olympia electronics GR-315/15L Manual Download Page 4

923316010_09_008

Page

 4

 from

 4

INSTALLATION INSTRUCTIONS

Base plastic

Cable entry channels

Luminaire mounting holes

1   To install the luminaire you must dismantle it to 3 parts

.

2   

Place a flat blade screwdriver in the area 

Α 

to release the diffusor’s 

     plastic hook

.

3

   

Place a flat blade screwdriver in the area 

B

 

to release the reflector’s 

     plastic hook

.

4   

Use the included mounting parts to mount the base plastic.

     

Pass the mains cable thru a cable entry channel

 and secure it with a 

     suitable bracket to ensure immobilization of the cable at a distance of 
     no more than 5cm from the luminaire

’s 

cable entry.

5   

Place the battery’s connector to the corresponding connector on the

     P.C.B

.

6   

Connect the mains cables to the respective detachable terminal 

     block

Ν 

for neutral

L for live wire

 and 

L1 for the maintained 

     operation

The L

wire can be connected to an external switch to 

     control the maintained or non maintained operation of the luminaire

     

For permanent maintained operation use two wires to power the 

     luminaire, 

Ν 

for neutral and L for live wire, and link the L and

 

L1.

7   

Refit the removed parts in steps 2 and 3 (mind the correct orientation) 

     and the luminaire is ready to operate

.

N

N

L

L

External 

switch

Link

Controled operation 
of the illumination source

Permanent 
operation of the illumination source 

N

N

L

L

L1

L1

NOTE: 

LED=

 

Light Emitting Diode

LABELING EXPLANATION:
X: Self contained
1: Maintained

 (*)

A: Including test device
90: 1.5 hour duration 
180: 3 hour duration 

All the types of

 

Easy Light 

series, are also produced with a 

new designed crystal with 

GR-XXX/CRV 

code

for example 

GR-315/30L/CRV.

1

3

Diffusor 

Reflector

Base plastic

B

A

B

2

A

(*) 

Maintained operation: The luminaire lights its illumination source, when it is powered by the mains 

power supply or not

Non-Maintained operation: The luminaire lights its illumination source,

 

only in  power supply’s failure. 

NOTE!!  After finishing the installation you must power the luminaire at least for 24 hours for battery 