GENERAL
This luminaire is used in places where
emergency luminaires are needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply.
In normal operation the led strip lights and the
capacitor is charging.
In case of a mains power supply failure
t h e l u m i n a i r e w i l l l i g h t t h e l e d s t r i p
automatically in emergency mode. When the
mains power supply is restored the device
turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
Capacitor charging
The capacitor charging is completely and
accurately controlled. In this case, is achieved
the perfect capacitor maintenance, as well as
the elongation of its duration. When the
capacitor has completely charged, it charges
with a maintenance current.
Capacitor Cut-off
The luminaire enters in this operation when
the mains power supply fails and capacitor has
lost its energy. During this operation the
luminaire enters the idle state and the
capacitor’s consumption is negligible.
Manual Test
The manual test can be conducted only if the
main power supply and the capacitor is
connected. By pressing the TEST/RESET
button briefly (page 3) an emergency operation
test is initiated. During this test period all
indication LEDs are OFF and the whole
emergency circuit is monitored.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the capacitor should be
connected.
Manual Autonomous Test
If the Test button is pressed for a period
between 5 to 10 seconds (with the capacitor
fully charged), the illumination sign will enter in
counting autonomy condition.
If the capacitor is
not fully charged this command is ignored
.
The BAT FAULT LED blinks during the
measurement, indicating this process to the
user. This measurement duration is equal with
the nominal autonomous duration of the
luminaire and at the end of the process, if the
measured duration was at least the nominal
autonomous duration, the BAT FAULT LED is
turned OFF, in the other hand stays
continuously ON indicating to the user that the
capacitor must be replaced.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire’s sign’s back up
operation and emergency duration. This test is
conducted automatically every six months. In
order to be performed, the main power supply
Page 1 from 4
GR-900/30L/SC
Waterproof Self Testing Maintained Emergency Luminaire
220-240V AC/50-60Hz
TECHNICAL CHARACTERISTICS
(for LED module specifications see page 4)
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS (L x W x H)
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BACK UP SOURCE
CHARGING TIME
INDICATIONS - CONTROLS
CAPACITOR PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
LIGHT SOURCE INTENSITY
ILLUMINATION SOURCE
3h
CHARGE, LAMP FAULT, BAT FAULT, TEST button
From overcharge
-30 to 40 C
o
Up to 95%
10 years
363 x 145 x 73 mm
White LEDs
7W / 7.5VA /PF: 0.93
923900000_09_007
IP65
60 min
250lm
/ 95lm (emergency)
(230V AC)
1055gr.
Ultra Capacitor A-900
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3