INSTALLATION INSTRUCTIONS

Base plastic

Cable entry channels

Luminaire mounting holes

1   To install the luminaire you must dismantle it into 3 parts.
2   Place a flat blade screwdriver in the area 

Α 

to release the diffusor’s 

     plastic hook.
3

   

Place a flat blade screwdriver in the area 

to release the reflector’s 

     plastic hook.
4   Use the included mounting parts to mount the base plastic.
     Pass the mains cable through a cable entry channel. The luminaire
     must be connected to a permanent electrical installation to ensure the
     immobilization of the cable.
5   Place the battery’s connector to the corresponding connector on the
     P.C.B.
6   Connect the mains cables to the respective detachable terminal 
     block. 

Ν for neutral

L for live wire

 and 

L1 for the maintained 

     operation

. The L1 wire can be connected to an external switch to 

     control the maintained or non maintained operation of the luminaire. 
     For permanent maintained operation use two wires to power the 
     luminaire, Ν for neutral and L for live wire, and link the L and L1.
7   Refit the removed parts in steps 2 and 3 (mind the correct orientation)
     and the luminaire is ready to operate.

N

N

L

L

External 

switch

Link

Controled operation 
of the illumination source

Permanent 
operation of the illumination source 

N

N

L

L

L1

L1

NOTE: 

LED=

 

Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained

1: 

Maintained (*)

A:

 Including test device

180: 

3 hour duration 

All the types of

 

Easy Light series, are also produced with a new designed crystal with GR-XXX/MAR/CRV code

for example GR-316/30L/MAR/CRV.

1

3

Diffusor 

Reflector

Base plastic

B

A

B

2

A

(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the mains power supply 
or not. 
Non Maintained operation: The luminaire lights its illumination source, only in  power supply’s failure. 

NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery charging to 
perform the nominal autonomy.

4

5

6

N

L

L

1

923316017_09_003

Battery replacement. 
It can be done only by a competent person and after the mains interruption.

1. Follow the step 2 and 3 of the installation procedure.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 5 of the installation procedure) and place it in the position
    of the old one.
4. Follow the step 7 of the installation procedure and power the device.