OPERATION DESCRIPTION 

z

 

Set Value Setting: 

In basal display status, if the parameter lock “Loc” isn't locked,  we can set 

setpoint (SV) by pressing 

 or 

.  Press 

 key to decrease the 

value, 

  key to increase the value, and 

  key to move to the digit expected 

to modify.  Keep pressing 

 or 

, the speed of decreasing or inscreasing 

value get quick.    The range of setpoint is between the parameter SPL and SPH.   

The default range is 0~400.   

 

z

 

Parameter Setting:

 

In basal display status, press 

 and hold for about 2 seconds can access 

Field Parameter Table.    Pressing 

  can go to the next parameter; pressing 

 or 

 can modify a parameter.  Press and hold 

 can return to 

the preceding parameter. Press 

 (don't release) and then press 

 key 

simultaneously can escape from the parameter table. The instrument will 
escape auomatically from the parameter table if no key is pressed within 30 
seconds.  Setting Loc=808 and then press 

 can access System 

Parameter Table.   

 

 

AI artificial intelligence control and auto tuning 

When AI artificial intelligence control method is chosen (CtrL=APId), the PID 
parameters can be obtained by running auto-tuning.  In basal display status, 
press 

  for 2 seconds, the “At” parameter will appear.    Press 

 to change 

the value of At from “oFF” to “on”, then press

  to active the auto-tuning 

process.    During auto tuning, the instrument executes on-off control.    After 2-3 
times of on-off action, the instrument will obtain the optimal control parameter 
value.    If you want to escape from auto tuning status, press and hold the 

 

key for about 2 seconds until the "At" parameter appear again.  Change “At” 
from “on” to “oFF”, press 

  to confirm, then the auto tuning process will be 

cancelled.  

 

Note 1: 

If the setpoint is different, the parameters obtained from auto-tuning are 

possible different.    So you’d better set setpoint to an often-used value or 

middle value first, and then start auto-tuning.    For the ovens with good 

heat preservation, the setpoint can be set at the highest applicable 

temperature.  Depending on the system, the auto-tuning time can be 

from several seconds to several hours. 

 

Note 2: 

Parameter Ctl (on-off differential, control hysteresis) has influence on the 

accuracy of auto-tuning.  Generally, the smaller the value of Ctl, the 

higher the precision of auto tuning.    But Ctl parameter value should be 

large enough to prevent the instrument from error action around setpoint 

due to the oscillation of input.    Ctl is recommended to be 2.0. 

 

Note 3: 

The instrument has the function of self-learning.  It is able to learn the 

process while working.    The control effect at the first run after auto tuning 

is probably not perfect, but excellent control result will be obtained after a 

period of time because of self-learning. 

 10

 

Summary of Contents for CN4000 Series

Page 1: ...e mail info omega com For latest product manuals www omegamanual info CN4000 SERIES Temperature Controllers TM Shop online at omega com User sGuide NORWALK CT ...

Page 2: ...specifications without notice omega com info omega com Servicing North America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only Tel 203 359 1660 Fax 203 359 7700 e mail info omega com For Other Locations Visit omega com worldwide ...

Page 3: ...ler with 0 0 decimal CN418V 1 8 DIN Vertical controller CN428V 1 8 DIN Vertical controller with 0 0 decimal CN418H 1 8 DIN Horizontal controller CN428H 1 8 DIN Horizontal controller with 0 0 decimal Specify controlling output code from Output Options table below Specify alarm code from Alarm Options table below Low voltage power supply option LV Controlling Output Options Option Type Code Relay R1...

Page 4: ...emperature Display Resolution CN 4116 CN414 CN418 1 1 CN4216 CN424 CN428 0 1 0 1 ON OFF Control Control Method AI PID Control with Auto Tuning AT Relay Output 1A 250VAC Output Type Voltage Output for SSR 12V 30mA Limit High Low Alarm Modularization High deviation Low deviation 100 240VAC 15 10 or 24VDC Supply Voltage 50 to 60Hz Power Consumption 3W Operating Environments Temperature 10 to 60 14 to...

Page 5: ...n PV LoAL alarm off when PV LoAL AHYS 999 3000 999 HdAL Deviation high alarm Alarm on when PV SV HdAL alarm off when PV SV HdAL AHYS 999 3000 3000 LdAL Deviation low alarm Alarm on when PV SV LdAL alarm off when PV SV LdAL AHYS 999 3000 999 Loc Parameter Lock Loc Auto Tuning SV Primary Parameter Secondary Parameter 0 X 1 X X 2 X X X 3 X X X X 808 allow to modify data or execute AT X not allow to m...

Page 6: ...nction on this model rE dr rEbA drbA rE P Proportion band Proportion band in PID with unit or 1 999 30 I Time of Integral No integral effect when I 0 0 9999 Sec 100 s d Time of derivative No derivative effect when d 0 0 999 9 Sec 50 0s CtI Control period Small value can improve control accuracy For SSR output generally 0 5 to 3 seconds Large value can increase using life of relay For Relay output ...

Page 7: ...ent input is stabilized but the response speed is slow Generally if great interference exists then you can increase parameter FILt gradually to make momentary fluctuation of measured value less than 2 to 5 When the meter of the instrument is being examined at laboratory FILt should be set to 0 or 1 to short the response time 0 40 1 Fru Selection of power frequency and temperature scale 50C 50Hz 50...

Page 8: ...put specification setting is incorrect Or Input wiring is disconnected thermocouple problem Or Short circuited HIAL High limit alarm LoAL Low limit alarm HdAL Deviation high alarm LdAL Deviation low alarm EErr IC Software error 8888 IC Software error ...

Page 9: ...ontal Note The compensation wires for different kinds of thermocouple are different and should be directly connect to the terminals Connecting the common wire between the compensation wire and the t e r m i n a l s w i l l c a u s e m e a s u r e m e n t e r r o r Wiring graph for 1 16 DIN dimension instruments 8 ...

Page 10: ...play status When power on the upper display window of the instrument shows the process value PV and the lower window shows the set point SV This status is called basic display status When the input signal is out of the measurable range for example the thermocouple or RTD circuit is break or input specification sets wrong the upper display window will alternately display orAL and the high limit or ...

Page 11: ...ive the auto tuning process During auto tuning the instrument executes on off control After 2 3 times of on off action the instrument will obtain the optimal control parameter value If you want to escape from auto tuning status press and hold the key for about 2 seconds until the At parameter appear again Change At from on to oFF press to confirm then the auto tuning process will be cancelled Note...

Page 12: ...GA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to mishandling improper interfacing operation outside of design limits improper repair or unauthorized modification This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows ...

Page 13: ...rs M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U Industrial pH Conductivity Equipment DATA ACQUISITION M U Communications Based Acquisition Systems M U Data Logging Systems M U Wireless Sensors Transmitters Receivers M U Signal Conditioners M U Da...

Reviews: