olympia electronics GR-316/15L/MAR Manual Download Page 1

Thank you for purchasing this product of Olympia 
Electronics. A European manufacturer.

GENERAL

These  luminaires  are  suitable  for  marine  and 
offshore  applications  where  emergency  light  is 
needed.  Each  luminaire  must  be  permanently 
connected  to  mains  power  supply.  In  normal 
operation  the  led  strip  lights  and  the  battery  is 
charging.  In    case    of    a    mains    power    supply 
failure    the    luminaire    will    light  the  led  strip 
automatically  in  emergency  mode  (powered  by 
its battery).  When the  mains  power  supply  is  
restored the device turns to normal operation. 

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 4.

Battery Charging

The  battery  charging  is  completely  controlled.  In 
this case, the best possible  battery maintenance 
is  achieved,  as  well  as  the  elongation  of  its 
duration.  When  the  battery  has  completely 
charged, it charges with a maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when  the 
mains power supply fails and battery has lost its 
energy.  During  this  operation  the  luminaire 
enters  the  idle  state  and  battery  consumption  is 
negligible,  in  order  to  be  protected  from  deep 
discharge.

Manual Test

The  manual  test  can  be  conducted  only  if  the 
main power supply and the battery is connected. 
By  pressing  the  test  button  briefly  an  operation 
test  is  initiated.  During  this  test  period  all 
indication LEDs are OFF.

Automatic Test

This  test includes  all  the  operations  that  provide 
the  manual  test  and  is  conducted  automatically 
every  15  days.  In  order  to  be  performed,  the 
main  power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomous Test

The  Automatic  Autonomous  Test  is  conducted 
and measures the luminaire`s back up operation. 
This  test  is  conducted  automatically  every  six 
months.  In  order  to  be  performed,  the  main 
power  supply  and  the  battery  should  be 
connected (the battery should be charged). If the 
battery is not charged, the test is postponed until 
the  battery  is    completely  charged.  If  during  the 
Automatic  Autonomous  Test  the  luminaire’s 
duration  is  lower  than  the  nominal,  then  the 
battery must be replaced. 

Back Up Operation

The  autonomous  duration  of  battery  during 
emergency  mode  is  at  least  the  one  that  is 
stated  in  the  technical  characteristics.  During 
emergency  mode,  a  LED  strip  test  is  also 
performed.

Resetting Errors

Push the Test button for 5 seconds, to extinguish 
all the indicated LED errors.  Then the luminaire 
enters regular operation mode.

Indication  LED  status  (with  connected  mains 
power supply).
Charge 
On: 

Good charge current.

Οff: 

No battery (No charging current 

or disconnected battery).

Lamp Fault 

with L1 connected to L

Page 1 from 4

                         SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LED’s

GR-316/30L/MAR

GR-316/15L/MAR

220-240V AC/50-60Hz

5W / 8VA

3.5W / 7VA

Bayblend FR3010, transparent  polycarbonate

TECHNICAL CHARACTERISTICS

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

180min

24h

Charge, lamp fault, fault indication LED, TEST button

From overcharge and full discharge

IP 40

3.6V/1.5Ah

3.6V/3Ah

  30 white LED’s 

  15 white LED’s 

5 to 40  C

o

Up to 95% 

3 years (1 year for the battery)

770gr.

350 x 134 x 45 mm (CRV 362 x 134 x 58 mm)

  

 

210lm / 210lm 

  

 

105lm / 105lm 

700gr.

High Quality European based Manufacturers

923316017_09_003

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, IEC 60092-306, IEC 60533