2.3.2 Process Current
The figure below shows the wiring hookup for Process Current 0 – 20 mA.
Figure 2.5 Process Current Wiring Hookup
(Internal and External Excitation)
2.3.3 Process Voltage
The figure below shows the wiring hookup for Process Voltage 0 – 100 mV,
0 – 1 V, 0 – 10 V.
Figure 2.6
a) Process Voltage Wiring Hookup b) Process Voltage Wiring Hookup
with Sensor Excitation
without Sensor Excitation
R
L
-
Voltage limited resistor, which allows to convert 24 Vdc internal excitation
voltage to the appropriate process input value. For instance: if the potentiometer
value is equal to 10 kΩ, the minimum R
L
is 14 kΩ for 10 V process input.
When configuring your instrument, select Process Type in the Input Type Menu
(see Part 3).
8