Technical Specifications
BS-627
4 zone panel with one extinguish output
Mains power supply
220-240V AC 50/60Hz
10
0VA
One or two 12V Lead acid sealed 7Ah maximum
Stabilized power supply 13.8V / max. 400mA
48 hours with one battery 12
V-7Ah and
72
hours with two batteries
12
V-7Ah
(
without using the
24VM and 24VP outputs)
Two 24V circuits that are monitored for open and short circuit conditions
(maximum current 300mA each). Each output is protected
with a self-reseting electronic fuse.
The output is protected with a self-reseting electronic fuse.
26VDC ( ±3VDC) permanent output with maximum current output 0.3 A
Electrostatically painted metal plate and
ABS - polycarbonate
Consumption
Battery type
Charging circuit
Autonomous duration
Zone circuits
Alarm circuits
Output 24VP
Construction material
2 circuits monitored for short and open circuit conditions for
detection devices (maximum current 35mA).
2 circuits monitored for short and open circuit conditions for
brake glass call points (maximum current 10mA).
26VDC ( ±3VDC) reset interrupted output with maximum current output 0.3 A
The output is protected with a self-reseting electronic fuse.
Output 24VM
The relay 1 and 2 contacts have value of
5Α 250
VAC.
The fault relay contacts have value
1Α 30
VDC.
Under no circumstances should voltages or currents outside limits
be connected. All relays output must be protected with a fuse of the same rating.
Fault relay and
relays 1 and 2
34
5
x
1
2
5
x
3
4
8
mm
38
80gr
ΕΝ 12094-1
, EN 54-2, EN 54-4
Dimensions
Weight
Produced in accordance to
Up to 95% relative humidity
Humidity
o
0 to 50 C
Operation temperature
The total output current ( zones circuits, siren circuit, outputs 24VP, 24VM)
must not exceed 1A.
Imax a=Imax b=1A, Imin=60mA
Total load
Battery cut of voltage
Maximum current
batteries discharge
Battery maximum internal
resistance Rimax
IP 40
1Ohm
1A
21V
Cables for fire rated cables systems such a FIP200,MICC, PYROFIL
Degrees of cover protection
Cables
Extinguish output for actuators and electro valves (maximum 26VA). The circuit
is monitored for open and short circuit conditions
Extinguish output