GENERAL

This  luminaire  is  used  in  places  where 
emergency luminaires are needed.
E a c h   l u m i n a i r e   m u s t   b e   p e r m a n e n t l y  
connected to mains power supply.
In normal operation the led strip lights and the 
capacitor is charging.
In    case    of    a    mains    power    supply  failure   
t h e   l u m i n a i r e     w i l l     l i g h t   t h e   l e d   s t r i p    
automatically  in  emergency  mode.    When  the   
mains    power    supply    is    restored  the  device 
turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

Capacitor charging

The  capacitor  charging  is  completely  and 
accurately controlled. In this case, is achieved 
the  perfect  capacitor  maintenance,  as  well  as 
the  elongation  of  its  duration.  When  the 
capacitor  has  completely  charged,  it  charges 
with a maintenance current.

Capacitor Cut-off

The  luminaire  enters  in  this  operation  when 
the mains power supply fails and capacitor has 
lost  its  energy.  During  this  operation  the 
luminaire  enters  the  idle  state  and  the 
capacitor’s consumption is negligible.

Manual Test

The  manual  test  can  be  conducted  only  if  the 
main  power  supply  and  the  capacitor  is 
connected. By pressing the TEST/RESET 

button briefly (page 3) an emergency operation 
test  is  initiated.  During  this  test  period  all 
indication  LEDs  are  OFF  and  the  whole 
emergency circuit is monitored. 

Automatic Operational Test

This test includes all the operations that provide 
the manual test and is conducted automatically 
every  15  days.  In  order  to  be  performed,  the 
main power supply and the capacitor should be 
connected. 

Manual Autonomous Test

If  the  Test  button  is  pressed  for  a  period 
between  5  to  10  seconds  (with  the  capacitor   
fully charged), the illumination sign will enter in 
counting autonomy condition. 

If the capacitor is 

not fully charged this command is ignored

.

The  BAT  FAULT  LED  blinks  during    the 
measurement,  indicating  this  process  to  the 
user.  This  measurement  duration  is  equal  with 
the  nominal  autonomous  duration  of  the 
luminaire  and  at  the  end  of  the  process,  if  the 
measured  duration  was  at  least  the  nominal 
autonomous  duration,  the  BAT  FAULT  LED  is 
turned  OFF,  in  the  other  hand  stays 
continuously  ON  indicating  to  the  user  that  the 
capacitor must be replaced.          

Automatic Autonomous Test

The  Automatic  Autonomous  Test  is  conducted 
and  measures  the  luminaire’s  sign’s  back  up 
operation  and  emergency  duration. This  test  is 
conducted  automatically  every  six  months.  In 
order to be performed, the main power supply 

Page 1 from 4

GR-900/30L/SC

 Waterproof Self Testing Maintained Emergency Luminaire 

220-240V AC/50-60Hz

TECHNICAL CHARACTERISTICS

 

(for LED module specifications see page 4)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS (L x W x H) 
TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BACK UP  SOURCE

CHARGING TIME

INDICATIONS - CONTROLS

CAPACITOR PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

LIGHT SOURCE INTENSITY 

ILLUMINATION SOURCE

3h

CHARGE, LAMP FAULT, BAT FAULT, TEST button

From overcharge

-30 to 40  C

o

Up to 95% 

10 years

363 x 145 x 73 mm 

  White LEDs 

7W / 7.5VA /PF: 0.93

923900000_09_007

IP65

60 min

  250lm 

/ 95lm (emergency) 

(230V AC) 

1055gr.

Ultra Capacitor A-900

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3