Page 3 of 4
921471000_0
9
_00
5
Page 2 of 4
921471000_0
9
_00
5
MG ON / MG OFF.
Disable the internal magnetic sensor. It is useful when
the device
co-operates only
with external magnetic contacts.
DEL / INS
:
DEL
ensures
that there are
delays
in
input and output for installed
detectors at the entrance of a building. The
INS
allows the detector to directly cause
the triggering of an alarm if the control panel is armed. This
DIP-
switch
(DEL/INS)
has effect only if the scanner has been programmed in a
natural reaction
from the
control panel (zone with delay
or
zone without delay).
ATTENTION!!
When
zone with delay
is
select
ed
, it is
necessary
the setting of the
BS-468/A
to be done
.
The device can be connected to external magnetic contacts via the CN2 terminal
block
(Figure 3). If a magnetic field is connected to this input, the device sends an
alarm signal to the
control
panel.
If
the contact is not connected to an external
device, at the
cable
terminal
of the CN2, the
n
manufacturer
’s cable
must remain.
N
OTE:
The maximum distance of the external sensor cable is 3 meters !!!
Figure 2
Front panel device (side view)
Alignment marks
Installation should only be carried out by
qualified
technicians. The device
is activated
when
it
is moved away from
the magnet. The main device must be installed in the stationary part of
the window or door and the magnet in the moving part. The detector must be installed
vertically
. It is forbidden to be installed
inside a metal frame (it prevents wireless
communication).
Its use is not
reliabl
e
on an iron door or an iron
window.
To install, follow the procedure below:
1.
Open the lid of the device.
2.
Secure the back plastic to the stationary part of the window or door.
3.
Attach the magnet to the moving part. The distance from the device must be
a
maximum of 5mm when the door / window is closed. The
bottom
of the magnet
must be aligned with the
bottom
of the device (Figure 1). T
he
magnet may be located
either
to the left or
to the
right of the device,
but please pay attention to the alignment
marks
(Figure 2).
4.
Unplug the battery and
let
the lid open,
set
the panel to
ins
tallation
mode
of
wireless
devices (see the manual of the table)
.
5.
Insert the battery into the device and close the lid.
6.
Please,
note that the device has revers
e
installation
protection
for
the battery.
CN2
Figure 3.
Example of con
nection
NC
external
magnetic contacts
with
BS-471
Once the device is connected to the panel's network, remove the battery and wait for
10 seconds. Then press the
tamper
and re
install
the battery. Wait until the
LED
lights
up. Once you release the
t
amper, the
LED
will go out. In this case, the range
test
will
start.
During
range test
the device LED
blink
s every second. The duration of
range
TEST is 60-95 seconds. When it is finished the LED
goes off
and after 2 seconds the
test
result
is displayed
as follows:
Single
blink
:
Strong signal.
The device can be
safely installed
at this point.
Two
blink
s:
Normal signal.
The device can be safely
installed
at this point.
Three
blink
s:
W
eak signal.
It is
recommended
not to
install
the device
at this point.
T
he
re will be communication bettween the device and
the control panel
but there will
be communication
packet
s losses
.
Four
blink
s:
Out of range.
The
device
is forbidden to be placed in th
is point
.
Note
!!
As soon as the TEST procedure is started, it is suggested that the
device
c
over
will
be placed directly in order to simulate the actual communication conditions. The
environment must be also
adapted to the worst possible conditions (eg closed doors).
Finally, in case of
home improvements or renovation
, it is suggested
to perform a
range
TEST
again
.
INSTALLATION
INSTALLATION
DIP SWITCH
ES
DIP SWITCH
ES
CONNECTION WITH EXTERNAL MAGNETIC
CONTACTS
CONNECTION WITH EXTERNAL MAGNETIC CONTACTS
RANGE TEST
RANGE TEST