background image

Appendix  C

IP Netmask

IP Netmask or Subnet Mask is a 32-bit pattern of ones and zeros used to determine

network portion of an IP address from the host portion of the IP address. Subnet mask is

a network ID that is created by borrowing bits from host portion of IP address and using

them as part of a network ID. The table below shows a default subnet mask for address

Classes A, B, and C. Each bit that is set to "1" in the subnet mask corresponds to the bit

in the IP address that is to be used as the network ID. Each bit that is set to "0" in the

subnet mask corresponds to a bit in the IP address that is to be used as the host ID.

Address Class

Mask Binary Value 

Mask Decimal Value

or Dotted Notation

Class A

255.0.0.0

Class B

255.255.0.0

Class C

255.255.255.0

If your network requires more network ID’s, you can extend the default subnet mask to

include additional bits from the host ID. This allows for additional network ID’s within the

network.  The table below shows some examples of subnet masks and bits moved from

the hosts ID to create a new subnet. 

Mask Dotted Notation

Mask Binary

Mask Bits

Class A

255.0.0.0 (Default)

0

255.192.0.0

2

255.224.0.0

3

255.240.0.0

4

255.248.0.0

5

255.252.0.0

6

255.254.0.0 

7

255.255.0.0

8

255.255.128.0

9

255.255.192.0.0

10

…………….........

.

255.255.255.252

22

Class B

255.255.0.0 (Default)

0

255.255.192.0

2

…………….........

.

255.255.255.252

14

Class C

255.255.255.0 (Default)

0

255.255.255.192

2

………………….

.

255.255.255.254

6

To determine the number of valid hosts ID’s remaining after subnetting, use the following

equation: 2

n

– 2, where n is the number of octet digits left after the subnet mask.

82

11111111

11111111

11111111

00000000

11111111

11111111

00000000

00000000

11111111

00000000

00000000

00000000

11111111

11111111

11111111

11111111

11111111

11111111

11111111

11111111

11111111

11111111

. . . . . . . .

11111111

00000000

11000000

11100000

11110000

11111000

11111100

11111110

11111111

11111111

11111111

. . . . . . . .

11111111

00000000

00000000

00000000

00000000

00000000

00000000

00000000

00000000

10000000

11000000

. . . . . . . .

11111111

00000000

00000000

00000000

00000000

00000000

00000000

00000000

00000000

00000000

00000000

. . . . . . . .

11111100

11111111

11111111

. . . . . . . .

11111111

11111111

11111111

. . . . . . . .

11111111

00000000

11000000

. . . . . . . .

11111111

00000000

00000000

. . . . . . . .

11111100

11111111

11111111

. . . . . . . .

11111111

11111111

11111111

. . . . . . . .

11111111

11111111

11111111

. . . . . . . .

11111111

00000000

11000000

. . . . . . . .

11111100

Summary of Contents for Wireless Meter Scanner & Controller wi...

Page 1: ...Minute 1 Day 1 Week 1 Month 1 Year 0 5 C Div 50 1200 300 100 0 10 Div 90 hPa Div C hPa Tue Feb 5 10 19 10 PDT 2008 Tue Feb 5 10 18 10 PDT 2008 http 192 168 1 200 Min Max Temperature 48 0 41 0 P1 Process P2 Sensor 2 P3 Process P4 Process P5 Process P6 Process P7 Process P8 Sensor 8 A1 Ambient A2 Sensor 2 A3 Ambient A4 Ambient A5 Ambient A6 Ambient A7 Ambient A8 Sensor 8 Save Current Graph ...

Page 2: ...his document is believed to be correct but OMEGA Engineering Inc accepts no liability for any errors it contains and reserves the right to alter specifications without notice WARNING These products are not designed for use in and should not be used for patient connected applications This device is marked with the international caution symbol It is important to read the Setup Guide before installin...

Page 3: ...1 10Base T RJ45 Pinout 16 2 2 2 10Base T Crossover Wiring 16 Part 3 Network Configuration 17 3 1 Ethernet MAC Address 17 3 2 Network Protocols 17 3 3 DHCP 17 3 4 DNS 18 3 5 IP Address 19 3 5 1 Default IP Address 19 3 5 2 Changing TCP IP Properties on your Computer 20 Part 4 Network Operations 21 4 0 Testing the Connection 21 4 1 iConnect Software 22 4 2 Setting a New IP Address over the Network 24...

Page 4: ...re 65 4 8 1 Installation 65 4 8 2 Program Options Setup and Configuration 66 4 8 3 Device Settings and Configuration 67 Part 5 Environment operating Conditions 69 5 1 General Deployment Guidelines 69 5 2 With Line of Sight 71 5 3 Without Line of Sight 72 5 4 Casing and Closure Around the Antenna 72 Part 6 Specifications 73 Part 7 Factory Preset Values 76 Appendix A Glossary 78 Appendix B IP Addres...

Page 5: ...ccessing the Wireless System for Configuration 23 Figure 4 4 Access Control 24 Figure 4 5 Wireless System Home Page Menu 25 Figure 4 6 LOGIN and ADMINISTRATOR passwords 26 Figure 4 7 Readings 27 Figure 4 8 Java 1 5 x x Screen Shots 29 Figure 4 9 Java 1 4 Screen Shots 30 Figure 4 10 Java Policy 32 Figure 4 11 Java Policy 33 Figure 4 12 Chart 34 Figure 4 13a Controller Setup 36 Figure 4 13b Controll...

Page 6: ...0 Mail Notifier Profile Setup 66 Figure 4 31 Mail Notifier Device Settings 68 Figure 5 1 Operation in Buildings 70 Figure 5 2 Fresnel Zone 71 Figure 5 3 Materials in Buildings 72 LIST OF TABLES Table 2 1 Front Panel Enunciators 5 Table 2 2 Rear Panel Connector 6 Table 2 3 Fuse Requirements See Specifications 11 Table 4 1 List of Commands 60 Table 4 2 Mail Notifier Commands 67 Table 7 1 Factory Pre...

Page 7: ...The switch shall not be incorporated in the main supply cord Furthermore to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment an overcurrent protection device shall be installed Do not exceed voltage rating on the label located on the top of the instrument housing Always disconnect power before changing signal and power connections Do ...

Page 8: ...assistance please call the nearest Customer Service Department listed in this manual Manuals Software The latest Operation Manual as well as free configuration software iConnect are available from the website listed in this manual or on the CD ROM enclosed with your shipment NOTES WARNINGS and CAUTIONS Information that is especially important to note is identified by following labels NOTE Provides...

Page 9: ...eries system let s you monitor and record temperature over an Ethernet network or the Internet without any special software just your Web Browser ETHERNET The wiSeries meter controller scanner is an independent node on the network sending and receiving data in standard TCP IP packets It is easily configured from a Web Browser and can be password protected From within an Ethernet LAN or over the In...

Page 10: ... reset by the operator The meter can also be programmed to display only one unchanging color GREEN AMBER or RED This is a useful way to let an operator identify at a glance temperature values in three separate locations or to display three different measurements The following example Figure 1 1 illustrates how you can hookup the Temperature Wireless System to your network The wireless system consi...

Page 11: ...perature Changes display to Configuration Mode and advances through menu items Make sure to press twice Stand by followed by pressing stop communication before entering the Configuration mode Used in Configuration Mode to change values In Run Mode it s used to lock the display to the next sensor reading Used in Configuration Mode to change values It s also used to resume scrolling sensors Accesses...

Page 12: ...Ethernet board ACTIVITY LED Red Blinking Indicates network activities receiving or sending packets NET LINK LED Green Solid Indicates good network link TX LED Yellow Blinking Indicates transmitting data to the serial port RX LED Green Blinking Indicates receiving data on the serial port ACTIVITY NET LINK TX RX 8 1 ETHERNET RST RJ45 10BASE T CONNECTION RESET BUTTON LED INDICATORS ANTENNA LOCATION P...

Page 13: ...2 1 3 Dimensions Figure 2 3 Mounting Dimensions 3 780 96 00 1 890 48 00 0 700 17 78 4 325 109 85 1 2 C F 1 2 RH D 1 2 C F PANEL THICKNESS 0 25 6 4 MAX 0 03 0 6 MIN PANEL CUTOUT 1 8 DIN 7 ...

Page 14: ...rom the rear of the case by removing thumbnuts 3 Insert the case into the opening from the front of the panel so the gasket seals between the bezel and the front of the panel 4 Slip the sleeve over the rear of the case 5 Tighten the thumbnuts to hold the unit firmly in the panel Figure 2 4 Panel Mounting Front Bezel Gasket Case Panel Thumbnuts Sleeve Model No Label 8 ...

Page 15: ... can reach a suitable location The antenna on this Meter and any End Devices should be installed in a vertical position pointing towards the sky Metallic structure should be kept at least 0 8 2 cm although 2 4 6 cm is recommended away from the antenna Any casing that encloses the antenna should be plastic In addition it is also wise to avoid plastic case with dark fillers or colorants Refer to Sec...

Page 16: ...om the case by pulling at the sides of the bezel 2 The bezel along with the board assembly will unlatch from the case housing Depending on the size of your Ethernet connector you may need to disconnect it from the RJ45 jack on the rear of the meter Depending on the length of your antenna cable you may need to disconnect it from the rear of the meter Figure 2 6 Accessing the Main Board Assembly Gas...

Page 17: ...ervoltage Category and pollution degree as the standard AC unit 90 240 Vac The Safety European Standard EN61010 1 for measurement control and laboratory equipment requires that fuses must be specified based on IEC127 This standard specifies for a Time lag fuse the letter code T The above recommended fuses are of the type IEC127 2 sheet III Be aware that there are significant differences between th...

