5.7 Safety functions
For protection against low-pressure, the low-pressure switch is added (RDP 750-1900). Other safety
functions are implemented in the controller.
5.7.1 Low-pressure switch
LPS: Low-pressure protection device on the suction side of the compressor trips, if the pressure drops
below the pre-set value. The values are automatically reset when the nominal conditions are restored.
Calibrated pressure: R 134.a Stop 0.7 barg - Restart 1.7 barg
5.7.1 Safety functions of RDC 2
ALARM
DISPLAY
CAUSE - PROPOSED ACTIVITY
»P
F
«
Temperature sensor failure - Ensure that the temperature sensor is properly
connected to the controller / replace the temperature switch
1
–
Dew point sensor
2
–
Compressor sensor
3
–
Condensation sensor
»
Cln
«
High condensation temperature/pressure
–
Check that the temperature sensor
is correctly inserted into its position, check the cooling system sealing / charging
/ check the hot gas bypass valve
»L
t
«
Low dew point temperature - Check that the temperature sensor is correctly
inserted into its position, check the cooling system sealing / charging / check the
hot gas bypass valve
»
Ht
«
High compressor outlet temperature
–
Check that the temperature sensor is
correctly inserted into its position, check the cooling system sealing / charging /
check the hot gas bypass valve
5.8 Filter / dehydrator
Moisture and impurities can be present in the refrigeration circuit. This can reduce the lubrication of
the compressor and block the expansion valve or capillary tube. The dryer filter / dehydrator is located
in front of the capillary tube to remove moisture and impurities from the circulation system.
5.9 Capillary tube
The capillary tube is located between the condenser and the evaporator and functions as a metering
device for reducing the pressure of the refrigerant. The pressure reduction is a design-based function.
The length and inner diameter of the capillary tube are precisely dimensioned, ensuring good
performance in all designed conditions.
Summary of Contents for RDP 20
Page 28: ...28 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation ...
Page 29: ...29 ...
Page 30: ...30 17 Drawings of RDP refrigeration air dryers RDP 20 100 ...
Page 31: ...31 RDP 140 235 ...
Page 32: ...32 RDP 300 480 ...
Page 33: ...33 RDP 600 950 ...
Page 34: ...34 RDP 1150 1900 ...
Page 35: ...35 RDP 2600 ...
Page 36: ...36 16 Electro schemes of RDP refrigeration air dryer RDP 20 180 ...
Page 37: ...37 RDP 235 600 ...
Page 38: ...38 RDP 750 1900 ...
Page 39: ...39 RDP 2600 ...