olympia electronics KLD-22/ST Quick Start Manual Download Page 2

922502051_09_010

922502051_09_010

922502051_09_010

2

Installation methods

Wall mounting

Luminaire disassembly

3

2

1

Ενδεικτικά

1

2

Insert the

power cable

Insert the

cable grommet

Insert the

cable grommet

Insert the

power cable

Insert the

power cable

>5mm

Insert the

power cable

Insert the

cable grommet

Ceiling mounting

1

1
1
1
1
1

Luminaire

Set of Pictograms

Manual

Package contents

General

Hanging installation

Wall mounting accessories
Ceiling mounting accessories

Push  the  test  button  for  more  than  10  seconds,  to 
delete all the LED indicated errors. Then  the device 
enters regular operation mode.

1.

  Operations  for  installation,  maintainance  or 

testing must be done by authorized personnel only.

3.

  In  case  of  battery  replacement,  this  must  be 

replaced  by  part  of  the  same  type,  by  the 
manufacturer or by a competent person.                

5.

  The  control  gear  is  not  proof  against  supply 

voltage polarity reversal.

ΑΤΤΕΝΤΙΟΝ!!!

 

Automatic Autonomy Test

The  Automatic  Autonomy  Test  is  conducted  every  6 
months and measures the device’s back up operation 
and  emergency  duration.  This  test  includes  all 
functions of the Manual Autonomy Test.

Resetting errors

2.

 The device must be connected to the mains power 

supply through a fuse  that is dependent on the total 
line’s  power load.

4.

 In case of inactive use for a period greater than 2 

months,  disconnect  the  battery  by  pulling  out  the 
battery’s connector. 

6.  It  is  not  allowed  to  discard  batteries  into 

common  trash  bins,  they  must  be  discarded 
only    in  battery  recycling  points.  Do  not 
incinerate.

Connectors
CN10:

 Power connector

CN7:

 Recess LED Port

CN9:

 Module Port

CN6 & CN7:

 Battery connector

CN5:

  Non user connector

CN11:

 Communication Port

During the Test the lamp fault LED blinks. 

Manual Autonomy Test

Automatic Operational Test

o

These  luminaries  are  used  indoors  (ta  40 C)  where 
emergency  light  is  needed.  Each  luminary  must  be 
permanently  connected  to  mains  power  supply.  In 
normal operation the led strip lights and the battery 
is  charging.  In    case    of    a    mains    power    supply 
failure    the  luminary  will  light  the  led  strip 
automatically  in  emergency  mode  (powered  by  its 
battery). When the mains  power  supply  is  restored 
the device turns to normal operation.

This test includes all the operations that provide the 
manual test and is conducted automatically every 15 
days.  In  order  to  be  performed,  the  mains  power 
supply and the battery should be connected.

A duration test can be conducted if the TEST button 
is pressed from 5 to 10 seconds. The luminary enters 
emergency mode, the charge LED is turned OFF and 
the  Battery  Fault  led  starts  to  blink.  The  test  is 
conducted until the battery is depleted.If at the end 
of  the  test  the  autonomy  is  low  then  the  Battery 
Fault LED will be ON. If the result of the test is good 
then  the  luminary  enters  charging  mode  and  the 
Charge led starts to blink until the batteries are fully 
charged.

Manual  test  for  emergency  operation  and  light 
source.
The manual test can be conducted only if the mains 
power supply and the battery is connected:

Description

Indications LED Status

BATT.

FAULT

(yellow)

LAMP
FAULT

(red)

CHARGE

(green)

Fully charged

Charging

Battery fault or
emergency mode

Operational test

Light source fault

Autonomy test

Duration fault

Note:

Permanently

ON

Blink

Indifferent

Off

After the desired installation follow the steps below

1

2

ON

1 2 3 4

Maintained operation

ON

1 2 3 4

Non-maintained operation

N
L

Power Connection

Ν

 for neutral, 

L

 for live wire

DS1

1h

ON

1 2 3 4

3h

(default position)

ON

1 2 3 4

8h

ON

1 2 3 4

Autonomy duration selection

The  user  can  select  one  of  the  3  available  minimum  autonomy  durations  1  hour,  3  hours  and  8 
hours.  The  selection  must  be  done  while  the  luminaire  is  disconnected  from  AC  and  battery 
supplies. The selection is achieved through Switches 2 & 3 of DS1. Switch 1 is not used. 

Changing the operating mode

The control of maintained or non maintained operation of the luminary is achieved through Switch 
4 of DS1. For maintained operation, switch number 4 must be in ON position. For non-maintained 
operation, switch number 4 must be in OFF position.

Technical label installation

Two additional labels are included in the package. one for 1 hour duration (60) and one for 8 hour 
duration  (480).  Depending  on  the  selected  duration,  the  installer  must  cover  the  default  3  hour 
(180) printing with one label that has the required duration. Please take notice of the orientation of 
the label.

3

4

Luminaire assembly

Battery Connection

L

N

Insert the

power cable