Page 4 from 4
INSTALLATION INSTRUCTIONS
Base plastic
Cable entry channels
Luminaire mounting holes
1 To install the luminaire you must dismantle it into 3 parts.
2 Place a flat blade screwdriver in the area
Α
to release the diffusor’s
plastic hook.
3
Place a flat blade screwdriver in the area
B
to release the reflector’s
plastic hook.
4 Use the included mounting parts to mount the base plastic.
Pass the mains cable through a cable entry channel. The luminaire
must be connected to a permanent electrical installation to ensure the
immobilization of the cable.
5 Place the battery’s connector to the corresponding connector on the
P.C.B.
6 Connect the mains cables to the respective detachable terminal
block.
Ν for neutral
,
L for live wire
and
L1 for the maintained
operation
. The L1 wire can be connected to an external switch to
control the maintained or non maintained operation of the luminaire.
For permanent maintained operation use two wires to power the
luminaire, Ν for neutral and L for live wire, and link the L and L1.
7 Refit the removed parts in steps 2 and 3 (mind the correct orientation)
and the luminaire is ready to operate.
N
N
L
L
External
switch
Link
Controled operation
of the illumination source
Permanent
operation of the illumination source
N
N
L
L
L1
L1
NOTE:
LED=
Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
1:
Maintained (*)
A:
Including test device
180:
3 hour duration
All the types of
Easy Light series, are also produced with a new designed crystal with GR-XXX/MAR/CRV code,
for example GR-316/30L/MAR/CRV.
1
3
Diffusor
Reflector
Base plastic
B
A
B
2
A
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the mains power supply
or not.
Non Maintained operation: The luminaire lights its illumination source, only in power supply’s failure.
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery charging to
perform the nominal autonomy.
4
5
6
N
L
L
1
923316017_09_003
Battery replacement.
It can be done only by a competent person and after the mains interruption.
1. Follow the step 2 and 3 of the installation procedure.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 5 of the installation procedure) and place it in the position
of the old one.
4. Follow the step 7 of the installation procedure and power the device.