Page 18: ... outputs The SPDT Mechanical Relay SPST Solid State Relay Pulse and Analog Output Connection are shown below Figure 2 8 a Mechanical Relay and SSR b Pulse and Analog Outputs Wiring Hookup Outputs Wiring Hookup 12 Use copper conductors only for power connections ...

Page 19: ...GE SSR DRIVER OUTPUT FAST BLOW FUSE 0 or 5 Vdc TYPICALLY 4 3 1 2 TEMPERATURE CONTROLLER CONTROL SIDE LOAD SIDE HEATER Vac Vac ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT FAST BLOW FUSE Vac DRIVING SSR 4 3 1 2 TEMPERATURE CONTROLLER CONTROL SIDE LOAD RESISTOR LOAD SIDE HEATER Vac Vac ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT FAST BLOW F...

Page 20: ... opened Refer to Section 2 1 4 3 for assembly and disassembly instructions 2 Locate S1 jumper on the back side of the display board Select the position for your color choice of Red Green or Amber Figure 2 10 Location of S1 Jumper To change the color of the upper Display see Section 4 3 7 6 1 4 3 2 ON 1 ON RED GREEN S1 8 GREEN RED S1 AMBER S1 Open S1 Display Board 14 ...

Page 21: ...he Meter is shipped with all DIP switches in OFF position To set the Wireless and Ethernet settings to Factory Default Refer to Section 7 Figure 2 11 Location of DIP Switches 1 4 3 2 OFF ON 1 4 3 2 OFF ON 1 ON OFF S1 8 4 Position DIP Switch on Ethernet Board 8 Position DIP Switch on Wireless Board OFF ON 1 8 15 1 N A 2 To change the Ethernet settings to Factory Default 3 To enable disable DHCP 4 N...

Page 22: ...Pinout 2 2 2 10Base T Crossover Wiring When connecting the iServer directly to the computer the transmit data pins of the computer should be wired to the receive data pins of the Meter and vice versa The 10Base T crossover cable with pin connection assignments are shown below Figure 2 13 10Base T Crossover Cable Wiring Use straight through cable for connecting the Meter to an Ethernet hub The port...

Page 23: ... room to put your IP address Figure 3 1 Label Detail 3 2 Network Protocols The Meter can be connected to the network using standard TCP IP protocols It also supports ARP HTTP WEB server DHCP DNS and Telnet protocols 3 3 DHCP DHCP Dynamic Host Configuration Protocol enables individual computers or devices to extract their IP configurations from a server DHCP server If the DHCP is enabled on your Me...

Page 24: ...se only http wis03ec or any sixteen character name stored as Host Name under Access Control page from the Wireless System Home Page The default DNS name for the Meter is wis followed by the last four digits of the MAC address of that particular Meter 1 It is very important to communicate with the network administrator in order to understand the DHCP and its existing configurations on the host serv...

Page 25: ... Subnet Mask of 255 255 255 0 If you are going to use a Web browser or Telnet program to access the Meter using its default IP address make sure that the PC from which you re establishing the connection has an IP address that is in the same range as the Meter s IP address 192 168 1 x where x can be any number from 1 to 254 See Section 3 5 2 Your PC s IP address cannot be the same as the Meter s IP...

Page 26: ...se 192 168 1 1 as shown below and press OK Figure 3 4 Network Connections 20 Look for Internet Protocol click on it and press Properties You can access the Meter s web server via any internet browser using IP address of 192 168 1 200 Once you log into the Meter s web server you will be able to change its IP configuration according to Section 4 2 After you configure the Meter s IP configurations yo...

Page 27: ... IP address of 192 168 1 x that is in the same range as the Meter s default IP address 192 168 1 200 and connect to the Meter using a cross over network cable between your PC s network port and the Meter After you re done with configuring the Meter you can always set your PC back to its original settings See Section 3 5 2 for more details On your computer from the MS DOS Prompt window type ping 19...

Page 28: ...T department for obtaining an IP address Figure 4 2 Assigning an IP Address using iConnect 1 Place the IP address in this box 2 Take the MAC address from the label attached to the bottom of the Meter and place it in this box 3 Click here to send the above IP address to the Meter 4 After the IP address is assigned to the Meter click here to access it s web pages 5 Click here to Ping the Meter whose...

Page 29: ...ued d To access the Wireless System for Configuration Click on the View Webpage button you will access the Wireless System s home page refer to Section 4 3 for details Figure 4 3 Accessing the Wireless System for Configuration 23 ...

Page 30: ...less System Home Page Select button you ll be asked for the password You should be on the Access Control page were you can simply type in the desired Static IP address and click Save For more details about the Access Control page refer to Section 4 3 10 Figure 4 4 Access Control For the IP address to take effect the Meter needs to be turned OFF and ON using the Network Reset button Pressing the ph...

Page 31: ...ts from the MAC address label located on the Meter see Figure 3 1 if DHCP and DNS are used If a static IP address is used then simply type http x x x x where x x x x is the Meter s IP address The Home Page will be displayed Figure 4 5 Wireless System Home Page Menu In order to access certain menu items of the Home Page users may be prompted for a password as shown in the two following figures 25 ...

