GENERAL
BS-691
and
BS-690
detectors are used to give
us a quick warning in case there is a natural gas
or LPG gas leak.
The installation must be done by a quilified
personnel. The instructions must be read first
before the installation.
Emergency actions
It is recommended that the following advice
should be given in the event of an alarm sounding
or the smell of gas even without an alarm:
Keep calm, and carry out the following actions,
not necessarily in the order given:
- extinguish all naked flames, including smoking
material;
- turn off all gas appliances;
- do not switch on or off any electrical equipment,
including the gas detection apparatus;
- turn off the gas supply at the gas main control
and/or ( with a LPG supply) the storage tank;
- open doors and windows to increase ventilation;
- do not use a telephone in the building where the
presence of a gas is suspected.
If the alarm continues to operate, even after an
alarm resetting action where appropiate, and the
cause of the leak in not apparent and/or connot
be corrected, vacate the premises and
IMMEDIATELY NOTIFY the gas supplier in order
that the installation may be tested and made safe,
and any necessary repair carried out.
Placement
Depending on the monitored gas, the unit must
be placed 30cm from the ceiling (for methane,
natural gas) or 30cm from the floor (for propane,
butane, LPG). The horizontal distance should
not be more than 4 meters from the probable
gas leak point and the detectors must not be
placed in humid or drafty areas.
It is suggested that the detector is tested for good
operation every 6 months or if it is changed
position.
The unit must should not be sited:
- directly above cooking appliances;
- directly above sink;
- adjacent to extractor fans;
- in any outside location;
- where the environmental conditions are outside
the manufacturers operational specification.
Installation
For the installation of the device first you must
remove the red plastic with a screwdriver as
shown in figure 1 and unscrew the screw in the
middle. Then with the help of figure 2 you can
connect the external devices.
Terminals
+Z, -Z
are used for a fire detection
zone. Up-to 5 conventional detectors can be
installed
.
The connection cable must be at least
2x1mm diameter and no more than 100m in
length. These detectors must operate with 12V
.
Such devices are
BS-655 (
smoke detector
) , BS-
660 (
heat rise detector
)
and
BS-668 (
heat
921691000_
09
_0
16
IP40
3
00gr.
BS-690
BS-691
2 years
Technical characteristics
5
years
220 - 240V AC / 50-60Hz
32
VA
EN 50194, EN 60335, EN 61000-3-2, EN 61000-3-3
145 x 85 x 45 mm
BS-691 Autonomous natural gas-methane detector
BS-690 Autonomous LPG detector
Operation voltage
Maximum consumption
Sensitivity
Indicators
Outputs
Degrees of cover protection
Produced in accordance with
Operation temperature range
Humidity
Fire detection zone
Dimensions
Sensor life time
Weight
Guarantee
5-15 %
L.E.L. Propane
Power LED , alarm LED
,
fault LED
Thank you for your trust in our products
Olympia Electronics - European manufacturer
5-15 %
L.E.L. Methane
Relay
(230
VAC
5Α)
and 12V DC
o
0 to
60
C
Up to 95% relative humidity
No more than 5 detectors 12V