PX791 & PX792 SERIES

OMEGA® SANITARY PRESSURE TRANSDUCER

INSTRUCTION SHEET

Mounting

Although the unit can withstand normal vibra-
tion without damage or significant output
effects, it is always good practice to mount the
transducer where there is minimum vibration. Be
sure to use a gasket that does not interfere with
the sanitary diaphragm. If the gasket I.D. is
smaller than 1.50 inches, an offset due to
clamping force will occur.

Power Supply

The supply voltage for the 1-5 and 
1-6 Vdc output transducers must be within the
range of 10 to 36 Vdc. The maximum supply
voltage for a 4-20mA current output transducer
is 36 Vdc while the minimum supply voltage is
dependent upon the loop resistance of the circuit.
Refer to Figure 1. The loop supply voltage vs.
loop resistance shows the minimum supply
voltage (V

min

) required for a given loop resistance

(R

LOOP

).

W A R N I N G !

This instrument is susceptible to damage when exposed to static
electrical charges. To avoid damage to the transducer observe the
following:

• Ground the body of the transducer BEFORE making any electrical

connections

•  When disconnecting, remove the ground LAST.
NOTE: The braided shield and drain wire in the cable (if supplied) is not
connected to the transducer body, and is not a suitable ground.
CAUTION: Pressure spikes in excess of the rated overpressure capabil-
ity of the transducer may cause irreversible electrical and/or mechani-
cal damage to the pressure measuring and containing element(s).

Excitation (Ratiometric Output Only)

For proper operation a voltage within the range
of 5 to 10 Vdc must be applied between the
transducer’s supply terminals.

Noise

For minimum noise susceptibility, avoid running
the transducer’s cable in a conduit that contains
high current AC power cables. Where possible
avoid running the cable near inductive equipment.

Shield Wiring

Connect the braided shield to the guard terminal
on the reading instrument (meter, etc.) if avail-
able or to ground or to the power supply nega-
tive terminal.

Adjustment Potentiometers

The zero and span pots are accessible through
the top of the case. Loosen the four screws and
separate the top carefully. The zero pot is marked
with a white dot. 

Summary of Contents for PX791 Series

Page 1: ...www omega com e mail info omega com omega comTM User sGuide PX791 PX792 Series Sanitary Pressure Transducer...

Page 2: ...TEL 33 0 130 621400 FAX 33 0 130 699120 Toll Free in France 0800 4 06342 e mail france omega com Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056 3017 FAX 49 0 7056 8540 T...

Page 3: ...serve the following Ground the body of the transducer BEFORE making any electrical connections When disconnecting remove the ground LAST NOTE The braided shield and drain wire in the cable if supplied...

Page 4: ...in the labeling can be reasonably expected to result in a significant injury to the user 2 A critical component is any component of a life support device or system whose failure to per form can be re...

Page 5: ...iaphragm but the fluid to be measured Fluid hammer and surges can destroy any pressure transducer and must always be avoided A pressure snubber should be installed to eliminate the damaging hammer eff...

Page 6: ...UCER POWER OUTPUT POWER SUPPLY Common Power Output METER TRANSDUCER 3 Wire Voltage 4 20mA POWER SUPPLY Power Power Output Output METER TRANSDUCER RED WHITE GREEN BLACK 4 Wire Ratiometric mV V WIRING D...

Page 7: ...all not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is...

Page 8: ...ty Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial...

Reviews: