2 - 3
2 RECEIVING FUNCTIONS
Input range table
Input type
Range
Input
Measurement range
Unit
DC Voltage
20 mV
20 mV
-20.00 to 20.00 mV
mV
60 mV
60 mV
-60.00 to 60.00 mV
mV
200 mV
200 mV
-200.0 to 200.0 mV
mV
2 V
2 V
-2.000 to 2.000 V
V
6 V
6 V
-6.000 to 6.000 V
V
20 V
20 V
-20.00 to 20.00 V
V
Input type
Range
Measurement range
˚C
T C
R
0.0 to 1760.0 ˚C
S
0.0 to 1760.0˚C
B
0.0 to 1820.0˚C
K
-200.0 to 1370.0˚C
E
-200.0 to 800.0˚C
J
-200.0 to 1100.0˚C
T
-200.0 to 400.0˚C
L
-200.0 to 900.0˚C
U
-200.0 to 400.0˚C
N
0.0 to 1300.0˚C
W
0.0 to 2315.0˚C
R T D
JPT
-200.0 to 550.0˚C
PT
-200.0 to 600.0˚C
CU1 to CU6*
-200.0 to 300.0˚C
CU25*
-200.0 to 300.0˚C
Measurement range
˚F
32 to 3200
°
F
32 to 3200
°
F
32 to 3308
°
F
–328.0 to 2498.0
°
F
–328.0 to 1472.0
°
F
–328.0 to 2012.0
°
F
–328.0 to 752.0
°
F
–328.0 to 1652.0
°
F
–328.0 to 752.0
°
F
32 to 2372
°
F
–328.0 to 752.0
°
F
–328.0 to 1112.0
°
F
–328.0 to 1022.0
°
F
–328.0 to 1112.0
°
F
–328.0 to 1022.0
°
F
* Allowed when the /N1 option (Cu10, Cu25) is equipped.
DI (Digital Input)
Format: SRp1, mode, p2
p1:
Channel number (CC)
mode:
DI (digital input)
p2:
Select the signal type from LEVL (level) or CONT (contact).
Example: SR01, DI, CONT
SCL (Scaling)
Format: SRp1, mode, p2, p3, p4, p5, p6, p7, p8
p1:
Channel number (CC)
mode:
SCL
p2:
Input type. VOLT, TC or RTD
p3:
Range
p4:
Low limit value of the display span (LOWER SPAN). Enter 5
digits, excluding the decimal point and the + or – sign.
p5:
High limit value of the display span (UPPER SPAN). Enter 5
digits, excluding the decimal point and the + or – sign.
p6:
Lower scale limit (SCL LOWER). Enter 6 digits, excluding the
decimal point and the + or – sign.
p7:
Upper scale limit (SCL UPPER). Enter 6 digits, excluding the
decimal point and the + or – sign.
p8:
Decimal point position of scaling value (0 to 4, which stands for
the number of digits after the decimal point)
2.2 Program Set Commands