Siemens V20_EN_rev01-08032019.docx
9-7
9.3.2
Setting motor data
Functionality
Parameter setup is already made by Omarlift. After a factory reset may be necessary to set the param-
eter setup. (Please, contact Omarlift Service).
Setting parameters
In the menu setup (
→ 9.2.2) the value of this parameter must be entered according to the rating plate of the
motor.
Parameter
Access
level
Function
Text Menu
(se P8553 = 1)
P0100
1
50 / 60 Hz selection
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
(EU
–US)
P0304[0]
1
Rated motor voltage [V]
Note that the input of rating plate data must correspond with
the wiring of the motor (star / delta)
(MOT V)
P0305[0]
1
Rated motor current [A]
Note that the input of rating plate data must correspond with
the wiring of the motor (star / delta)
(MOT A)
P0307[0]
1
Rated motor power [kW / hp]
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
P0100 = 0 o 2:
(MOT P)
P0100 = 1
(M COS)
P0308[0]
1
Rated motor power factor (cos
φ)
Visible only when P0100 = 0 or 2
(M COS)
P0309[0]
1
Rated motor efficiency [%]
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
(M EFF)
P0310[0]
1
Rated motor frequency [Hz]
(M FREQ)
P0311[0]
1
Rated motor speed [RPM]
(M RPM)
P1900
2
Select motor data identification
= 0: Disabled
= 2: Identification of all parameters in standstill
(MOT ID)
Alternatively you can ingress the motor configuration using the Parameters menu (
→ 9.2.2), and input:
P0003 = 3
P0010 = 1