background image

220-240V AC/50-60Hz

Bayblend FR3010

transparent 

 

polycarbonate

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specs. see page 2)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY

 (

Ni-Cd

)

CHARGING TIME

INDICATIONS 

CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION (mains/emergency)

ILLUMINATION SOURCE

24h

Battery charging LED

TEST button

From overcharge and deep discharge

5 to 40  C

o

Up to 95% 

3 years 

(1 

year for the battery

)

262 

x 100 x 70 mm 

  White LEDs 

3W / 4VA

IP20

3.6V/1Ah

180 min

590gr.

  30lm/75lm 

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

‘’ 

CLASSIC LIGHT ‘’ SERIES FOR

NON MAINTAINED / MAINTAINED (OPTIONAL) LUMINAIRES

GENERAL

o

These luminaires are used indoors 

(

ta 40 C

)

 where emergency light 

is needed.
Each  luminaire  must  be  permanently  connected  to  mains  power 
supply

In normal operation the led strip lights and the battery is charging.
In case of a mains power supply failure the luminaire will light the led 
strip  automatically  in  emergency  mode.  When  the  mains  power   
supply is restored the device turns to normal operation.

NON MAINTAINED OPERATION

By default the luminaire operates as maintained. The luminaire has a 
possibility  to  operate  as  non  maintained.  To  change  the  maintained 
to  non  maintained  operation  follow  the  relative  instructions  on  page 
2.
  

LED  STRIP  CHECK

 

(

with

 

normal  power  supply  in  maintained 

operation or in emergency operation with the led strip powered

).

By pressing continuously the 

(

led strip check) 

button, an intentional 

disconnection  of  the  led  strip  is  carried  out  and  that  is  indicated  by 
the red indication led. When the button is released the indication led 
will be turned off

.

 So in every disconnection of the led strip, the red 

led will indicate it

INSTALLATION

To install the luminaire follow the installation instructions on page 2.
 

ΑΤΤΕΝΤΙΟΝ

!!!

1.  Operations  for  installation,  maintainance  or  testing  must  be  done 
by authorized personnel only

.

2. 

The device must be connected to the mains power supply through 

a fuse dependent by the total amount of the line’s  power load

.

3. 

It is suggested to check every month the indication LED for battery 

charging, and by 
pushing  the  TEST  button  to  check  the  emergency  circuit.  The  led 
strip should: a) light with bigger intensity as long as the TEST button 
is pressed (maintained operation),
b)  light  as  long  as  the  TEST  button  is  pressed  (non-maintained 
operation).

4. 

It is suggested to check every 6 months the minimum autononous 

duration by disconnecting
the mains power supply

Count the time that  the led strip lights and 

in  case  of  less  time  than  the  minimum  autonomous  duration  the 
battery  must  be  replaced.  If  the  measured  time  is  considerably  less 
than the minimum autonomous duration 

 In case 

 If the luminaire doesn’t work as described above contact 

the installer.

contact the installer.

of battery or led strip replacement, these must be replaced by parts of 
the same type

t i

 

in battery recycling points. Do not 

incinerate.

.

5. 

In  case  of  inactive  use  for  a  period  greater  than  2  months, 

disconnect the battery by pulling out the battery’s connector.

6. 

I

s not allowed to discard batteries in to common trash bins, 

they must be discarded only 

 GR-151-3/L

923151004_09_007

Page

 

1 of

 3

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

Reviews: