CALIBRATION

1. After configuring the DIP
switches, connect the input to a cali-
brated AC source.  Connect the
output of the actual device load (or a
load approximately equivalent to the
actual device load value) and apply
power.  Refer to the Terminal Wiring
Diagram. (Figure 3)

NOTE: to maximize thermal stability, fi-
nal calibration should be performed in the
operating installation, alllowing approxi-
mately 1 to 2 hours for warm up and
thermal equilibrium of the system.

2. Set the calibrator to the desired
minimum and adjust the zero poten-
tiometer for the desired minimum
output.

3. Set the calibrator to the desired
maximum and adjust the span poten-
tiometer for the desired maximum
output.

4. Repeat steps 2 and 3, if necessary
for best accuracy.