background image

An  O ME GA Te c h n o l o g i e s  Co m p a n y

 M2119/1294

INSTRUCTION

SHEET

DP18 Series

Options R1 / R2
Single & Dual Setpoint Options

SETPOINTS CONTROLLER BOARD, OPTION R1(AL1) and OPTION R2 (AL2)

5 - THIS PUSHBUTTON ALLOWS THE DISPLAY OF SETPOINT
6 - THIS LED LAMP IS ON WHEN THE RELAY IS ENERGIZED
7 - POTENTIOMETER FOR SETPOINT REGULATION
8 - POTENTIOMETER FOR DEADBAND REGULATION

OPTION R2

SETPOINT 2 (AL2)

"1" = RELAY  ENERGIZED

LED SWITCHED OFF

"0" = RELAY  DE-ENERGIZED

LED SWITCHED ON

- 1.999

NEGATIVE RANGE

DISPLAY READING

+ 1.999

POSITIVE RANGE

NOTE : LEDS ACTUATION "2" AND "6" IS OPPOSITE TO THE RELAYS ACTUATION

CCD1294APC10B

THE SETPOINTS CONTROLLER BOARD ALLOWS THE USE OF TEMPERATURE METERS AS CONTROLLERS IN  ON/OFF MODE AND AS CONTROLLERS
OF MAXIMUM (HIGH SETPOINT) AND/OR MINIMUM (LOW SETPOINT) IN OTHER MODELS.
THE VERSATILITY OF THIS UNIT  ALLOWS THE PROGRAMMING OF THE FOLLOWING FUNCTIONS :

A - EACH ONE OF THE SETPOINTS, OPERATING AS MAXIMUM (HIGH) OR MINIMUM (LOW)
B - SETPOINT RANGE, POSITIVE OR NEGATIVE
C - SETPOINT DISPLAY RANGE, FOR 1.000 or 2.000 COUNTS
D - DEADBAND (HYSTERESIS) ADJUSTABLE IN TWO SCALES

E - SETPOINTS OPERATING DELAY IN FOUR TIME SCALES

SETPOINT PROGRAMMING

PRESS THE PUSHBUTTON "1",  AND THE DISPLAY WILL SHOW THE PRESELECTED VALUE, TURN THE POTENTIOMETER "3", TO THE RIGHT OR TO THE
LEFT SIDE, UNTIL THE DISPLAY SHOWS THE NEW VALUE DESIRED.
DEPRESS THE PUSHBUTTON "1", AND THE DISPLAY WILL SHOWS AGAIN THE SIGNAL INPUT.
USE THE SAME PROCESS FOR THE SETPOINT "2".

FRONT VIEW 

WITHOUT UPPER PROTECTION COVER

SET

SET

hys

SET

hys

0

1

LOW SETPOINT

HIGH SETPOINT

hys

0

1

SET

hys

RELAYS OPERATING DIAGRAM

SETPOINT ADJUST IN TWO RANGES .  .  .  0 to 1.000 COUNTS (Selectable)

0 to 2.000 COUNTS  (Standard)

HYSTERESIS OF BOTH SETPOINTS
ADJUSTABLE IN TWO RANGES . . . . . . . .  1 to 10 COUNTS  (Standard)

5 to 50 COUNTS  (Selectable)

SETPOINT OPERATING DELAY . . . . . . . .  0.2 sc.  (Standard)

0.4 - 0.8 - 1.6 sc.  (Selectable)

ACCURACY . . . . . . . . . . . . . . . . . . . . . . . .  ± 1 COUNT
SETABILITY . . . . . . . . . . . . . . . . . . . . . . . .  ± 1 COUNT
OUTPUT RELAY . . . . . . . . . . . . . . . . . . . . .  1 SPDT FOR EACH SETPOINT
RELAY CONTACTS

MAX. ADMISSIBLE VOLTAGE . . . . . .  250 Vac.
MAX. ADMISSIBLE CURRENT . . . . .  3 Amp. NON INDUCTIVES

TECHNICAL FEATURES

1 -

THIS PUSHBUTTON ALLOWS THE DISPLAY OF SETPOINT

2 -

THIS LED LAMP IS ON WHEN THE RELAY IS ENERGIZED

3 -

POTENTIOMETER FOR SETPOINT REGULATION

4 -

POTENTIOMETER FOR DEADBAND REGULATION

OPTION R1

SETPOINT 1 (AL1)

1

hys

hys

SET

SET

2

AL2

AL1

SIGNAL
INPUT

SPDT FOR AL2

(OPTION R2)

SPDT FOR AL1

(OPTION R1)

REAR VIEW

POWER SUPPLY

ANALOG OUTPUT
(OPTIONAL)

CONNECTIONS

1   2    3    4

     8

  7   6   5