the  faulty  lamp  is  replaced  then  the  error  is 
automatically  restored  and  the  indicator  is 
turned OFF.

AUTOMATIC EMERGENCY CIRCUIT TEST

The  unit  automatically  tests  the  emergency 
circuit every 15 days (if the battery and mains 
power  are  connected)  .  During  this  test  the 
lamps are turned ON for 3 seconds using the 
batteries. In some cases this function might not 
be acceptable (i.e in cases this function might 
not be acceptable (i.e in cinema theaters) so the 
installer must take this into account during the 
installation.

AUTOMATIC DURATION TEST

This  test  is  conducted  every  6  months  by 
simulating  a  power  failure,  if  the  battery  and 
mains  power  supply  are  connected.

 

The  unit 

lights the lamps using the charged battery and 
counts the time until the stated duration. If the 
lamps are ON during the end of the test then the 
unit is restored to its normal operation (lamps 
OFF and battery charging). If the lamps go OFF 
before  the  end  of  the  test  then  the  unit  is 
restored to its normal operation but the LAMP

 

FAULT

  / 

BATT

FAULT  indicator  is  lit  to  show 

that there is a problem with the battery and that 
the battery must be replaced.

 

Let it be noted that 

this duration test is also done during every long 
power failure. If the power failure lasts for a long 
time  and  the  luminaire  has  entered  the 
BATTERY  CUTOFF  mode  and  the  duration 
measured is not correct then the fault indicator 
will light when the power is restored.

ERASING ERRORS

Erasing  errors  is  accomplished  with  a 
prolonged pressing of the TEST button 

(>5 

sec

when the unit is connected to the mains power 
supply.

 

The  fault  indicated  with  the  indicator 

 

LAMP

 

FAULT

 / 

BATT

FAULT

 

will be erased. If 

the cause of the fault has not been restored (i.e 
burned lamp) then the indicator will light again. 
If  the  fault  was  caused  by  a  low  emergency 
duration and you erase the error then this will be 
indicated  again  during  the  next  duration  test 
after 6 months. In this case (for duration errors) 
it is vital to replace the battery before erasing 
the error (the error is automatically erased if the 

mains power and the battery are disconnected).

WARNING !!!

1. Every test, installation or maintenance
    procedure must be done only by qualified
    personnel.

2. 

The unit must be connected to the mains

    power supply using a line fuse rated
    accordingly.

3. 

The replacement of the battery and the

    light source must be done using parts of
    the same type, by the manufacturer or by
    a competent person.

t i

in  battery  recycling 

points. Do not incinerate.

Battery replacement

 

It can be done only by a competent person 
and after the mains interruption

.

1.

 Follow the step 2 

o

f the installation

    

procedure.

2.

 Disconnect the 

cables

 and remove the

    

old battery.

3.

 Connect the new battery with the same

    

type (step 

3

 of the installation procedure)

    

and place it in the position

 

of the old

 

one.

4.

 Follow the step 

6

 of the installation

    

procedure and power the device.

Connection  to  module  (After  request)

This  luminary  can  be  connected  to  any  of  the 
following  modules:  Remote  module,  address 
module

wireless  module  and  fault  relay 

module.  If  you  connect  it  to  a  module  that 
supports  inhibit  or  rest  mode,  you  should 
know  that  these  commands  can  be  cancelled 
only  during  normal  mode  (ie.  not  in 
emergency).  For  installation  refer  to  step  5  of 
the  istallation  procedure  in  page  3.
Also  refer  to  the  user  manual  of  each  module 
for  additional  information.

4. 

If the luminaire must be isolated from the

    mains power supply for more than 2
    months then the batteries must be
    disconnected by removing the battery
    connectors.

5. 

I

s not allowed to discard batteries in to 

common  trash  bins,  they  must  be 
discarded  only 

 

923037006_09_00

6

INDICATION LED STATUS (with the mains power supply connected

)

Indicator ON

Indicator Blinking

Indicator OFF

POWER / CHARGE

LAMP FAULT / BATT. FAULT

Disconnected battery

 / 

not charging

Normal operation mode

Charged battery

Low emergency duration

 (

replace battery

)

Battery under charge

Lamp fault (Check lamps and replace if needed)