PSW2000

Operating Instructions Dual Pressure Switch

Shop online at

User

s Guide

PSW2000.qxp  6/12/2008  10:37 AM  Page cov-3

Summary of Contents for PSW2000

Page 1: ...omega com e mail info omega com For latest product manuals omegamanual info PSW2000 Operating Instructions Dual Pressure Switch Shop online at User sGuide PSW2000 qxp 6 12 2008 10 37 AM Page cov 3 ...

Page 2: ... 7056 9398 0 FAX 49 0 7056 9398 29 Toll Free in Germany 0800 639 7678 e mail info omega de United Kingdom One Omega Drive River Bend Technology Centre ISO 9002 Certified Northbank Irlam Manchester M44 5BD United Kingdom TEL 44 0 161 777 6611 FAX 44 0 161 777 6622 Toll Free in United Kingdom 0800 488 488 e mail sales omega co uk OMEGAnet Online Service Internet e mail omega com info omega com It is...

Page 3: ...ems according PED 97 23 RC Only install or uninstall the device when depressurized Mount the pressure switch from bottom to the fitting with a wrench hex 36 1 4 resp 19 with 45 Nm torque Electrical connection depends on the type of pressure switch see type label according to the chart below Electrical connections PSW3000 Dimensions in mm Plug M 12 x 1 4 pin Model with 1 switching output Model with...

Page 4: ...or SP2 if the ON value is smaller than the OFF value the switching point evaluation is falling 0 xxx Switch off point for SP2 0 0 s 9 9 s Switch on delay for SP2 in seconds 0 0 s 9 9 s Switch off delay for SP2 in seconds Inversion of switching output SP2 List of functions 4 mbar bar unit display on every 30 sec no unit display psi x 10 Window technology standard evaluation high level fail save nor...

Page 5: ...low 25 of the measuring range the analog output is switched off 0 xxx Display of peak value Max xxxx max 125 f s Delete the maximum value memory Error display Note When changing units from psi to bar or bar to psi the switching point values must be changed accordingly exceeding neg measuring range sensor error no error exceeding pos measuring range data error EEProm program error error switching o...

Page 6: ...ialog item is shown and can be altered with the and keys If the dialog with the unit is not continued within two minutes the device automatically returns to the measuring mode without accepting the new values To terminate programming more quickly you can switch back to the measuring mode primary menu from any item in the menu by holding the M key pressed for five seconds If the key lock has been a...

Page 7: ...xceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Should any Product s...

Page 8: ...wheel Systems 䡺 Totalizers Batch Controllers pH CONDUCTIVITY 䡺 pH Electrodes Testers Accessories 䡺 Benchtop Laboratory Meters 䡺 Controllers Calibrators Simulators Pumps 䡺 Industrial pH Conductivity Equipment DATA ACQUISITION 䡺 Data Acquisition Engineering Software 䡺 Communications Based Acquisition Systems 䡺 Plug in Cards for Apple IBM Compatibles 䡺 Datalogging Systems 䡺 Recorders Printers Plotter...