8.1 SELF TEST #1  (Communication Ports Test)

In order to test the serial communication ports, this test mode converts the unit to
a transponder for ASCII characters. Any transmitted character will be echoed to
the host terminal. The host parameters should be set to:

Baud rate : 4800, Word length: 8 bits, Parity: even, Stop bit: 1

8.2 SELF TEST #2 (Same Leve)l

In this test mode, the DRA-DCC-8 unit ignores the address field. All the outputs
are set according to the data field only.

8.3 SELF TEST #3 (Saw Tooth)

In this test mode, only one output channel (according to the address setting) will
produce a saw tooth wave form in which the whole value range is used.

9. MULTIDROP CONFIGURATION

Up to eight DRA-DCC-8 units can be installed in a multidrop configuration using
the RS422 communication port.

The controller's RS-422 transmitter is connected to the units' receivers while the
controller's RS-422 receiver is connected to the units' transmitters.

As the communication cable might be several thousand feet long, it is necessary
to terminate the end of the line with its characteristic impedance in order to avoid
reflections in the transmission line causing data distortion. SW8 in its ON state
terminates the Rx inputs with a 100

load.

10. PUTTING THE UNIT INTO OPERATION

The DRA-DCC-8 is supplied with a set configuration for parallel control mode.
The DIP switch setting is:

The communication port selector (see para #7.1) is set to RS232C.

The unit should be set up according to the required configuration.

Before applying voltage to the unit see para #4 for power supply consideration.

S1

S2

S3

S4

S5

S6

S7

PARALLEL 4-20mA

ON

OFF

OFF

OFF

OFF

OFF

OFF

MODE

Summary of Contents for DRA-DCC-8

Page 1: ...DRA DCC 8 DIGITAL TO 8 CURRENT LOOP CONVERTER User sGuide http www omega com e mail info omega com...

Page 2: ...02 Certified Broughton Astley Leicestershire Irlam Manchester LE9 6TU England M44 5EX England Tel 44 1455 285520 Tel 44 161 777 6611 FAX 44 1455 283912 FAX 44 161 777 6622 Toll Free in England 0800 48...

Page 3: ...Interface 6 2 The E ENABLE Terminal 7 SERIAL CONTROL MODE 7 1 RS232c RS422 Select 7 2 RS422 Termination 7 3 Serial Control Switch Settings 7 4 Serial Communication Parameters 7 4 1 Baud Rate Select 7...

Page 4: ...river Press down gently on the plastic springloaded tabs located in the slots either side of the unit c Disconnect the flat connector which couples the LED circuit on the front panel d Replace the blo...

Page 5: ...y an internal array of 8 DIP switches as follows 4 20 or 0 20mA output current mode Parallel control mode Serial control mode Self test mode 5 1 0 20 OR 4 20mA OUTPUT CURRENT MODE Two current output s...

Page 6: ...ture The data should be valid for at least 160 microseconds S1 S2 S3 S4 S5 S6 S7 SELF TEST 1 ON OFF X OFF X OFF ON OFF X MODE ON ON OFF X SELF TEST 2 SELF TEST 3 S1 S2 S3 S4 S5 S6 S7 PARALLEL MODE OFF...

Page 7: ...election is carried out by controlling the E inputs 7 SERIAL CONTROL MODE Figure 3 7 1 RS232c RS422 SELECT he DRA DCC 8 is equipped with two serial communication ports The RS232c and the RS422 A jumpe...

Page 8: ...cknowledgment stating the DRA DCC 8 ID number and the addressed channel number Status report Three types of command formats are available 7 4 3 1 WITHOUT ECHO BACK FORMAT A ID CODE CHANNEL VALUE CR Th...

Page 9: ...T S ID CODE CR The addressed DRA DCC 8 unit will respond with the values stored in its eight channels The response will start with S ID code following with eight channel values separated with commas a...

Page 10: ...in a multidrop configuration using the RS422 communication port The controller s RS 422 transmitter is connected to the units receivers while the controller s RS 422 receiver is connected to the units...

Page 11: ...2 Monitor all the 8 channels in 4mA state and calibrate the Zero trimmer so that their average readings is 4 000mA Then repeat for 20mA state and calibrate the Span trimmer so that their average read...

Page 12: ...Enable E 0 0 0 5V 4 1 60V 160 microsecond 6000 updates per second RS232c full duplex RS422 full duplex 300 4800 9600 19200 BPS Even One Reports as interrogated Up to eight units 8 continues current lo...

Page 13: ...EGA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to...

Page 14: ...Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH Conductivity Equipm...

Reviews: