Digital Filtering for Analog Inputs 

9  

Safety

The digital filter is updated once per conversion.  It is an “IIR” running average filter 
that emulates a simple RC filter.  The equivalent time constant is determined by the 

Filter Constant and the sum of the conversion times for the two channels.  The Filter 

two input mode selections.  This filter delay is in addition to the PLC scan delay.  

Constant determines the weight given to the most recent conversion.   

The following table lists the equivalent time constant for the three possible total  
conversion times, which are dependent upon the 

Equivalent RC Time Constant in Seconds 

(Nominal time to reach 63% of final value.)

 

Total Conversion Time in Seconds 

Filter Constant 

0.03 

0.09 

0.13 

0* 

0.03* 

0.09* 

0.13* 

0.07 

0.18 

0.27 

0.13 

0.35 

0.53 

0.27 

0.71 

1.07 

0.53 

1.41 

2.13 

1.07 

2.83 

4.27 

2.14 

5.65 

8.54 

4.28 

11.30 

17.08 

* No filter delay,  reading is unfiltered conversion value 

Thermocouple Grounding Schemes 

All applicable codes and standards need to be followed in the installation of this 

product.   

  Adhere  to  the  following  safety  precautions  whenever  any  type  of  connection  is 

made to the module:  

Connect the safety (earth) ground on the power connector first before making any 

other connections. 

  When  connecting  to  electric  circuits  or  pulse-initiating  equipment,  open  their 

related breakers. 

 Do not make connections to live power lines. 

 Make connections to the module first; then connect to the circuit to be monitored. 

Route power wires in a safe manner in accordance  with  good  practice and local 

codes. 

 Wear proper personal protective equipment including safety glasses and insulated 

gloves when making connections to power circuits. 

Ensure hands, shoes, and floor are dry before making any connection to a power 

line. 

 Make sure the unit is turned OFF before making connection to terminals. 

 Make sure all circuits are de-energized before making connections. 

Before each use, inspect all cables for breaks or cracks in the insulation.  Replace 

immediately if defective.  

 Use Copper Conductors in Field Wiring Only, 60/75° C.  

Warning:  Consult 

user documentation.

Warning:  Electrical 
Shock Hazard. 

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or 
Non-hazardous locations only

WARNING – EXPLOSION HAZARD – Substitution of components may impair 

suitability for Class I, Division 2 

AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE 

COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES 
EMPLACEMENTS DE CLASSE 1, DIVISION 2

WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power 
has been switched off or the area is known to be non-hazardous. 

AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR 

L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE 

L'EMPLACEMENT EST DESIGNE NON DANGEREUX.

WARNING:  To avoid the risk of electric shock or burns, always connect the safety 

(or earth) ground before making any other connections.  

WARNING:  To reduce the risk of fire, electrical shock, or physical injury it is 
strongly recommended to fuse the voltage measurement inputs.  Be sure to locate 
fuses as close to the source as possible. 

WARNING:  Replace fuse with the same type and rating to provide protection 

against risk of fire and shock hazards.   

WARNING:  In the event of repeated failure, do not replace the fuse again as a 

repeated failure indicates a defective condition that will not clear by replacing the 

fuse.  

WARNING:  Only qualified electrical personnel familiar with the construction and 

operation of this equipment and the hazards involved should install, adjust, 

operate, or service this equipment.  Read and understand this manual and other 

applicable manuals in their entirety before proceeding.  Failure to observe this 
precaution could result in severe bodily injury or loss of life. 

Ungrounded Thermocouples

Alternate Shield Connection for 

Ungrounded Thermocouples.

Ungrounded Thermocouples 

Preferred Shield Connection for 

Ungrounded Thermocouples.

Grounded Thermocouples 

Field Ground Potential Less 

Than Seven Volts AC 

Typical Shield Connection for 

Grounded Thermocouples

Grounded Thermocouples 

Field Ground Potential Less Than Seven Volts AC 

Shields Connected at One End Only May be Used to 

Reduce Noise 

Grounded Thermocouples May Use the Ungrounded 

Thermocouple Shield Connections if the Shield is not 

Grounded at the Field End

Note:  The examples for thermocouple grounding schemes above are generic illustrations. 

The XT105 has two thermocouple inputs. 

This device complies with part 15 of the FCC Rules. Operation is subject to the 
following two conditions: 

1.  This device may not cause harmful interference. 

2.  This device must accept any interference received, including interference 

that may cause undesired operation.  

When found on the product, the following symbols specify:

Summary of Contents for HE-XT105

Page 1: ...il info omega com For latest product manuals omegamanual info User sGuide Shop online at MADE IN HE XT105 12 Digital DC Inputs 12 Digital DC Outputs 2 Analog Inputs Including T C RTD High Resolution 2 Analog Outputs ...

Page 2: ...aged by the United Kingdom Office Toll Free 0800 466 342 TEL 33 0 161 37 29 00 FAX 33 0 130 57 54 27 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany Toll Free 0 800 6397678 TEL 49 0 7059 9398 0 FAX 49 0 7056 9398 29 e mail info omega de United Kingdom OMEGA Engineering Ltd ISO 9001 Certified One Omega Drive River Bend Technology Centre Northbank Irlam Mancheste...

Page 3: ...0 C J 1382 0 F to 346 0 F 750 C to 210 C K N 2498 0 F to 400 F 1370 C to 240 C Safe input voltage range 10 VDC 0 5 V to 15 V 20 mA 0 5 V to 6 V RTD T C 24 VDC V 0 1 e g n a R e d o M n o m m o C e l p u o c o m r e h T Nominal Resolution 10V 20mA 100mV 14 Bits RTD Thermocouple 16 Bits a m g i S a t l e D e p y T r e t r e v n o C Max Error at 25 C excluding zero 4 20 mA 0 10 0 20 mA 0 10 0 10 VDC ...

Page 4: ...s Removable Memory for data logging screen captures program loading and recipes Horner Part No HE MC1 Serial Communications MJ1 RS 232 RS 485 Use for Cscape programming and Application Defined Communications MJ2 RS 232 RS 485 Use for Application Defined Communications J1 J2 J3 JP2 JP1 JP3 JP4 001XLE030 Location of I O jumpers JP and wiring connectors J1 J3 Wiring Specifications For I O wiring disc...

Page 5: ...a e R 0 3 I I31 Error 6 MJ2 Pinouts in Full and Half Duplex Modes J2 Black Name 0V Ground V V NC No Connect Q12 OUT12 Q11 OUT11 Q10 OUT10 Q9 OUT9 Q8 OUT8 Q7 OUT7 Q6 OUT6 Q5 OUT5 Q4 OUT4 Q3 OUT3 Q2 OUT2 PWM2 Q1 OUT1 PWM1 V Supply for Sourcing Outputs I1 I2 I3 I4 H2 H3 H4 0V I5 I6 I7 I8 NC NC H1 001XLE007 12 24 VDC J1 Orange Positive Logic Digital In Q1 Q2 Q3 Q4 Q9 Q10 Q11 Q12 Q5 Q6 Q7 Q8 V 0V LOAD ...

Page 6: ...sion 2 Groups A B C and D or Non hazardous locations only WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I Division 2 AVERTISSEMENT RISQUE D EXPLOSION LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1 DIVISION 2 WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area...

Page 7: ...ise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Shoul...

Page 8: ... Indicators 䡺 Turbine Paddlewheel Systems 䡺 Totalizers Batch Controllers pH CONDUCTIVITY 䡺 pH Electrodes Testers Accessories 䡺 Benchtop Laboratory Meters 䡺 Controllers Calibrators Simulators Pumps 䡺 Industrial pH Conductivity Equipment DATA ACQUISITION 䡺 Data Acquisition Engineering Software 䡺 Communications Based Acquisition Systems 䡺 Plug in Cards for Apple IBM Compatibles 䡺 Data Logging Systems...

Reviews: