In every device there is a double sticker with the UID (Unique Identifier) number. This number is
unique for each device.
After installation the device must not be covered with dust or be painted or anything else happen that will
block the air to get to the sensor. Special attention must be given during the installation and the use of the
device, since the user assumes full responsibility for proper operation afterwards.
-
Adjustable temperature alarm level for maximum flexibility.
-
Automatic fault diagnosis.
SETTING THE ADDRESS
CAUTION !!
The detector has fault diagnosis function, which automatically informs you when detector replacement is
required. This function combined with periodic manual testing ensure maximum security level. It is
suggested to carry out a test every 6 months or after a change in the position of the sensor. A key element
of its proper function is the air to be able to freely circulate inside it. So be careful not to block the openings
of the outer cover. Before the manual testing procedure it is suggested to enable the special “walk in test”
mode from the panel.
The detectors should be placed in the ceiling in visible points without side obstacles, away from places
that are barely ventilated or with strong air currents and water vapor. Each detector covers an area of 50
2
m while the distance between two detectors should not be more than 15m. Also, they must be placed at
least 50 cm away from fluorescent lamps. Cable diameter should be from
. to .
0 5
2 5mm
.
UID:
Each detector must have a unique address, with which it is recognised from the panel. It is forbidden for
two devices in the same loop to have the same address. To set it up you can use the function of changing
address point as described in the user manual of the panel.
INSTALLATION
- Integration of dynamic algorithms for noise and false alarm rejection.
indicator led blinks every 10 sec indicating the connection status with the main panel.
MAINTENANCE & FUNCTIONAL TESTING
Additional features of the device
:
-
360
o
optically visible LED.
Page
2 from
4
5.
:
Connected to the cable’s shield (when shield is used).
4.
Place the detector carefully so that the side marks are on the same position and rotate the detector
clockwise until it locks. Power the device and after 3-5 seconds it is ready for operation.
CONNECTION
1. + IN/OUT:
Connect to
(+L)
of the loop.
3. -
OUT:
Connect to
(
-
L)
of the loop.
3.
Connect the power cables (minding the correct polarity) according to the requirements of the
installation (Figure 1, 2).
1.
Remove the detector from its base rotating to the left till the side marks are aligned.
2.
Fasten the base with the supplied mounting materials (point 5).
2. - IN:
Connect to (-L) of the loop.
4. - R :
External LED connection.
Mounting base
Figure
1
R
+
-R
Installation process
2
Connection
with exterrnal
LED
U
T
/
O
N
I
+
N
-
I
T
U
-
O
Page
3 from
4
eni
t
n
s
g
a
f
d
t
e
n
ta
e
c m
h
1
Indicating
LED
Side marks
Figure
2
Loop
Loop
-R
U
T
/
O
N
I
+
N
-
I
T
U
-
O
Loop
Loop
-R
-R
-R
-R
-R
+L
-L
+L
-L
CN2
U
T
/
O
N
I
+
N
-
I
T
U
-
O
U
T
/
O
N
I
+
N
-
I
T
U
-
O
U
T
/
O
N
I
+
N
-
I
T
U
-
O
U
T
/
O
N
I
+
N
-
I
T
U
-
O
U
T
/
O
N
I
+
N
-
I
T
U
-
O
PE
IN
OUT
921
6
1
60
00_0
9
_00
5
921
6
1
60
00_0
9
_00
5