ELECTRICAL CONNECTIONS
1
1
2
2
3
3
4
4
5
Dismantle the luminaire by pushing the lock/unlock hooks
on each side and pull it down.
Pass thru the cables from the entry hole and connect them
as shown in the picture.
N
for neutral
L
for live wire and
PE
for ground (optional).
Connect the battery’s connector to the respective
connector on P.C.B.
Place upwards the luminaire until the plastic hooks are
securely locked.
Power on the device
.
FLAG MOUNTING INSTALLATION (optional)
Install the flag mounting base on the wall (page 3) and
perform the respective steps of the electrical connections.
SURFACE MOUNTING ON A WALL (single sided)
Dismantle the luminaire, install the plastic bracket on the
wall (page 3) and perform the respective steps of the
electrical connections.
CEILING INSTALLATION
Dismantle the luminaire, install the plastic bracket on the
ceiling (page 3) and perform the respective steps of the
electrical connections.
HANGING INSTALLATION (optional)
Install the mounting base (tube) on the ceiling (page 4)
and perform the respective steps of the electrical
connections.
NOTE!! After finishing the installation you must power
the luminaire for at least 24 hours for battery charging
to perform the named autonomy.
INSTALLATION INSTRUCTIONS
SURFACE MOUNTING ON A WALL
(
single side luminaire
)
FLAG MOUNTED ON A WALL
MOUNTING METHODS
CEILING MOUNTED
If necessary place the included
spacers to mount the base.
If necessary place the included
spacers to mount the base.
Test
button
Charge Lamp fault
Battery
fault
Indications
device enters regular
operation mode.
Changing the operating mode
Press and hold the TEST button for more
than 5 seconds
.
T
he l
uminaire
will erase first
the errors (3 LED indicators will light in
succession) and
after
2 seconds the LED
Lamp Fault will remain lit steadily.
When the
TEST button
is released
, the l
uminaire
will
change between
maintained or no-maintained
mode.
The change is recorded permanently
in it’s memory.
Indication LED status (with connected
mains power supply).
Charge
On:
Good charge condition.
Οff:
No battery
(
No charging current
or disconnected battery
).
Lamp fault
Οn
(with LED strip off)
:
faulty LED strip (must
be replaced).
Οn
(with LED strip on)
:
Problem in the back
up circuit of the LED strip (must be checked by
an authorized personel).
Off:
Good LED strip.
Battery Fault
Ο
ff
:
Battery OK.
Blink
(
With Charge LED ON):
Autonomy or
low battery problem
(the battery must be
replaced).
Blink
(
With Charge LED Off):
No charging
current or disconnected battery
.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only
.
2.
The device must be connected to the mains
power supply through a fuse that is dependent
on the total amount of the line’s power load
.
In case of battery or lamp replacement,
these must be replaced by parts with same
type, by the manufacturer or by a competent
person.
t i
in battery recycling
points. Do not incinerate.
3.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery’s connector.
5
.
I
s not allowed to discard batteries in to
common trash bins, they must be
discarded only
922502500_09_001
922502500_09_001
L
N
PE