Page 32: ...is powered on the green LED TX will blink periodically This indicates the End Device is broadcasting its data to the Meter on channel 12 defined by IEEE 802 15 4 The LED will blink only when the End Device sends data to the Meter If the Meter is not powered on or it s out of reach the End Device will not receive the acknowledgment packet from the Meter and therfore to save battery power it will go...

Page 33: ...tion running or image of a Java logo please verify you have the latest Java Runtime Environment installed and configured according to the Section 4 3 3 1 If you do not have Java Runtime Environment you may download it from our website or contact the Customer Service Department nearest you wiSeries Lab 200 Lab 100 ID 1 Strength 100 Sequence 10 Success 100 Battery 3 78V Update 120sec Running ID 2 St...

Page 34: ...radio signal strength 0 100 the higher the better Success 0 100 a low success rate indicates a longer data delay shorter battery lifetime and high network traffic Battery The total voltage of the battery in the End Device Once the voltage gets to 3 0V the batteries should be replaced Update The time interval the Meter received data from the End Device Running Lost It displays Running if the Meter ...

Page 35: ...e dialog box to show the General Tab again 4 Select the Network Settings button on the General Tab Proceed to the Browser tab Follow the Browser Proxy Selection instructions below You should either select the Use Browser Settings option or the Direct Connection option depending on the network connections between your computer and the Meter Generally select Direct Connection if accessing the Meter ...

Page 36: ...he box if accessing the Meter on your local network and check the box for access from your internal network to the internet 4 Refresh or restart the webpage To disable cache setting For Java Version 1 4 2 x it is found under the CACHE TAB Figure 4 9 Java 1 4 2 x Screen Shot Java TM Plug in Control Panel Advanced Basic Proxies Browser Certificates Cache About Update Enable Caching Cache Settings Vi...

Page 37: ...Options dialog and make sure that the Proxy tab shows that the Use Browser Settings option is not selected i e when you specify proxy connections in the Java Plugin control panel Accessing Meter units over Peer to Peer network A simple peer to peer network is setup by disconnecting from the main network as users will often do when trying to do initial setup of the Meter and then connecting the Met...

Page 38: ...s shown in the file needs to be changed otherwise it will not work If more than one Meter is being monitored from the same computer it is necessary to repeat the above for each of the Meters in the same java_policy txt file If DHCP DNS is enabled the unique Meter s name using DNS should replace the IP address Example http zServer_TEST Make sure the DHCP server updates the DNS table to keep track o...

Page 39: ...e Data Logging and Save Current Graph buttons in the Readings and Chart pages will not be active if the instructions explained in the above Section 4 3 4 are not followed Java Runtime Settings Control Panel Java Control Panel Control Panel Address Comments Name Java Java TM Control Panel General Update Security Advanced Java Java Applet Runtime Settings Runtime settings are used when an applet is ...

Page 40: ...ns refer to Section 4 3 3 1 If you do not have Java Runtime Environment you may download it from our website or contact the Customer Service Department nearest you Figure 4 12 Chart wiSeries Main Menu CHART 2 Seconds Div 1 Minute 1 Minute 1 Day 1 Week 1 Month 1 Year 0 5 C Div 50 1200 300 100 0 10 Div 90 hPa Div C hPa Tue Feb 5 10 19 10 PDT 2008 Tue Feb 5 10 18 10 PDT 2008 http 192 168 1 200 Min Ma...

Page 41: ...ine will disappear When clicked again it comes back to normal operation Chart Area Display the trend lines of the sensors Range of temperature can be controlled by the upper and lower boxes on the left and range of pressure can be controlled by the upper and lower boxes on the right S button Ambient S shows the sensor name displays error messages Lost and controls the ambient sensor readings When ...

Page 42: ...ar Figure 4 13a Controller Setup Channel 12 Please refer to local regulation for maximum transmit power range Transmit Power Range Reset PID 13106 version x x iSeries Firmware Version x x End Device ID Input Setpoints On Off Alarm 2 Alarm 1 Loop Break Passcode ID Display Permanent Store Enable Standby Mode Before Configuring Unit Scrolling Main Menu CONTROLLER SETUP Setup Transmit Power Misc Monit...

Page 43: ... local regulation for maximum transmit power range Transmit Power Range Reset PID 13106 version x x iSeries Firmware Version x x End Device ID Input Setpoints On Off Alarm 2 Analog Out Passcode ID Display Permanent Store Enable Standby Mode Before Configuring Unit Scrolling Main Menu CONTROLLER SETUP Setup Transmit Power Misc Monitor CONTROLLER SETUP http 192 168 1 200 Address Update Update Update...

Page 44: ... Device specified on Device ID End Device ID Address ID of the End Device that will be display on the Meter C Transmit Power Channel 12 The Receiver communicates in a fixed channel Operation channel 12 defined in IEEE 802 15 4 for the sensor network Transmit Power Range This determines the signal power transmitted by the Receiver The options are 10dBm and 20dBm D Miscellaneous PID 13106 version Th...

Page 45: ...evice ID number that will be used as input to control Filter This option allows the user to specify the number of readings stored in the Digital Averaging Filter Temperature Unit Unit of temperature readings ºC or ºF Figure 4 14 Input Temperature Unit F Filter 4 Control End Device ID for Retransmission and On Off 5 Main Menu SETUP Input SETUP http 192 168 1 200 Address Cancel Update 39 ...

Page 46: ... Permanent Store Check to save Setpoints in the Meter s permanent storage On Off 1 and On Off 2 To enable and disable On Off Control Enabling On Off Controls will disable the Alarms and vice versa DeadBand The Dead Band or neutral zone is the number of degrees counts around Setpoint 1 or Setpoint 2 if On Off 2 which the temperature value must pass above or below the Setpoint before the output chan...

Page 47: ...n Off Control Setpoint 2 Permanent Store 100 DeadBand DeadBand On Off 1 On Off 2 Auto Setpoint Deviation Disabled Disabled Disabled Direct 0 Setpoint 1 0 Action Action Reverse 0 Main Menu SETUP Setpoints On Off Control SETUP http 192 168 1 200 Address Cancel Update 41 ...

Page 48: ...f you have the Analog Output Option installed in your Meter Figure 4 15b Setpoints On Off Control if Analog Output Option Setpoint 2 Permanent Store 100 DeadBand On Off 2 Disabled Direct 10 Action Main Menu SETUP Setpoints On Off Control SETUP http 192 168 1 200 Address Cancel Update 42 ...

Page 49: ...ause the temperature digits to blink in a rotating pattern If the temperature reaches the setpoint the blinking will stop otherwise the Break Alarm warning will flash and the Output will be turned off Loop Break Time allows the user to determine the time interval in MM SS from zero to 99 minutes and 59 seconds that the value changes 4 Fahrenheit or 2 Celsius Figure 4 16 Loop Break Loop Break Loop ...

Page 50: ...gized under normal conditions and becomes de energized during alarm or power failure Latch if Latched Alarm remains latched until reset To reset already latched alarm select Unlatched and press Update If Unlatched Alarm remains latched only as long as the alarm condition is true Absolute if Absolute this allows Alarms to function independently from their respective Setpoints If the process being m...

Page 51: ...ower On Alarm could be triggered immediately by non controlling end device at startup Absolute Active Alarm 1 Relay Alarm 1 Low Enabled 0 Above Absolute Enabled Alarm 1 High 100 Latch Unlatched Open Main Menu SETUP Alarm 1 SETUP http 192 168 1 200 Address Cancel Update 45 ...

Page 52: ...A If the input reaches high value the output will be 0V and 0mA Voltage Current Select the output to be Voltage 0 10V or Current 0 20mA Input Low The minimum input value scaled for Output Low Output Low Output Voltage or Current represented by Input Low Input High The minimum input value scaled for Output High Output High Output Voltage or Current represented by Input High Input High Output Low Re...

Page 53: ...when alarm 2 is true In order to display one color set the same display color on all three submenus If user wants the Display to change color every time when both Alarm 1 and Alarm 2 are triggered the Alarm values should be set in such a way that Alarm 1 value is always on the top of Alarm 2 value otherwise value of Alarm 1 will overwrite value of Alarm 2 and Display Color would not change when Al...

Page 54: ...er the display time in seconds between each End Device Normal Choose the display color of temperature when it is in the normal stage Alarm 2 Choose the display color of temperature when alarm 2 is true In order to display one color set the same display color on both submenus Figure 4 19b Display Menu if Analog Output Option Screen Update seconds 3 Normal Green Alarm 2 Amber Main Menu SETUP Display...

Page 55: ...1 Output 2 SSR Alarm Setup Absolute Above Alarm 2 HI Value ALR H 200 Alarm 1 HI Value ALR H 400 Color Display Setup Normal Color N CLR Green Alarm 1 Color 1 CLR Amber Alarm 2 Color 2 CLR Red Display Colors change sequences GREEN RED AMBER 0 AL2 H 200 AL1 H 400 Example 2 Output 1 Output 2 Pulse Alarm Setup Absolute Below Alarm 2 Low Value ALR L 300 Alarm 1 Low Value ALR L 100 Color Display Setup N ...

Page 56: ... is designed to monitor the Input Value around the Setpoint 2 Example 4 Output 1 Relay Setpoint 1 200 Output 2 Relay Setpoint 2 200 Alarm 1 Setup Deviation Band ALR H 20 Alarm 2 Setup Deviation Hi Low ALR H 10 ALR L 5 Color Display Setup N CLR Green 1 CLR Amber 2 CLR Red Display colors change sequences AMBER RED GREEN GREEN RED AMBER 0 180 195 200 210 220 Reset The Meter automatically resets after...

