The above diagram shows the menu for the configuration of a relay:
The parameters are:
DELAY ON
: it is the delay time (max 250 seconds) of the output activation from the moment when the gas
concentration is in the alarm setting.
DELAY OFF
: it is the delay time (max 250 seconds) of the output deactivation from the moment when the
gas concentration returns under the alarm setting.
TIME ON
: it is the maximum time (max 250 seconds) of the output activation when the sensor is in an
alarm condition. After this time the relay is deactivated.
LOGIC CONTACT
: it indicates if the relay works normally activated (Positive Logic) (NC) or normally
deactivated (Negative Logic) (NO).
LATCHED OUTPUT
: it indicates if you want to keep the output active even if the gas concentration returns
under the alarm setting.
Zones configuration
Zones configuration is a useful procedure to unify the procedures when a sensor is activated. When some
sensors belong to the same zone they activate the same relays, as the zone configuration indicates.
This menu is used for the configuration of the zone. First you must choose which zone you want to change
Below is the zone menu
===== ZONES =====
SELECT ZONES
[1..16]: 1
====================
SETUP RELAY
SETUP RELAY
DELAY ON
DELAY OFF
TIME ON
LOGIC CONTACT
LATCHED OUTPUT
SAVE RELAY?
COPY RELAY
INITIALIZE RELAY
NO YES
POSITIVE NEGATIVE
0..250
0..250
0..250
Figure 7: Diagram menu setup relay