37
SETUP MENU
See Quick Reference (p.74) for a listing of the menu.
PARAMETER DESCRIPTION
roFF - rhLd
Ramp/Soak Command:
The Ramp/Soak program auto-
matically changes the setpoint value with time
according to a preset pattern.
Setting: roFF : Normal operation is performed
rrUn : Ramp/Soak operation is performed
rhLd : Ramp/Soak operation is suspended
rEnd indicates that the operation is terminated.
AH
High Alarm Setpoint
: The High Alarm Setpoint is that
point of the process above which, the high alarm output
relay is energized. If the alarm type, programmed in the
setup menu, includes an absolute value for the High
Alarm Setpoint, enter the actual value you want the
alarm to be activated at regardless of what the main set-
point is set for. If the alarm type includes a deviation
value for the High Alarm Setpoint, enter the number of
units above main setpoint in which you want the alarm to
be activated at; the deviation alarm tracks main setpoint.
Set within the Input Range.
Not indicated without the alarm option.
AL
Low Alarm Setpoint:
The Low Alarm Setpoint is that
point of the process below which, the low alarm output
relay is energized. Absolute and deviation alarm configu-
rations are programmable from within the secondary
menu.
Blinking
‘H’ LED
Blinking
‘L’ LED
Summary of Contents for CN4321
Page 33: ...32 SYSTEM WIRING DIAGRAMS Example 1 Example 2...
Page 45: ...44 Deadband Overlap...
Page 48: ...47 Table of Input Type Codes...
Page 50: ...49...
Page 53: ...52 Table of Alarm Action Type Codes CN4321...
Page 54: ...53 Table of Alarm Action Type Codes CN4431...
Page 59: ...58 Table of Output Type Codes...