SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in this 

literature or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired. Do not use this unit to directly 

command motors, valves, or other actuators not equipped with safeguards. To do 

so can be potentially harmful to persons or equipment in the event of a fault to 

the unit.

METER INSTALLATION 

The DP63100-S meets NEMA 4X/IP65 requirements  when properly 

installed. The unit is intended to be mounted into an enclosed panel. Prepare the 

panel cutout to the dimensions shown. Remove the panel latch from the unit. 

Slide the panel gasket over the rear of the unit to the back of the bezel. The unit 

should be installed fully assembled. Insert the unit into the panel cutout. 

While holding the unit in place, push the panel latch over the rear of the unit 

so that the tabs of the panel latch engage in the slots on the case. The panel latch 

should be engaged in the farthest forward slot possible. To achieve a proper seal, 

tighten the latch screws evenly until the unit is snug in the panel (Torque to 

approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.

Installation Environment

The unit should be installed in a location that does not exceed the operating 

temperature and provides good air circulation. Placing the unit near devices that 

generate excessive heat should be avoided.

SETTING THE JUMPERS

Bridge Excitation

This jumper is used to select bridge excitation voltage level. Use the 5 V 

excitation with high output (3 mV/V) bridges, so that the higher sensitivity 24 

mV range can be used. Using the 5 V excitation also reduces bridge power 

consumption compared to the 10 V excitation. A maximum of four 350 ohm load 

cells can be driven by the internal bridge excitation voltage.

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

PANEL

LATCHING 

SLOTS

BEZEL

PANEL 

GASKET

PANEL 

LATCH

LATCHING 

TABS

PANEL 

MOUNTING 

SCREWS

-.00

(92    )

-.0

+.8

3.62

+.03

(45    )

1.77

-.0

+.5

-.00

+.02

PANEL CUT-OUT

10V

5V

±240mV

±24mV

INPUT RANGE

BRIDGE

EXCITATION

REAR TERMINALS

JUMPER SELECTIONS

The 

 indicates factory setting.

Main Circuit Board 

REAR TERMINALS

FRONT DISPLAY

JUMPER

LOCATION

Finger

Tab

Finger

Tab

USB

Connector