INSTALLATION INSTRUCTIONS
Base plastic
Cable entry channels
Luminaire mounting holes
1 To install the luminaire you must dismantle it to 3 parts
.
2
Place a flat blade screwdriver in the area
Α
to release the diffusor’s
plastic hook
.
3
Place a flat blade screwdriver in the area
B
to release the reflector’s
plastic hook
.
4
Use the included mounting parts to mount the base plastic.
Pass the mains cable thru a cable entry channel
and secure it with a
suitable bracket to ensure immobilization of the cable at a distance of
no more than 5cm from the luminaire
’s
cable entry.
5
Place the battery’s connector to the corresponding connector on the
P.C.B
.
6
Connect the mains cables to the respective detachable terminal
block
.
Ν
for neutral
,
L for live wire
and
L1 for the maintained
operation
.
The L
1
wire can be connected to an external switch to
control the maintained or non maintained operation of the luminaire
.
For permanent maintained operation use two wires to power the
luminaire,
Ν
for neutral and L for live wire, and link the L and
L1.
7
Refit the removed parts in steps 2 and 3 (mind the correct orientation)
and the luminaire is ready to operate
.
N
N
L
L
External
switch
Link
Controled operation
of the illumination source
Permanent
operation of the illumination source
N
N
L
L
L1
L1
NOTE:
LED=
Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained
(*)
A: Including test device
90: 1.5 hour duration
180: 3 hour duration
All the types of
Easy Light
series, are also produced with a
new designed crystal with
GR-XXX/CRV
code
,
for example
GR-315/30L/CRV.
1
3
Diffusor
Reflector
Base plastic
B
A
B
2
A
(*)
Maintained operation: The luminaire lights its illumination source, when it is powered by the mains
power supply or not
.
Non-Maintained operation: The luminaire lights its illumination source,
only in power supply’s failure.
NOTE!! After finishing the installation you must power the luminaire at least for 24 hours for battery
charging to perform the named autonomy.
4
5
6
N
L
L
1
Cable
support