Page 57: ...point ID If enabled ID Code is set to Setpoint ID Security Level and if a user attempts to enter the Configuration Menu using the Front Panel Buttons they will be prompted to enter an ID Code Full ID If enabled ID Code is set to Full Security Level and if a user attempts to enter the Main Menu using the Front Panel Buttons they will be prompted to enter an ID Code ID editable box to enter the 4 di...

Page 58: ... IP Address Remote Port 0 0 0 0 02000 Remote Access Disable TCP UDP Server Type TCP Command Forward CR Disable Secured Applet Title wiSeries Number of Connections 1 Port 02000 Main Menu NETWORK SETUP General Terminal Server Remote Access Tunneling NETWORK SETUP http 192 168 1 200 Address Update Network Setup A B C ...

Page 59: ...network host Number of Connections The range is from 0 to 5 If 0 is selected the Terminal Server feature is disabled This means that no network connection can be made to the Meter If 1 is selected only one network connection can be made to the Meter Any number more than 1 would allow that number of network hosts to read from the Meter simultaneously default is 5 Port Port number for TCP connection...

Page 60: ...0 120 0 0 0 0 120 0 F F F F F F F F F F F F F F F F 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0D 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F 0000000F Name Update Access Units Remote FormatEndChar Display Alarm Click on End Device ID to modify Sensor Parameters Network Access Data from Network Applet Displ...

Page 61: ...s data to the Meter Access Each check box controls whether or not readings from the End Device will be outputted If unchecked the reading from the End Device will not be displayed on the Readings and Chart pages nor it will be reported through Telnet Each End Device has two access boxes assigned the first is for the external process sensor and the second is for the internal ambient sensor Units Ty...

Page 62: ... Char Hex 0x 0000000F 0D Offset xxxx C 0 Remote Display Format Remote End Char Hex 0x 0000000F 0D Offset xxxx C 0 Device Name Update Sec ABCDEFGH 120 Display Alarm Main Menu END DEVICE PARAMETERS End Device 1 END DEVICE PARAMETERS http 192 168 1 200 Address Update Cancel Device Reset Sensor2 Sensor1 ...

Page 63: ...y the unit of F for a maximum of 8 characters Any letters before and or after the number will be displayed accordingly Keep in mind that the displayed letters will take away from the available 8 characters Make sure that you have enough 0 s to display the entire temperature value Any extra 0 s will be ignored If there is no temperature unit then the unit will read from the Input menu if the Contro...

Page 64: ...oes back to the End Device Setup page Reset Device Reset the End Device s readings and status Its data will be cleared immediately 4 3 10 Access Control This section describes the Access Control page of the Wireless System Web interface This page allows the users to set up the network and security parameters of the Wireless System At the initial entrance to the Access Control page you may be promp...

Page 65: ... the Internet The Meter s default IP address is 192 168 1 200 The Meter s IP address should be changed to fit user s networking environment Consult with your IT department for obtaining an IP address The DHCP will be enabled in the Meter if its IP address is set to 0 0 0 0 The DHCP can also be enabled by setting the 4 position DIP switch 3 to ON Gateway Address A gateway is a network point that ac...

Page 66: ...R01i r Success rate 0 100 100 SR01j r Battery voltage mV 2810 SR01k r Device status hex msb on the left hand side 12th bit set to enable control 8th bit set to enable display 7th bit set when Open detected 1100 6th bit set when Lost detected 0 bit set when device is in identification mode otherwise it is in running mode SR01l r Expected sample rate in seconds 120 also known as update time SR01m r ...

Page 67: ...ay be needed with some Meters when you need to view readings from the web page while simultaneously collecting data through TCP IP communications 4 5 1 HTTPget using Port 2000 You can setup and read the information from the Meter by using the HTTPget program The following program can be used to read data from the embedded server firmware by using TCP port 2000 The command string is sent to this TC...

Page 68: ...ftware which may be downloaded from our website to do these IP changes whenever possible Use ARP first to assign the mac address to a static IP address in computer arp table by this command arp s 192 168 1 200 00 03 34 00 06 b6 Then use the following command to assign new IP to the device Httpget r S 00000000 192 168 1 200 1 where 0000000 is admin password If the password is wrong the unit will ig...

Page 69: ... entries for specific network interface arp s plus IP address plus Physical address Use this command to manually add a permanent static entry to the ARP cache arp d plus IP address Use this command to manually delete a static entry The following window shows examples of arp commands and responses Your computer has an IP address of 192 168 1 118 The destination computer has an IP address of 192 168...

Page 70: ...ad the iLog software from the website listed in this manual b Install iLog software on a networked PC This software is compatible with Windows 95 98 NT 2000 and XP c For complete information of how to use the iLog software click on the HELP button d There is a list of Error Messages in Appendix E Figure 4 28 iLog Software Logging Data for End Device 2 6 7 ...

Page 71: ...ith existing email that supports the MAPI messaging interface If MS OutlookTM has been loaded the MAPI support should be available 4 8 1 Installation The Mail Notifier must be loaded on a computer running MicrosoftTM Windows versions specified earlier using an email program that provides MAPI access Network access must be available between this computer and the Meter Network access must also be av...

Page 72: ...o 2005 The Mail Notifier will attempt to automatically identify whether the Outlook is a newer version A red bar appears under the Mail Notifier splash window to confirm that the detection of the 2002 or newer version is acceptable With the newer versions no additional steps should be taken to enable the connection between the Mail Notifier and the Email server MS Outlook tends to require that the...

Page 73: ... Notifier Commands Desired Value to Monitor Reading Command Actual Command String String see Note 2 Temperature1 Thermocouple SR a SR05a r in scale configured at Meter Temperature1 Thermocouple SR o SR05o r in Degree C Temperature2 Ambient at SR b SR05b r End Device sensor in scale configured at Meter Temperature2 Ambient at SR p SR05p r End Device sensor in Degree C Battery voltage mV SR j SR05j ...

Page 74: ...us Address Device ID Socket Number Description Src ID Reading Cmd Server IP Address 3 2000 Dev1 zRdgA 192 168 1 200 Device Info 1 of 2 Alarm Type Alarm High Alarm Low Alarm High 73 0 Info Message Email Interval Monitor Interval 0 05 Alarm Hold Time 0 0 0 5 hrs min min Alarm Configuration Only Monitor Access to iServer device SR a ...

Page 75: ...nd people 6 The FCC approval for this meter specifies the specific antenna supplied with this meter 5 1 General Deployment Guidelines 1 Position Meter in a central location When multiple End Devices are in operation position your Meter in a central space if possible in equal distance to each End Device 2 Test your system before permanent mounting Try to move the devices to different location aroun...

Page 76: ...o performance as well 10 Reduced performance scenario a A large building may have few obstructions between nodes but large amount of metallic paneling that cause reflections b A small domestic installation may have numerous brick walls between nodes in individual rooms c An office building may have metalized dry wall partitions together with mezzanine ceilings Figure 5 1 Operation in Buildings Dat...

Page 77: ...e communication range between the End Device and Meter Also if the antennas are mounted just barely off the ground or below the ceiling over half of the Fresnel zone ends up being obstructed resulting in significant reduction in range Below is the calculated radius of the football shaped tunnel for different distance range Distance feet Radius feet 100 3 2 200 4 5 300 5 5 It is recommended that wi...

Page 78: ...small holes in the panel or around metal edges through the process of diffraction Material Type Possible Signal Reduction Wood Plaster Sheetrock Fiberglass Uncoated Glass w out Metal 0 to 10 Brick Pressboard 5 to 35 Reinforced Concrete 10 to 90 Metal Walls Metal Doors Elevators Metal Piping Metal Stair Cases Metal Mesh Metal Screening 90 to 100 Figure 5 3 Materials in Buildings In a non line of si...

Page 79: ...mmable Non Isolated Retransmission 0 to 10 Vdc or 0 to 20 mA 500 Ω max Output 1 only Accuracy is 1 of FS when following conditions are satisfied 1 Input is not scaled below 1 of Input FS 2 Analog Output is not scaled below 3 of Output FS Alarm 1 2 programmable Type Same as Output 1 2 Operation High low above below band latch unlatch normally open normally closed and process deviation front panel c...

Page 80: ...tification for CE are claimed External Fuse Required Time Lag IEC 127 3 recognized 100 mA 250 V 400 mA 250 V Low Voltage Power Option Time Delay UL 248 14 listed 100 mA 250 V 400 mA 250 V Low Voltage Power Option Environmental Conditions 0 to 55 C 32 to 131 F 90 RH non condensing Protection NEMA 1 Type 1 front bezel Dimensions 48 H x 96 W x 127 mm D 1 89 x 3 78 x 5 Panel Cutout 45 H x 92 mm W 1 77...

Page 81: ... WIRELESS COMMUNICATION Standard IEEE 802 15 4 Frequency 2 4 GHz 2410 MHz Channel 12 Network Topology Star Topology Range UWTC 1 UWRTD 1 up to 60 m 200 ft without obstructions or interference UWTC 2 UWRTD 2 up to 120 m 400 ft without obstructions or interference Refer to the UWTC Manual for more specifications APPROVALS FCC Part 15C CE EMC 2004 108 EC LVD 2006 95 EC RTT E 1999 5 EC This product is...

Page 82: ... Put the 8 position DIP switch 1 to ON position it does not matter if the Meter is On or Off 2 Power cycle the Meter and wait about 10 seconds until the Meter fully boots up 3 Put the DIP switch 1 back to OFF position it does not matter if the Meter is powered On or Off just make sure that the DIP switch is set to OFF otherwise everytime the unit is power cycled the factory settings will take over...

