OMWT-SOFT-OPC Server
OMWT-SOFT-OPC Server Tags
x
41
Repeater: REPEATER
n
(OMWT-REPEAT)
online
(R)
- indicates if the device is communicating (0 or 1)
polltime
(R/W)
- how often to poll the device (in milliseconds)
nodaladdress
(R)
– (TCP/IP Receiver). The node address starts at 1. For
TCP/IP Receivers, the node address corresponds to the node number
for the TCP/IP connection.
repeateraddress
(R)
– (Wireless mode) contains the location identifier of
the OMWT-REPEAT Repeater. If the sensor did not pass through a
repeater then the value is 0.
serialno
(R)
- registration number of the access/control reader
updatecount
(R/W)
– value is incremented whenever the sensor is updated.
battery
(R)
- current battery voltage (in volts)
locatorid
(R)
– location id of the repeater. This is the id that is attached to
sensor packets and is represented by the OPC item “repeateraddress”.
(starts with “a”)
cnt418
(R)
– count of packets received through the 418 Mhz receiver.
cnt900
(R)
– count of packets received through the 900 Mhz transiever.
radionetwork
(R)
– describes the set 900 Mhz network class of the repeater
(R) –
indicates that the tag is readable.
(W) –
indicates that the tag is writeable only.
(R/W) –
indicates that the tag is both readable and writeable. OPC Write operations
will either change an I/O point at the device, or an operation will be performed.