29
DPF20 Frequency, rate, total or period counter
Instruction Manual
Register R0 and R1 (DISPLAY1_L and DISPLAY1_H)
Contains the display value of the instrument, codified in two registers
of 16 bits each. Possible values are from 999999 to -199999. Decimal
point position is codified on register R2.
Example R0=FBF1 (hex) and R1=0009 (hex)
Register value = 0009 FBF1 (hex)
Reading value = 654321
Register R2 (DECIMALS1)
Contains the number of decimals of the display, codified in a single
register of 16 bits. Possible values are from 0 to 6.
Example R2=0002 (hex)
Number of decimals = 2 = 6543.21
Register R3 and R4 (MAXMEM_L and MAXMEM_H)
Contains the memory of maximum reading of the instrument, codi
-
fied in two registers of 16 bits each. Possible values are from 999999
to -199999. Decimal point position is codified on register R2.
Example - same example as in R0 and R1 but accessing to R3 and
R4.
Register R5 and R6 (MINMEM_L and MINMEM_H)
Contains the memory of minimum reading of the instrument, codi
-
fied in two registers of 16 bits each. Possible values are from 999999
to -199999. Decimal point position is codified on register R2.
Example - same example as in R0 and R1 but accessing to R5 and
R6.
Register R7 and R8 (SETPOINT1_L and SETPOINT1_H)
Contains the setpoint value of alarm 1, codified in two registers of 16
bits each. Possible values are from 999999 to -199999. Decimal point
position is codified on register R2.
Example - same example as in R0 and R1 but accessing to R7 and
R8.
Register R9 and R10 (SETPOINT2_L and SETPOINT2_H)
Contains the setpoint value of alarm 2, codified in two registers of 16
bits each. Possible values are from 999999 to -199999. Decimal point
position is codified on register R2.
Example - same example as in R0 and R1 but accessing to R9 and
R10.
Register R11 and R12 (SETPOINT3_L and SETPOINT3_H)
Contains the setpoint value of alarm 3, codified in two registers of 16
bits each. Possible values are from 999999 to -199999. Decimal point
position is codified on register R2.
Example - same example as in R0 and R1 but accessing to R11 and
R12.
Register R13 (STATUS)
Information bit-by-bit, for the alarm status (on / off) and instrument
status. See below for a description.
Bit 0
Alarm 1 status (0 = inactive, 1 = active)
Bit 1
Alarm 2 status (0 = inactive, 1 = active)
Bit 2
Alarm 3 status (0 = inactive, 1 = active)
Bit 3 a 7 Reserved
Bit 8
Display overrange
Bit 9
Display underrange
Bit 10
Lost communication with the main processor
Bit 11 to 15 Reserved
Registers R14, R15 and R16
Reserved
2.3.4
Description and example for Modbus RTU registers