Automatic Operational Test

Automatic Autonomy Test

The  Automatic  Autonomy  Test  tests  the 
device’s  back  up  operation  and  emergency 
duration. This  test  is  conducted  automatically 
every 6 months. In order to be performed, the 

mains power supply should be connected and 
the  battery  must  be  fully  charged

If  the 

battery  is  not  fully  charged

the  test  is 

postponed

 

until  the  battery  is  completely 

charged.  If  during  this  test,  the  autonomy  is 
less  than  nominal  then  the  battery  fault  LED 
will  permanently  be  on  and  the  battery  must 
be replaced. 

Hold the A-1900 card in TEST position for 10 
to  15  seconds  in  order  to  delete  all  LED 
indicated  errors.  Then    the  device  enters 
regular operation mode.

Back Up Operation

ADDRESSABLE COMMUNICATION

The  autonomy  duration  of  battery  during 
emergency mode must be at least as the one 
stated 

in 

the 

list 

of 

the 

technical 

characteristics.  During  emergency  mode,  a 
light source test is also performed.

Resetting Errors

The  luminaire  has  the  ability  to  be  connected 
to  GR-6500  panel.  In  order  to  do  so,  the 
luminaire’s  address  has  to  be  unique  in  the 
same  bus.  For  more  details  see  page  3 
(installation instruction).

This  test  includes  all  the  operations  that  are 
provided  in  manual  test  and  is  conducted 
automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery should be connected.

Ο

ff

:

 

 Battery OK. 

4.  In  case  of  inactive  use  for  a  period 
greater  than  2  months,  disconnect  the 
battery  by  pulling  out  the  battery’s  connector. 

ΑΤΤΕΝΤΙΟΝ!

!!

Blink:

 Charging.

Οn:

 

Faulty LED.

5

I

s  not  allowed  to  discard  batteries  in 

t  i

to  common  trash  bins,  they  must  be 
discarded  only 

 

in  battery  recycling 

points.  Do  not  incinerate.

Οff:

 

 

No battery 

(

No charging current 

Lamp Fault 

Indication LED status (mains on)

Charge 

2. The  device  must  be  connected  to  the 
mains  power  supply  thr

o

u

gh

  a  fuse 

  that  is 

dependent  on  the  total  line’s   power  load.

or disconnected battery

).

1.  Operations  for  installation,  maintainance 
or  testing  must  be  done  by  authorized 
personnel  only

.

On:

 

 

Fully charged.

3.  In  case  of  battery  or  lamp  replacement, 
these  must  be  replaced  by  parts  with  same 
type,  by  the  manufacturer  or  by  a  competent 
person.

                

Off:

 

 LED  OK.

Blink: 

Operational Test.

Battery Fault

 

ON

  (

With  Charge  LED  ON):

    Autonomy  or 

low  battery  problem 

(the  battery  must  be 

replaced).

Blink

 

(

With Charge LED Off): 

Autonomy test 

is performed

.

Page

 

2 from

 

9

Battery 

Fault

Lamp

Fault

Charge

Indicators

92349300

3_0

9

_001

Summary of Contents for GR-490/ADR

Page 1: ...can be conducted by holding the A 1900 card steadily for 5 to 10 seconds In order to be performed the mains power supply and the battery should be connected The luminaire enters emergency mode the cha...

Page 2: ...details see page 3 installation instruction This test includes all the operations that are provided in manual test and is conducted automatically every 15 days In order to be performed the mains powe...

Page 3: ...nnect the cables as shown in the photograph Open another cutout cable entry hole and install the second supplied cable grommet Use the supplied self adhesive pad and cable tie to anchor the cable Pass...

Page 4: ...screwing them on the plaster board ceiling 6 Open a cable entry cutout hole on the plastic base and follow step 3 in the initial installation 2 Install the supplied cable grommet from the inside of th...

Page 5: ...e mounting location 4 If the cable entry hole is not suitable then use one of the supplied cables grommets to cover the holes and open another cable entry cut out hole figure 3 Follow step 3 of the in...

Page 6: ...y For Autonomy Test you must place the card in front of TEST and hold it for 5 to 10 seconds To reset errors you must place the card in front of TEST by holding it for 10 to 15 seconds and removing it...

Page 7: ...2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3...

Page 8: ...2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3...

Page 9: ...instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re setting done by a third party unless Olympia Electronics h...

Reviews: