Page
2 from
3
Indication LED status (with connected mains
power supply).
Charge
On:
Good charge current.
Οff:
No battery
(
No charging current
or disconnected battery
).
Lamp Fault
with L1 connected to L
Οn
(with LED strip off)
:
Faulty LED strip (must be
replaced).
Οn
(with LED strip on)
:
Problem in the back up
circuit of the LED strip (must be checked by an
authorized personnel).
Off:
Good LED strip.
Battery Fault
Ο
ff
:
Battery OK.
Blink
(
With
Charge LED
ON): Autonomy or low
battery problem
(the battery must be replaced).
Blink
(
With
Charge LED
Off):
No charging current or disconnected battery
.
ΑΤΤΕΝΤΙΟΝ
!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
2.
The device must be connected to the mains
power supply through a fuse dependent by the
total amount of the line’s power load
.
In case of battery or lamp replacement, these
must be replaced by parts of the same type, by the
manufacturer or by a competent person.
t i
in battery recycling
points. Do not incinerate.
3.
4. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
5
.
I
s not allowed to discard batteries in to
common trash bins, they must be
discarded only
923416001_09_00
8
In order for the luminaire to become operational,
you have to:
1.
Remove the mounting base by removing the 4
retaining screws (figure 1).
2.
Place the mounting base to the ceiling by using the
mounting accessories (included).
3.
Connect the wires to the terminal block according to
figure 2.
4.
Connect the battery`s connector to the appropriate
connector (figure 3).
5.
Refit the luminaire`s body by placing the removed
screws in step 1.
6.
Power on the luminaire.
Also the luminaire can be used in hanging installation by
using the rings on the mounting base.
NOTE!! After finishing the installation you must
power the luminaire at least for 24 hours for battery
charging to perform the nominal autonomy.
BATTERY REPLACEMENT
It can be done only by a competent person and after
the mains interruption
.
1.
Detach the labeling frame from its base (
step
1
of the
installation procedure
)
.
2
.
Disconnect the connector and remove the old battery.
3.
Connect the new battery with the same type
and place
it in the position
of the old one.
4.
Replace the removed part (
step
1)
.
INSTALLATION INSTRUCTIONS
F
igure 1
220-240V AC / 50-60 Hz
L
N
Figure 2
Figure 3
N
1
2
N
L
L1
L1
(*)
Maintained operation: The luminaire lights its
illumination source, when it is powered by the mains
power supply or not
.
Non Maintained operation: The luminaire lights its
illumination source,
only in power supply’s failure.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
1:
Maintained (*)
A:
Including test device
G:
Internally illuminated safety sign
*90:
1.5 hour duration
18
0:
3
hours duration
Remove the
retaining screws
Mounting
Base