I
n every device there is a double sticker with the UID (Unique Identifier) number. This number is
unique for each device.
CAUTION !!
•
After installation the device must not be covered with dust or be painted or anything else happen
that will block the smoke to get to the sensor. Special attention must be given during the
installation and the use of the device, since the user assumes full responsibility for proper
operation afterwards.
- 360
o
optically visible LED.
(Only for BS-655/A & BS-657/A)
-
Automatic fault diagnosis.
-
Compensation of smoke measurements based on ambient temperature which ensures high
precision measurements even under extreme environmental conditions
.
•
Caution! Do not disassembly the detector for cleaning or for any other action.
-Dust compensation and automatic indication when cleaning is required. Stable level of detection
regardless of detector’s working hours.
-
Integration of dynamic algorithms for noise and false alarm rejection.
UID:
Additional features of the device
:
(Only for BS-655/A & BS-657/A)
1
1
1
1
During site works place the plastic cover to the detector (only for BS-655/A & BS-657/A) as shown in
the picture above to protect the device from dust. Remove the plastic cover when all the site works
have finished.
Accessories
1
2
Installation
Dimensional drawing
(
mm)
1
2
3
921655004, 921657002, 921660004_
0
8
_00
6
921655004, 921657002, 921660004_
0
8
_00
6
921655004, 921657002, 921660004_
0
8
_00
6
927600001
927600003
921196000
Note
:
BASE-6012
/
A
Base 12V with relay
BASE-6024
Base
24
V with relay
BASE-196/N
Waterproof base
103
103
103
103
48 55
17
52
Detector
Package Contents
Mounting Accessories
General
Manual
Detector
Base
The
BS-
6
5
7/A
is a conventional smoke detector which integrates functions of optical smoke
and heat detection. It can detect smoke and heat. The detector transitions to alarm state
when the concentration of smoke reaches 0
.107
dB/m or when the temperature reaches
o
57 C. Also, the detector transitions to alarm state when the temperature rises suddenly by
o
32 C regardless of the initial temperature at the beginning of the sudden rise event.
F
or spacings, heights and all mounting points consult the local/national regulation or the
standard
EN 54-14/2018
. The detectors must be placed at least 50 cm away from fluorescent
2
lamps. Cable cross-section should be from
0
.
5
to
2
.
5mm .
The user have to read carefully the following instructions, in order to be properly informed
and keep them for future use.
The
BS-
6
55
/A
is a conventional smoke detector which integrates function of optical smoke
detection. The detector transitions to alarm state when the concentration of smoke reaches
0
.107dB/m.
They are composed by two parts. A plastic base which is placed on the ceiling and the main
body of the detector which fits on the plastic base with a simple rotation to the right. The
o
detectors have a 360 visible led and a remote led driver which are light up constantly in case
of detection of fire, till cancelled from the panel.
They are turned off only when a reset
command is given from the panel. The indicator led blinks every 7 sec indicating the normal
function.
The
BS-
660/A
is a conventional heat detector which integrates
the function of rate-of-rise
o
heat detection. The detector transitions to alarm state when the temperature reaches 57 C.
o
Also, the detector transitions to alarm state when the temperature rises suddenly by 32 C
regardless of the initial temperature at the beginning of the sudden rise event.
INSTALLATION
MAINTENANCE & FUNCTIONAL TESTING
The detector has fault diagnosis and dust compensation functions, which automatically
informs you through the onboard LED when replacement or cleaning actions are required.
The indication LED blinks every 7 seconds. In normal operation it blinks 1 time, if cleaning
action is required it blinks 2 times and if there is a failure it blinks 3 times. After cleaning
procedure it will take about 10 minutes for detector’s working indication to return to normal.
These functions combined with periodic manual testing ensure maximum security level. The
manual testing procedure is carried out by spraying a small amount of smoke into the
detector with an testing spray or a counterpart product. It is suggested to carry out a test
every 6 months or after a change in the position of the sensor. A key element of its proper
function is the air to be able to freely circulate inside it. So be careful not to block the
openings of the outer cover.
You can clean the detector by blowing clean pressurised air from
the outer side of the mesh.
Description
Indications LED Status
(Red LED)
Cleaning Action (2 times)
Normal Operation (1 time)
Detector Failure (3 times)
Blinking
Permanently ON
Alarm
Remove the detector from
its base by rotating counter-clockwise till
the side marks are
aligned.
Fasten the base with the supplied mounting accessories.