 9 054 83 2 265 122 0 729 6 48 42 45 8 705 84 2 194 123 0 71 ...

Page 46: ...9 24 51 41 63 10 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 274 29 41 34 68 9 17 107 2 72 9 259 3 30 39 61 69 8 85 108 2 64 8 245 6 31 37 96 70 8 56 109 2 57 7 232 6 32 36 38 71 8 27 110 2 50 6 220 5 33 34 88 72 7 99 111 2 43 5 209 34 33 45 73 7 73 112 2 37 4 198 3 35 32 09 74 7 47 113...

Page 47: ......

Reviews: