GENERAL

   BS-691 

and

 BS-690 

detectors are used to give 

us a quick warning in case there is a natural gas 
or LPG gas leak.
The  installation  must  be  done  by  a  quilified 
personnel.  The  instructions  must  be  read  first   
before the installation.

Emergency actions

It  is  recommended  that  the  following  advice 
should be given in the event of an alarm sounding 
or the smell of gas even without an alarm:
Keep calm, and carry out the following actions, 
not  necessarily  in the order given:
- extinguish all naked flames, including smoking 
material;
 - turn off all gas appliances;
- do not switch on or off any electrical equipment, 
including  the gas detection apparatus;
-   turn off the gas supply at the gas main control 
and/or ( with a LPG supply) the storage tank;
- open doors and windows to increase ventilation;
- do not use a telephone in the building where the 
presence of a gas is suspected.
If the alarm continues to operate, even after an 
alarm resetting action where appropiate, and the 
cause of the leak in not apparent and/or connot 
be  corrected,  vacate  the  premises  and 
IMMEDIATELY NOTIFY the gas supplier  in order 
that the installation may be tested and made safe, 
and any necessary repair carried out.

Placement

Depending on the monitored gas, the unit must 
be placed 30cm from the ceiling (for methane, 
natural gas) or 30cm from the floor (for propane, 
butane, LPG).   The horizontal distance should 
not  be  more  than  4  meters  from  the  probable 
gas  leak  point  and  the  detectors  must  not  be 
placed in humid or drafty areas.  
It is suggested that the detector is tested for good 
operation  every  6  months  or  if  it  is  changed 
position.
The unit must should not be sited:
- directly above cooking appliances;
- directly above sink;
- adjacent to extractor fans;
- in any outside location;
- where the environmental conditions are outside 
the manufacturers operational specification.

Installation

For  the  installation  of  the  device  first  you  must 
remove  the  red  plastic  with  a  screwdriver  as 
shown in figure 1 and unscrew   the screw in the 
middle. Then with the help of figure 2   you can 
connect the  external devices.

 

Terminals 

 +Z, -Z 

are used for a fire detection 

zone.  Up-to  5  conventional  detectors  can  be 
installed

The connection cable must  be at least 

2x1mm  diameter  and  no  more  than  100m  in 
length. These detectors must operate with 12V

Such devices are 

BS-655 (

smoke detector

) , BS-

660  (

heat  rise  detector

and 

BS-668  (

heat 

921691000_

09

_0

16

IP40

3

00gr.

BS-690

BS-691

2 years

Technical characteristics

years

220 - 240V AC / 50-60Hz

32 

VA

EN 50194, EN 60335,  EN 61000-3-2, EN 61000-3-3

145 x 85 x 45 mm

BS-691       Autonomous natural gas-methane detector

BS-690       Autonomous LPG detector

Operation voltage

Maximum consumption

Sensitivity

Indicators

Outputs

Degrees of cover protection

Produced in accordance with
Operation temperature range

Humidity

Fire detection zone

Dimensions

Sensor life time 

Weight

Guarantee

5-15 % 

L.E.L. Propane

 

Power LED , alarm LED 

,

 fault LED

 

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

5-15 % 

L.E.L. Methane

 Relay

 (230

VAC 

5Α)

 and 12V DC

o

0 to

 60 

C

Up to 95% relative humidity

No more than 5 detectors 12V