Page 83: ... Alarm 1 Low 100 C Alarm 1 high 4000 C Active Above C Normally Open C Latch Unlatched C Absolute Absolute C Alarm at Power On Enabled C Alarm 2 Alarm 2 Relay Enabled C Alarm 2 Low 100 C Alarm 2 high 4000 C Active Hi Lo C Normally Open C Latch Unlatched C Absolute Absolute C Alarm at Power On Enabled C Display Screen Update secs 3 W Normal Green C Alarm 1 Red C Alarm 2 Amber C Passcode ID Setpoint ...

Page 84: ...ID 13106 version x x iSeries Firmware Ver x x NETWORK SETUP General Secured Applet E Title wiSeries E Terminal Server TCP IP TCP E Server Type Command E Forward CR Enable E Number of Connections 1 E Port 02000 E Remote Access Tunneling Remote IP Address 0 0 0 0 E Remote Port 02000 E Remote Access Disable E Access Control Login Password 12345678 E Admin Password 00000000 E Host name wisxxxx MAC Add...

Page 85: ...FGH 120 F 0000000F 0D F 0000000F 0D 5 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D 6 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D 7 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D 8 ABCDEFGH 120 F 0000000F 0D F 0000000F 0D END DEVICE PARAMETERS End Device 1 8 Device Name ABCDEFGH E Update 120 secs W Sensor 1 Remote Display Format 0000000F E Remote End Char Hex 0x 0D E Offset xxxx 0 W Display W Alarm W Sensor 2 R...

Page 86: ...s a 32 bit pattern of bits used to determine which part of the IP address is the network portion and which part is the host portion MAC Media Access Control Address is your computer s unique hardware number When you re connected to the Internet from your computer a correspondence table relates your IP address to your computer s physical MAC address on the LAN Ping is a utility that tests the netwo...

Page 87: ...upport approximately 216 65 536 computers per network The IP addresses range in binary from 10000000 00000000 xxxxxxxx xxxxxxxx to 10111111 11111111 xxxxxxxx xxxxxxxx The IP addresses range in decimal from 128 0 x x TO 191 255 xxx xxx Class B network ID s support a medium number of hosts Class C addresses have 24 bits of network ID and 8 bits of host ID They can support approximately 28 256 comput...

Page 88: ...t Mask Dotted Notation Mask Binary Mask Bits Class A 255 0 0 0 Default 0 255 192 0 0 2 255 224 0 0 3 255 240 0 0 4 255 248 0 0 5 255 252 0 0 6 255 254 0 0 7 255 255 0 0 8 255 255 128 0 9 255 255 192 0 0 10 255 255 255 252 22 Class B 255 255 0 0 Default 0 255 255 192 0 2 255 255 255 252 14 Class C 255 255 255 0 Default 0 255 255 255 192 2 255 255 255 254 6 To determine the number of valid hosts ID ...

Page 89: ...2 01010010 DC3 19 13 00010011 S 83 53 01010011 DC4 20 14 00010100 T 84 54 01010100 NAK 21 15 00010101 U 85 55 01010101 SYN 22 16 00010110 V 86 56 01010110 ETB 23 17 00010111 W 87 57 01010111 CAN 24 18 00011000 X 88 58 01011000 EM 25 19 00011001 Y 89 59 01011001 SUB 26 1A 00011010 Z 90 5A 01011010 ESC 27 1B 00011011 91 5B 01011011 FS 28 1C 00011100 92 5C 01011100 GS 29 1D 00011101 93 5D 01011101 RS...

Page 90: ...7 11 Crtl Q Data Control 1 XON SOH 01 01 Crtl A Start of DC2 18 12 Crtl R Data Control 2 Header STX 02 02 Crtl B Start of Text DC3 19 13 Crtl S Data Control 3 XOFF ETX 03 03 Crtl C End of Text DC4 20 14 Crtl T Data Control 4 EOT 04 04 Crtl D End of NAK 21 15 Crtl U Negative Transmission Acknowledge ENQ 05 05 Crtl E Inquiry SYN 22 16 Crtl V Synchronous Idle ACK 06 06 Crtl F Acknowledge ETB 23 17 Cr...

Page 91: ...0007 Windows socket error Wrong IP or wrong Port number was used 10008 The Meter failed to respond to a request Wrong IP or wrong Port number was used 10011 Response came empty No data was sent 10012 Device responded with Possibly the iLog is configured for Serial Time Out string wrong product model 10014 Terminal Server Mode when the Port is 1000 Try Port 2000 in iLog configuration 15100 Error on...

Page 92: ...NOTES ...

Page 93: ...NOTES ...

Page 94: ...NOTES ...

Page 95: ...IONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Should any Product s be used in or with any nuclear installation or activity medical application used on humans or misused in any way OMEGA assumes no responsibility as set forth i...

Page 96: ...ocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH Conductivity Equipment DATA ACQUISITION Data Acquisition Engineering Software Communications Based Acquisition Systems Plug in Cards for Apple IBM Compatibles Datalogging Systems Recorders Print...

Reviews: