Automatic Operational Test
Automatic Autonomy Test
The Automatic Autonomy Test tests the
device’s back up operation and emergency
duration. This test is conducted automatically
every 6 months. In order to be performed, the
mains power supply should be connected and
the battery must be fully charged
.
If the
battery is not fully charged
,
the test is
postponed
until the battery is completely
charged. If during this test, the autonomy is
less than nominal then the battery fault LED
will permanently be on and the battery must
be replaced.
Hold the A-1900 card in TEST position for 10
to 15 seconds in order to delete all LED
indicated errors. Then the device enters
regular operation mode.
Back Up Operation
ADDRESSABLE COMMUNICATION
The autonomy duration of battery during
emergency mode must be at least as the one
stated
in
the
list
of
the
technical
characteristics. During emergency mode, a
light source test is also performed.
Resetting Errors
The luminaire has the ability to be connected
to GR-6500 panel. In order to do so, the
luminaire’s address has to be unique in the
same bus. For more details see page 3
(installation instruction).
This test includes all the operations that are
provided in manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Ο
ff
:
Battery OK.
4. In case of inactive use for a period
greater than 2 months, disconnect the
battery by pulling out the battery’s connector.
ΑΤΤΕΝΤΙΟΝ!
!!
Blink:
Charging.
Οn:
Faulty LED.
5
.
I
s not allowed to discard batteries in
t i
to common trash bins, they must be
discarded only
in battery recycling
points. Do not incinerate.
Οff:
No battery
(
No charging current
Lamp Fault
Indication LED status (mains on)
Charge
2. The device must be connected to the
mains power supply thr
o
u
gh
a fuse
that is
dependent on the total line’s power load.
or disconnected battery
).
1. Operations for installation, maintainance
or testing must be done by authorized
personnel only
.
On:
Fully charged.
3. In case of battery or lamp replacement,
these must be replaced by parts with same
type, by the manufacturer or by a competent
person.
Off:
LED OK.
Blink:
Operational Test.
Battery Fault
ON
(
With Charge LED ON):
Autonomy or
low battery problem
(the battery must be
replaced).
Blink
(
With Charge LED Off):
Autonomy test
is performed
.
Page
2 from
9
Battery
Fault
Lamp
Fault
Charge
Indicators
92349300