GR-750x series
Control panel for addressable
emergency luminaires
Document number:
923750400_90_001_EN
Date: 25/5/2023
Page: 5 of 15
[5]
2 INSTALLATION
2.1 Mounting the panel
WARNING
All installation operations must be done while the panel is disconnected from mains
power supply and batteries.
Only trained personnel should carry out operations inside the
panel and only after taking all the precautionary measures.
Prior to installing/maintaining the panel, read the manual and have knowledge of the system
’
s capabilities,
functionality, and design to ensure proper operation.
Do not connect or disconnect system components while mains power supply or batteries are connected.
Prior to any operation inside the enclosure of the panel, ESD prevention measures should be taken.
The panel mounting area must be clean, dry, and free of collisions and vibrations. The panel must be
permanently installed on a fixed position in an indoor location. In (Figure 1) the interior mounting holes of the
panel are marked. Use all three mounting holes with the included wall mounting accessories of the package for
proper installation (plugs and screws).
The panel should be placed at least 1m above floor level, 1m bellow roof level and at a minimum distance of
30cm from other electronic devices. No other lines should cross the wall behind the panel except the panels
own power supply. The panel should be placed in a visible and accessible area to
the building’s stuff, fire and
lighting safety personnel.
Figure 2 - Panel's interior