Figure 1: DRG-SC-TC Factory Calibration: J-Type, 0-500°C, 4-20mA, Upscale

Figure 3: Wiring Diagram for DRG-SC-TC

Figure 2:  Mechanical dimensions for DRG-SC-TC

Table 6: Thermocouple Range Settings

CALIBRATION

CALIBRATION

CALIBRATION

CALIBRATION

CALIBRATION

1. After configuring the dip switches,
connect the input to a calibrated ther-
mocouple source.  Connect the out-
put to the actual device load (or a
load  approximately equivalent to the
actual device load value) and apply
power.

NOTE:  To maximize thermal stability,
final calibration should be performed in
the operation installation, allowing
approximately 1 to 2 hours for warm up
and thermal equilibrium of the system.

2. Set the calibrator to the desired
minimum input and adjust the zero
potentiometer for the desired mini-
mum output.

3. Set the calibrator to the desired
maximum input and adjust the span
potentiometer for the desired maxi-
mum output.

4. Repeat steps 2 and 3, if necessary
for best accuracy.

TABLE 2

Range switch settings used in
conjunction with Table 6 (SW2,
positions 4, 5, 6, and 7)

TABLE 3

Thermocouple burnout

detection switch settings
(SW2, position 1, 2)

Note: SW2 position 3 is not used.

TABLE 1:     Thermocouple type
switch settings (SW2, positions 8,
9, 10)

Note1: All modules are designed and tested to operate in ambient
temperatures from 0 to 55°C, when mounted on a horizontal DIN rail.
When five or more modules are mounted on a vertical rail, circulating air
or model DRG-HS01 Heat Sink is recommended.

TABLE 5:

Accuracy

TABLE 4
Output switch settings (SW1,
position 1-8)