and  emergency  duration.  This  test  is 
conducted  automatically  every  6  months.  In 
order  to  be  performed,  the  mains  power 
supply  and  the  battery  should  be  connected 
and  fully  charged.  If  the  battery  is  not  fully 
charged, the test is postponed until the battery 
is    completely  charged.  If  during  this  test,  the 
autonomy is less than nominal then the battery 
fault  led  turned  on  continuously  and  the 
battery must be replaced. 

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency  mode  is  at  least  the  one  that  is 
stated 

in 

the 

list 

of 

the 

technical 

characteristics.  During  emergency  mode,  a 
light source test is also performed.

Resetting Errors

Push  the  TEST/RESET  button  for  5  seconds, 
to delete all the indicated LED errors (page 3). 
Then  the  luminaire  enters  regular  operation 
mode.

Indication  LED  status  (with  connected 
mains power supply).
Charge 
On:
 

Good charge condition.

Οff: 

No battery (No charging current 

or disconnected battery).

Lamp Fault 

with L1 connected to L

Οn  (with  LED  strip  off): 

Faulty  LED  strip 

(must be replaced).

Οn (with LED strip on): 

Problem in the back 

up circuit of the LED strip (must be checked by 
an authorized personnel).

Off:

  Good LED strip.

Battery Fault 
Οff:
 

Battery OK. 

Blink  (With  Charge  LED  ON):

  Autonomy  or 

low  battery  problem 

(the  battery  must  be 

replaced).
Blink  
(With  Charge  LED  Off): 

No  charging 

current or disconnected battery.

ΑΤΤΕΝΤΙΟΝ!!!

1.  Operations  for  installation,  maintainance  or 
testing  must  be  done  by  authorized  personel 
only, after a mains interruption.
2. The device must be connected to the mains 
power supply through a fuse dependent on the 
total amount of the line’s  power load.

In  case  of  battery  or  lamp  replacement, 

these  must  be  replaced  by  parts  of  the  same 
type,  by  the  manufacturer  or  by  a  competent 
person.

                

3. 

4. In case of inactive use for a period greater 

than  2  months,  disconnect  the  battery  by 
pulling out the battery’s connector. 
5. 

I s not allowed to discard batteries in to 

common  trash  bins,  they  must  be 
discarded  only 

t i

  in  battery  recycling 

points. Do not incinerate.

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained 

  

1: 

Maintained (*)

A: 

Including test device 

 

G: 

Internally illuminated 

 

*480: 

8 hours duration

(*)  Maintained  operation:  The  luminaire  lights 
its  illumination  source,  when  it  is  powered  by 
the mains power supply or not. 
Non Maintained operation: The luminaire lights 
its illumination source, only in   power supply’s 
failure.
 
Note!!  The  installer  should  fill  in,  on  the 
specification label, the letter 

G

 if the luminaire 

is used as a safety sign.

NOTE!!  After  finishing  the  installation  you 
must  power  the  luminaire  at  least  for  24 
hours  for  battery  charging  to  perform  the 
nominal autonomy. 

Battery replacement

 

It can be done only by a competent person 
and after the mains interruption.

1. Unfasten the 4 retaining screws (not all the 
way) (step 10 of the installation instructions) 
and remove the diffusor.
2.  Unfasten  the  2  retaining  screws  (step  9  of 
the  installation  instructions)  and  remove  the 
reflector.
3. Remove the old battery and place a new 
one of the same type and characteristics.
4. Replace the removed parts (previous steps 
1,2). 

The  light  source  contained  in  this  luminaire 

s h a l l   o n l y   b e   r e p l a c e d   b y   t h e  
manufacturer,  or  his  agent,  or  a  similar 

qualified person.

NOTE! The light source is non-user 
replaceable.