![background image](http://html1.mh-extra.com/html/omega/omegabus-a2400/omegabus-a2400_user-manual_4015811052.webp)
Chapter 8
Troubleshooting
Symptom: RS-232 Module is not responding to commands
1
Using a voltmeter, measure the power supply voltage at the +Vs and
GND terminals to verify the power supply voltage is b10 and
+30Vdc.
2
Verify using an ohmmeter that there are no breaks in the communica-
tions data lines.
3
Connect the module to the host computer and power-up each device
(module and computer) then using a voltmeter measure the voltage be-
tween RECEIVE and GND. This voltage should be approximately - 10Vdc.
Repeat the measurement between TRANSMIT and GND terminals and
confirm the voltage value to be approximately -10Vdc. If either of the two
readings is approximately 0.0Vdc then the communications data lines are
wired backwards. Proper communications levels on both TRANSMIT and
RECEIVE terminals should idle at -10Vdc.
4
If you are using a serial communications converter (A1000) ensure that
the communications Baud Rate switch is set to the proper Baud Rate value.
5
Confirm software communications settings in Host computer match
those values being used by the connected module(s).
6
If the Baud Rate value being used in the application is greater than 300
Baud and the module will only communicate 300 Baud then make sure that
the DEFAULT* terminal is not connected to Ground (GND).
7
If the module(s) are being used in a RS-232 daisy-chain communica-
tions configuration then ensure that the “Echo Bit” is enabled in the
setup(SU) message of each module.
8
If the problem is not corrected after completing the steps above then
connect the module by itself to a Host computer as outlined in Chapter 1.0
under “Quick Hook-up”. Start the supplied Utility software and please call the
factory for further assistance.
Symptom: RS-485 Module is not responding to commands
1
Perform steps 1, 2, 4, 5 and 6 listed above.
Summary of Contents for OMEGABUS A2400
Page 19: ...Communication 3 3...
Page 54: ...Extended Addressing 9 2 Figure 7 1 Typical system overview...
Page 64: ...Transparent Mode 10 5 Example 4 A2400 interfacing several instruments with a string of modules...
Page 65: ...Transparent Mode 10 6 Figure 10 5 Adding secondary control using A2400 modules...